Min/Max Airflows
7.2 Air flow/Pressure
Basic functions are set at INSTALLATION LEVEL
and values are read and set at USER LEVEL.
Therefore see also Section 9.3, in which the func-
tions for flow/pressure are described in detail.
7.2.1 Readings
Used for performance checks.
7.2.2 Settings
The functions selected at INSTALLATION LEVEL and the
min. and max. airflows of each unit size (see the table
below) determine which values can be set.
Values for airflow (l/s, m3/s, m3/h), pressure (Pa) or input
signal strength (%) can be preset depending on the func-
tion selected.
LOW SPEED
Must always be preset! The value for low fan speed can-
not be higher than the value for high speed. Low speed
can be set to 0, which means that the fan is standing still.
HIGH SPEED
Must always be preset! The value or pressure for high fan
speed cannot be lower than the value for low fan speed.
MAX SPEED
Max speed is only appropriate for functions such as pres-
sure regulation, Heating BOOST or Cooling BOOST. The
value for max fan speed cannot be lower than the value
for high fan speed.
MIN/MAX SPEED
Min/max fan speed is only appropriate for demand-con-
trolled operation. The lowest and highest permissible
flows are preset for each of the fans. This means that the
fans will not operate outside these limits, regardless the
load.
AIR FLOW/PRESSURE
*FLOW/PRESSURE*
READINGS
SETTINGS
*FLOW/PRESSURE*
READINGS
SETTINGS
LOW SPEED
HIGH SPEED
MAX. SPEED
MIN/MAX. SPEED
* When entering settings, round off the values to the nearest
adjustable step.
AIRFLOW
MIN. FLOW
GOLD LP
MAX. FLOW
GOLD LP
SIZE
m
3
/h *
m
3
/s
m
3
/h
m
3
/s
05
300
0.08
1900
0.53
08
720
0.20
2600
0.74