GB.GOLDSK509.091101
We reserve the right to alter specifications without notice.
www.swegon.com 75
a
larm
n
o.:
Function
Factory preset value
adjusted value
Priority
Indication
effect
Priority
Indication
effect
0=blocked
LeD
0=Operat. 0=blockedt
LeD
0=Operat.
A=A alarm
0=Off
1=Stop
A=A alarm
0=Off
1=Stop
B=B alarm
1=On
B=B alarm
1=On
1
External fire alarm tripped
A****
1
1*
2
Internal fire alarm tripped
A****
1
1*
3
Frost protection below alarm limit
A****
1
1*
4
R.hx. speed monitor tripped
A
1
0**
5
Frost protection sensor defective
A****
1
1*
6
Supply air temp sensor defective
A
1
1
7
Extract air temp sensor defective
A
1
1
8
Outdoor air temp sensor defective
B
1
0
9
No communication to r.hx. controller
A ***
1
1
10
No communication to SA frequency conv.
A ***
1
1
11
No communication to EA frequency conv.
A ***
1
1
12
Over current in SA frequency conv.
A ***
1
1
13
Over current in EA frequency conv.
A ***
1
1
14
Under voltage in SA frequency conv.
A ***
1
1
15
Under voltage in EA frequency conv.
A ***
1
1
16
Over voltage in SA frequency conv.
A ***
1
1
17
Over voltage in EA frequency conv.
A ***
1
1
18
Over temperature in SA frequency conv.
A ***
1
1
19
Over temperature in EA frequency conv.
A ***
1
1
20
No communication to SA-2 frequency conv.
A ***
1
1
21
No communication to EA-2 frequency conv.
A ***
1
1
22
Over current in SA-2 frequency conv.
A ***
1
1
23
Over current in EA-2 frequency conv.
A ***
1
1
24
Under voltage in SA-2 frequency conv.
A ***
1
1
25
Under voltage in EA-2 frequency conv.
A ***
1
1
26
Over voltage in SA-2 frequency conv.
A ***
1
1
27
Over voltage in EA-2 frequency conv.
A ***
1
1
28
Over temperature in SA-2 frequency conv.
A ***
1
1
29
Over temperature in EA-2 frequency conv.
A ***
1
1
30
Ext. EA/room temp sensor defective
A ***
1
1
31
Ext. outdoor temp sensor defective
B ***
1
0
32
Plate heat exch. sensor faulty
A ***
1
0
33
Coil heat exch. sensor faulty
A ***
1
0
34
Over current in r.hx. controller
A ***
1
1
35
Under voltage in r.hx. controller
A ***
1
1
36
Over voltage in r.hx. controller
A ***
1
1
37
Over temperature in r.hx. controller
A ***
1
1
38
R.hx pressure drop above alarm limit
B ***
1
0
39
El.heating coil tripped
A ***
1
1
40
Extract air temp below alarm limit
A ***
1
1
41
Supply air temp below setpoint
A ***
1
1
42
Ext.alarm No.1 tripped
A ***
1
1