5
20200910 Swegon reserves the right to alter specifications.
REACT
P
Function
Description
Addr
Enables you to set the actuator's Modbus address, by turning the "edit wheel". It
is possible to set the address from 1 till 247. If you turn the value selector to end
stop "+", the display will show a "2". This makes it possible to select the second
level. If you select the second level, this is indicated in the display by a small circle.
The following functions are available at the second level:
Pres/Unit
Return to previous level
P
min
Not used.
P
max
Not used.
Test
Not used.
Mode
Shows the angle of the rotation (0…255 digital 0....100%)
Addr.
Used for selecting communication settings for Modbus. See table below.
P
nom
Used for setting response delay for the Modbus communication (see separate
documents)
How to use Modbus
Modbus tables are available in a separate document (REACT-Modbus-m)
Display number
EEPROM value
Communication rate
Parity
Stop bits
1
3
0
1200
None
2
2
3
1
1200
Even
1
3
3
2
1200
Odd
1
4
3
2400
None
2
5
4
2400
Even
1
6
5
2400
Odd
1
7
6
4800
None
2
8
7
4800
Even
1
9
8
4800
Odd
1
10
9
9600
None
2
11
10
9600
Even
1
12
11
9600
Odd
1
13
12
19200
None
2
14
4
13
19200
Even
1
15
14
19200
Odd
1
16
15
38400
None
2
17
16
38400
Even
1
18
17
38400
Odd
1
19
3
18
1200
None
1
20
19
2400
None
1
21
20
4800
None
1
22
21
9600
None
1
23
22
19200
None
1
24
23
38400
None
1
3
Limited data length per reading of max. 8 addresses
4
Default setting