GB.GOLDSK509.091101
We reserve the right to alter specifications without notice.
www.swegon.com 57
a
larm no.
alarm text
Function
Priority
Stop
Indication
LeD
Delay
Resetting
0=blocked 0=In operat.
0=Off
s=seconds
M=manual
A=A alarm
1=Stop
1=On
m=minutes
A=automatic
B=B alarm
164
COOL DXS K1 HAS TRIPPED
No contact reply is obtained for K1 on the I/0 module
of the COOL DXS. The motor protection or pressure
switch may have tripped.
A
0
1
10 s
M
165
COOL DXS K2 HAS TRIPPED
No contact reply is obtained for K2 on the I/0 module
of the COOL DXS. The motor protection or pressure
switch may have tripped.
A
0
1
10 s
M
166
COOL DXS K3 HAS TRIPPED
No contact reply is obtained for K3 on the I/0 module
of the COOL DXS. The motor protection or pressure
switch may have tripped.
A
0
1
10 s
M
167
COOL DXS K1 TOO MANY RESTARTS
COOL DXS Compressor 1 has done too many
restarts.
A
0
1
3 s
M
168
COOL DXS K2 TOO MANY RESTARTS
COOL DXS Compressor 2 has done too many re-
starts. starter.
A
0
1
3 s
M
169
COOL DXS K3 TOO MANY RESTARTS
COOL DXS Compressor 3 has done too many
restarts.
A
0
1
3 s
M
170
COOL DXS FAN HAS TRIPPEDThe thermostatic
contacts in the COOL DXS condenser fan motor may
have tripped.
A
0
1
3 s
M
171
COOL DXS INCORRECT PHASE SEQUENCEThe phase-
sequence protection for the voltage supplied to the
COOL DXS has tripped.
A
0
1
3 s
M
172-
199
SPARE