INSTALLATION
FUNCTIONS
*FUNCTIONS*
teMPeRatURe
AIR FLOW/PRESSURE
FILTER
OPERATION
HEATING
COOLING
HUMIDITY
ReCO
2
IQnomic Plus
ALL YEAR COMFORT
CONTROL Optimize
8 FUNCTIONS
8.1 Temperature
Basic functions can be set at INSTALLATION LEVEL
and values are read and set at USER LEVEL.
IMPORtant!
If you intend to substantially alter the tem-
perature settings, you should first stop the air handling
unit before doing so.
If only GOLD SD supply air handling units are installed,
they require an external room sensor for ERS and extract
air control.
8.2 Temperature Regulation
Select ERS Regulation, Supply air regulation or Extract air
regulation.
If ERS Regulation is selected, select between 1 and 2.
Control sequence for ERS regulation and Supply air regula-
tion:
1. The temperature efficiency of the air handling unit’s
heat exchanger is modulated to provide max. heat
recovery. (Not applicable to GOLD SD without heat
exchanger).
2. After that the air heater, if installed, will begin to
generate heat.
3. If a downstream heating coil is not installed, or if the
its output is not adequate, the supply air fan will be
automatically and variably downspeed-regulated to
convey air at a lower flow rate. (If the unit is a GOLD
SD without heat exchanger, this function can be deacti
vated).
A neutral zone can be preset, which allows a lower supply
air temperature setpoint before regulation to a lower flow
rate begins. See 8.3.4
When the supply airflow is regulated to a lower rate, the
heat exchanger will have ”excess heat”, i.e. warm extract
air, giving it capacity to maintain the supply air tempera-
ture required.
As the supply airflow is regulated to a lower rate, the air
pressure in the premises will become negative and this will
instead cause outdoor air to be sucked in through leak-
age spots such as doors and windows. This outdoor air
will then be heated by the ordinary heating system of the
premises. (Not applicable if only a GOLD SD supply air or
extract air handling units are installed)
Downspeed regulation to lower the airflow rate occurs
from the current preset flow (high speed or low speed),
down to half of this flow rate. The degree of regulation
to a lower rate is also limited by the min flow setting of
the unit. When preset flow for low speed is near the min
flow rate, the effect of this regulation to a lower rate will
be small.
Control sequence for Extract air regulation:
1. The temperature efficiency of the air handling unit’s
heat exchanger is modulated to provide max. heat
recovery. (Not applicable to GOLD SD without heat
exchanger).
2. After that, the re-heating coil, if installed, will begin
to generate heat.
* TEMPERATURE *
teMPeRatURe ReG
TEMP.REG. Xzone
OUTDOOR TEMP COMP
SUMMER NIGHT COOL
INTERM. NIGHT HEAT
MORNING BOOST
SETPOINT TEMP DISPL
EXTRA REG. SEQUENCE
EXT. SENSORS
Important! The appearance
of the menus varies
depending on the type of air
handling unit and functions
selected.