REACT
P
2
Swegon reserves the right to alter specifications. 20200910
Installation, torque, dimensions and weights
Figure 3. Dimensions (mm), REACT P circular. The damper can be
installed at an optional angle.
C
Ød
A
B
F
F
Installation – all designs
• The product’s pressure measurement requires spacing
as per the installation figures.
• In unfavourable conditions before or with disruption,
the product’s tolerances cannot be guaranteed.
• Instructions for Use are supplied with the product on
delivery, but can also be downloaded from www.
swegon.com.
Installation – circular version
• Installation is position dependent.
• Can be installed horizontally or vertically.
Figure 1. Installation in the duct system. The ducts must be firmly
fixed to the frame of the building on each side of REACT P.
Figure 2. Spacing requirements, circular ducts, quantity Ø before
and after the product:
1. At least 5 x Ø after the damper (supply air).
2. At least 5 x Ø before the damper (extract air).
3. Examples of how spacing can be measured.
4. Installation of measurement toppings.
1.
2.
E
1. REACT P
2. FSR Clamp
80
36
0°
Circular design
Si
ze Ø
D (
m
m
)
Tu
be l
en
gt
h
(m
ete
rs
)
A (
m
m
)
B (
m
m
)
C (
m
m
)
E (
m
m
)
F (
m
m
)
W
eig
ht
(k
g)
Motor
To
rq
ue
(
N
m
)
100
2
210
27
190
220
50
1.3
10
125
2
210
27
220
220
50
1.4
10
160
2
210
27
260
220
50
1.5
10
200
2
210
27
300
220
50
1.7
10
250
2
210
27
355
220
50
1.9
10
315
4
210
27
415
220
50
2.4
10
400
4
255
5
505
265
50
3.4
10
500
6
255
5
605
275
50
4.9
10
630
6
255
5
735
275
50
6.5
15
Spacing at least 5
Ø
Damper
Measuring
tube
Measurement
tappings
Spacing at least 5
Ø
Damper
Measuring
tube
mm
Measurement
tappings
3.
Damper
Measuring tube
Measurement tappings
Sp
ac
in
g
at
leas
t 5 Ø
4.