Function
Factory preset values
adjusted value
Priority
Indication
effect
Priority
Indication
effect
0=blocked
LeD
0=Operat. 0=blocked
LeD
0=Operat.
A=A alarm
0=Off
1=Stop
A=A alarm
0=Off
1=Stop
B=B alarm
1=On
B=B alarm
1=On
86
CoolDX, C2 tripped
A
1
0
87
CoolDX, C1 too many restarts
A****
!
1
88
CoolDX, C2 too many restarts
A****
1
1
89
No comm. with press. sensor by SA prefilter
B***
1
0
90
No comm. with press. sensor by EA prefilter
B***
1
0
91
Frost prot. for preheating, below alarm limit
A
1
1
92
Frost prot. for preheating sensor, faulty
A
1
1
93
Preheating sensor faulty
A
1
1
94
Electric air heater for preheating, tripped
A***
1
1
95
Preheating below setpoint
A***
1
1
97
No comm. with ReCO2 pressure sensor
A***
1
1
98
ReCO2 damper motor faulty
A***
1
1
99
Time lock tripped
A
1
1
102 Cooling valve I/O-7 defective
B***
1
0
103 Heating valve I/O-7 defective
A***
1
0
104 Cool. circuit pump I/O-7 tripped
B***
1
0
105 Heat. circuit pump I/O-7 tripped
A***
1
1
106 Cooling water temp. I/O-7 below set point
B***
1
0
107 Heat. water temp. l I/O-7 below set point
A***
1
0
108 Cooling water temp. I/O-7 above set point
0***
1
0
109 Heating water temp. I/O-7 above set point
0***
1
0
110 Cooling water temp. sensor I/0-7 defective
B
1
0
111 Heating water temp. sensor I/0-7 defective
A
1
0
135
SA fan motor blocked
A***
1
1
136
EA fan motor blocked
A***
1
1
137
SA-2 fan motor blocked
A***
1
1
138
EA-2 fan motor blocked
A***
1
1
139
Fluctuation voltage between the phases, SA
A***
1
1
140
Fluctuation voltage between phases, EA
A***
1
1
141
Fluctuation voltage between the phases, SA-2
A***
1
1
142
Fluctuation voltage between phases, EA-2
A***
1
1
143 No communication - CONTROL Optimize
B***
1
0
144 No communication – I/O Module No. A
B***
1
0
145 No communication – I/O Module No. B
B***
1
0
146 No communication – I/O Module No. C
B***
1
0
147 No communication – I/O Module No. D
B***
1
0
148 No communication – I/O Module No. E
B***
1
0
149 No communication – I/O Module No. F
B***
1
0
150 Frost prot. in extra zone, below alarm limit
A
1
1
151 Frost protection sensor in extra zone, faulty
A
1
1