GB.GOLDLP.170830
64 www.swegon.com
We reserve the right to alter specifications without notice.
Function
Factory preset value
Adjusted value
OPTIMIZE
X Inactive
Active
Inactive
Active
Upper damper limit (%)
90
Lower damper limit (%)
70
Step size (Pa)
20
Interval (min)
2
Permissible deviation (Pa)
10
Power up start delay (min)
15
Min. pressure (Pa)
50
Max. pressure (Pa)
400
"IQnomic Plus"
I/O module Nr 0
Input/Output
X
Inactive
Active
Inactive
Active
I/O module Nr 3
Ext. monitoring
X
Inactive
Active
Inactive
Active
If active, function:
I/O module Nr 6
Ext. cooling
X
Inactive
Active
Inactive
Active
I/O module Nr 7
All Year Comfort
X
Inactive
Active
Inactive
Active
I/O module Nr 8
Booster air
diffusers
X
Inactive
Active
Inactive
Active
I/O module Nr 9
Preheating
X
Inactive
Active
Inactive
Active
I/O module Nr A
Heating zone
X
Inactive
Active
Inactive
Active
I/O module Nr B
Cooling zone
X
Inactive
Active
Inactive
Active