background image

REACT

 Pa

Instructions for Use

20200910

Art. 1546075

The document was originally written in Swedish

Symbol key

Symbols on the machine.

This product complies with applicable EU directives

Symbols in this user manual

Warning/Caution!

Risk of crushing

Application area

The product is a pressure regulating damper designed for 
comfort ventilation indoors. The product is used to regulate the 
supply air or extract air in ventilation ducts.
The product may not be used for anything other than its 
intended use.

General

Read through the entire instructions for use before you 
install/use the product and save the instructions for future 
reference. It is not permissible to make changes or modify 
this product other than those specified in this document.

The packaging contains the following items:

1 x REACT P
1 x Measuring tube
1 x Measuring nipple
1 x Instructions for use

Protective equipment

Always use appropriate personal protective equipment 
for the work in question, in the form of gloves, respira-
tors and protective glasses during handling, installation, 
cleaning and service/maintenance.

Electrical safety

Permitted voltage, see “Electrical data”. It is not permissible 
to insert foreign objects into the product’s contactor con-
nections or the electronics's ventilation openings; risk for 
short circuiting.

24 V isolation transformer to be connected should comply with 
the provisions of IEC 61558-1.
Cable sizing must be carried out for cabling between the product 
and the power supply source.
Disconnect the power supply when working on products that 
are not required to run in production.
Always follow the local/national rules for who shall be permitted 
to carry out this type of electrical installation.

Other risk

When the product is voltage fed, the damper will be 

either open or close and there can be a certain risk 

for pinch injuries, for example, on the fingers if these 

are placed between the damper blade and ventilation 

duct when the damper blade rotates. The product’s 

actuator is equipped with a release button that permits 

manual control of the damper blade, always ensure this 

is activated before working on the internal parts of the 

damper. 

If the product is equipped with a spring return actuator there is 

no release button, manual control is performed using the sup-

plied hex key where the damper blade is cranked to the required 

position and then locked. Do not forget to disable the lock after 

working on it.

Handling

•  Always use appropriate transport and lifting devices when the 

product is to be handled to reduce ergonomic loads. 

•  The product must be handled with care.

Installation

•  Moist, cold and aggressive environments must be avoided.
•  Avoid installing the product near a heat source.
•  Assemble the product according to applicable industry  

regulations.

•  Install the product so that it is not accessible by unauthorized 

persons, for example above a suspended ceiling.

•  Install the product for easy access during service/maintenance.
•  Supplement the duct system with a cleaning hatch in the 

vicinity of the product to facilitate cleaning.

•  If the product is mounted above a fixed ceiling, the inspection 

hatch must be located so that the product is accessible for 

inspection.

•  If the product is mounted so that it is possible to gain access 

to the inside of the product, it must be supplemented with 

appropriate protection, for example, a ventilation unit.

•  If the product is mounted in cold areas, the whole product 

must be insulated on the outside against condensation.

•  For installation, the accessory FSR is recommended.
•  The product can be installed position-independent.
•  It is recommended to mount the product so that the   

product’s display is visible.

•  The product must be laid down prior to installation so that it 

cannot fall over.

•  Check to make sure that the product does not have any  

visible defects.

•  Check that the product is properly secured after it has been 

installed.

•  Use the product’s eyes to secure the cables with cable ties.
•  Check that all cables are properly secured in place after  

installation.

•  Check that the actuator/controller is properly mounted in 

place.

Содержание REACT Pa

Страница 1: ...n the damper blade rotates The product s actuator is equipped with a release button that permits manual control of the damper blade always ensure this is activated before working on the internal parts of the damper If the product is equipped with a spring return actuator there is no release button manual control is performed using the sup plied hex key where the damper blade is cranked to the requ...

Страница 2: ...e frame of the building on each side of REACT P Figure 2 Spacing requirements circular ducts quantity Ø before and after the product 1 At least 5 x Ø after the damper supply air 2 At least 5 x Ø before the damper extract air 3 Examples of how spacing can be measured 4 Installation of measurement toppings 1 2 E 1 REACT P 2 FSR Clamp 80 3 6 0 Circular design Size ØD mm Tube length meters A mm B mm C...

Страница 3: ...9 2 15 1600 x 600 16 43 3 15 700 x 700 8 27 6 15 800 x 700 8 30 3 15 1000 x 700 12 34 9 15 1200 x 700 12 40 6 15 1400 x 700 16 45 7 15 H B 104 20 220 20 20 Figure 6 Dimensions mm REACT P rectangular Installation rectangular design Dimension B in the figure and table below is found in the table Rectangular design to the left NOTE Damper spindles must be installed horizontally Straight section befor...

Страница 4: ...n 0 10 and 2 10 V via the edit wheel Pnom Pnom Pres Unit Pres Unit Pmin Pmin Pmax Pmax T Test est Mode Mode Adr Adr Pa Test inH O 10 3 x P n o m P n o m P r e s U n it P r e s U n it P m in P m in P m a x P m a x T T e s t e s t M o d e M o d e A d r A d r P a T e s t in H O 1 0 3 x Addr Used for Modbus for particulars on how to use Modbus see next page Pnom Pnom Pres Unit Pres Unit Pmin Pmin Pmax...

Страница 5: ... 0 100 Addr Used for selecting communication settings for Modbus See table below Pnom Used for setting response delay for the Modbus communication see separate documents How to use Modbus Modbus tables are available in a separate document REACT Modbus m Display number EEPROM value Communication rate Parity Stop bits 13 0 1200 None 2 23 1 1200 Even 1 33 2 1200 Odd 1 4 3 2400 None 2 5 4 2400 Even 1 ...

Страница 6: ...anized sheet steel Z275 Disposal Waste must be handled according to local regulations Product warranty The product warranty or service agreement will not be valid will not be extended if 1 the product is repaired modified or changed unless such repair modification or change has been approved by Swegon AB or 2 the serial number on the product has been made illegible or is missing Trouble shooting T...

Страница 7: ... you know the value of the current pressure Pact Calculation of the current actual value U when you know the value of the current pressure Pact Key to formulas above Y control signal in V DC U actual value signal in V DC Pact current air pressure in Pa inH2 O 10 3 Pmin set min pressure in Pa inH2 O 10 3 Pmax set max pressure in Pa inH2 O 10 3 Performance checks Replacing the damper motor Figure 11...

Страница 8: ... EU EMC and 2011 65 EU RoHS2 The following standards have been observed EN ISO 12100 2010 Safety of machinery General principles for design Risk assessment and risk mitigation EN 60204 1 2006 Safety of machinery Electrical equipment of machines Part 1 Generic standards EN 60730 1 2011 Automatic electrical controls for household and similar use Part 1 Generic standards EN 61000 6 2 2007 Electromagn...

Отзывы: