Swegon REACT Pa Скачать руководство пользователя страница 6

REACT 

P

6

Swegon reserves the right to alter specifications.                           20200910

Cleaning

Ideally, the product should be cleaned in connection with 
the cleaning of the rest of the ventilation system.

Cleaning of electrical components

•  If needed, use a dry cloth to clean the components.
•  Never use water, detergent and cleaning solvent or a 

vacuum cleaner.

External cleaning

•  If necessary use tepid water and a well-wrung cloth.
•  Never use detergent and cleaning solvent or a vacuum 

cleaner.

Internal cleaning

•  When cleaning the ventilation system, the product 

must be dismantled if there are no cleaning hatches 
close to the product.

•  Cleaning equipment such as whisks and the like must 

not be fed through the product.

•  If necessary remove dust and other particles that can 

be present in the product.

•  Never use detergent and cleaning solvent or a vacuum 

cleaner.

Service/maintenance

•  The product does not require any maintenance, except 

for any cleaning when necessary.

•  In connection with a service, mandatory ventilation 

inspection or cleaning of the ventilation system, check 
that the general condition of the product appears to be 
good. Pay particular attention to the suspension, cables 
and that they sit firmly in place.

•  It is not permissible to open or repair electrical    

components.

•  If you suspect that the product or a component is 

defective, please contact Swegon.

•  A defective product or component must be replaced by 

an original spare part from Swegon.

Materials and surface treatment

All sheet-metal parts are galvanized sheet steel (Z275).

Disposal

Waste must be handled according to local regulations.

Product warranty

The product warranty or service agreement will not be 
valid/will not be extended if: (1) the product is repaired, 
modified or changed, unless such repair, modification 
or change has been approved by Swegon AB; or (2) the 
serial number on the product has been made illegible or 
is missing.

Trouble shooting

The product does not communicate over Modbus

•  Make sure that the product is energized.
•  Check the product's Modbus connection.
•  Check the product's communication settings.
•  Check that the product has the right and unique 

Modbus address.

The product shows the incorrect/no air pressure

•  Make sure that the product is energized.
•  Make sure that the product is installed according to the 

recommended distance to disruptions, see “Installation”.

•  Check that there is an air flow.
•  Make sure that the product is correctly oriented in 

terms of air direction. The air flow must follow the 
instructions on the product.

•  Check that the measuring tube is mounted correctly, 

plus for supply air function or minus for extract air 
function.

•  Check that the measuring tubes are undamaged and 

not creased.

•  Check the pressure in the measuring tube. Check the 

pressure in the measuring nipple.

The product does not regulate the air pressure

•  Make sure that the product is energized.
•  Check that the damper motor has not become 

detached from the damper spindle.

•  Check that the damper motor works by pressing in 

the motor’s release button, turn the damper spindle, 
release the release knob and then see whether the 
damper motor starts to move.

•  Check that the product is connected correctly.
•  Check that the product is not force controlled.

Содержание REACT Pa

Страница 1: ...n the damper blade rotates The product s actuator is equipped with a release button that permits manual control of the damper blade always ensure this is activated before working on the internal parts of the damper If the product is equipped with a spring return actuator there is no release button manual control is performed using the sup plied hex key where the damper blade is cranked to the requ...

Страница 2: ...e frame of the building on each side of REACT P Figure 2 Spacing requirements circular ducts quantity Ø before and after the product 1 At least 5 x Ø after the damper supply air 2 At least 5 x Ø before the damper extract air 3 Examples of how spacing can be measured 4 Installation of measurement toppings 1 2 E 1 REACT P 2 FSR Clamp 80 3 6 0 Circular design Size ØD mm Tube length meters A mm B mm C...

Страница 3: ...9 2 15 1600 x 600 16 43 3 15 700 x 700 8 27 6 15 800 x 700 8 30 3 15 1000 x 700 12 34 9 15 1200 x 700 12 40 6 15 1400 x 700 16 45 7 15 H B 104 20 220 20 20 Figure 6 Dimensions mm REACT P rectangular Installation rectangular design Dimension B in the figure and table below is found in the table Rectangular design to the left NOTE Damper spindles must be installed horizontally Straight section befor...

Страница 4: ...n 0 10 and 2 10 V via the edit wheel Pnom Pnom Pres Unit Pres Unit Pmin Pmin Pmax Pmax T Test est Mode Mode Adr Adr Pa Test inH O 10 3 x P n o m P n o m P r e s U n it P r e s U n it P m in P m in P m a x P m a x T T e s t e s t M o d e M o d e A d r A d r P a T e s t in H O 1 0 3 x Addr Used for Modbus for particulars on how to use Modbus see next page Pnom Pnom Pres Unit Pres Unit Pmin Pmin Pmax...

Страница 5: ... 0 100 Addr Used for selecting communication settings for Modbus See table below Pnom Used for setting response delay for the Modbus communication see separate documents How to use Modbus Modbus tables are available in a separate document REACT Modbus m Display number EEPROM value Communication rate Parity Stop bits 13 0 1200 None 2 23 1 1200 Even 1 33 2 1200 Odd 1 4 3 2400 None 2 5 4 2400 Even 1 ...

Страница 6: ...anized sheet steel Z275 Disposal Waste must be handled according to local regulations Product warranty The product warranty or service agreement will not be valid will not be extended if 1 the product is repaired modified or changed unless such repair modification or change has been approved by Swegon AB or 2 the serial number on the product has been made illegible or is missing Trouble shooting T...

Страница 7: ... you know the value of the current pressure Pact Calculation of the current actual value U when you know the value of the current pressure Pact Key to formulas above Y control signal in V DC U actual value signal in V DC Pact current air pressure in Pa inH2 O 10 3 Pmin set min pressure in Pa inH2 O 10 3 Pmax set max pressure in Pa inH2 O 10 3 Performance checks Replacing the damper motor Figure 11...

Страница 8: ... EU EMC and 2011 65 EU RoHS2 The following standards have been observed EN ISO 12100 2010 Safety of machinery General principles for design Risk assessment and risk mitigation EN 60204 1 2006 Safety of machinery Electrical equipment of machines Part 1 Generic standards EN 60730 1 2011 Automatic electrical controls for household and similar use Part 1 Generic standards EN 61000 6 2 2007 Electromagn...

Отзывы: