background image

10

VAR

Swegon reserves the right to alter specifications. 

20111011 

www.swegon.com

VAR 2

Checking the performance

Start

A 3-minute warm-up period is required when you switch 
on the voltage (cold start) before the controller will oper-
ate normally.

Checking the min. airflow

This can be done by disconnecting the control signal cable 
from terminal 3. The damper will then move to the closed 
position. This position is conditional on the bearing pres-
sure and the preset min. airflow rate. Measure the voltage 
U and calculate the airflow using Formula 2 on page 7.

Checking the max. airflow

Use the room thermostat or some other microprocessor 
substation equipment to override the system so that the 
control voltage will be a 10 V input on terminal 3. As an 
alternative you can short circuit between terminals 2 and 
7. This will steer the controller to the preset max. airflow 
setting. The damper will move to the open position. 
Measure the pressure in the pressure tapping and calcu-
late the airflow using the K-factor for the relevant size. 
Measure the voltage U and calculate the airflow using 
Formula 2 on page 7.

The VAR 2 as a constant-flow controller 

The VAR 2 can be used as a constant-flow controller in 
two ways. It is most appropriate to use the min. flow 
setting as the set point for the constant airflow. 24 V AC 
only should be connected to cable pair 1 and 2.  You can 
also use the max. airflow setting, however you must then 
provide for a short circuit between cables 2 and 7. See 
under: Checking the max. airflow.

Trouble shooting

Incorrect polarity on control signal zero conductor

It is important that the neutral conductor follows the 
entire chain of connections from thermostat to control-
ler. Check this by measuring the control voltage between 
cables 1 and 3 on the VAR. Correctly wired it should be 
possible to vary the signal between 0-10 V DC.  If incor-
rectly wired the signal will be ~  8 - 14 V DC. The follow-
ing values apply to the RTC: ~ 5-10 V DC.

Start menu of the VAV controller

Start:

Connect the cable provided to the VAV 
controller 

Reply:

The type of controller connected appears in 
the display window 

"OK" button

The serial number of the controller is shown

"+" button

The program version of the controller is 
shown

Select fun-
ction:

▼▲

 Navigate forward/backward to scroll 

between the various menu positions (see 
table below)

Exit:

Disconnect the cable to the VAV controller

PC-TOOL

A PC-based program can be used for checking performance 
and changing settings. PC-Tool version 3.0 or later is required. 
This is simpler since contact with the controller takes place 
with a separate bus cable, no reconnection is required (Plug 
And Play). Contact Swegon’s representative for further info.

Configuration menu of the ZTH-GEN

Start:

Hold the (OK) button depressed and at the 
same time connect to the VAV controller.

Answer:

"Configuration menu"appears in the display 
window 

Select setting

Press the 

 button (see selection below)

Choice of 
language

German

*

/English

Choice of unit

m

3

/h

 *, l/s, cfm

Voltage

DC/AC 24 V (shows current supply voltage)

MP test

Shows the pulse train in the network (for 
system integrator)

Expert mode

0 */ 1 (provides expanded access to settings)

Advanced 
mode

0 */ 1 (provides expanded access to settings)

Exit

Via menu selection (returns automatically to 
the mode for configuring the VAV controller) 
or for removing the connection to the VAV 
controller. The selected settings are automa-
tically stored in the ZTH.

Airflow does not correspond

This is almost always due to that the requirements for 
lengths of straight ducting upstream/downstream of the 
VAR have not been met. If the ducting deviates from these 
requirements, the error can be as much as 20%. The flow 
measurement sensor may become fouled in systems with 
considerable dusty air (most often extract air systems).
This however doesn’t occur until the system has been 
operating for 3-5 years. The sensor can be cleaned by 
blowing it with clean air in the opposite direction, i.e. in 
the minus tube connection. We recommend compressed 
air in a low-pressure aerosol tube. The duct must also be 
cleaned so that the flow measurement stick and the pres-
sure tappings are not clogged.

Содержание BELIMO ZTH-GEN

Страница 1: ...ce 20111011 Contents Installation Wiring guides Pages 2 7 Commissioning Flows Pages 7 8 How to use the VAR 1 Pages 9 10 How to use the VAR 2 Pages 10 11 How to use the VAR 4 Pages 12 13 How to use the VAR 5 Page 13 Dimensions and weights Page 14 ...

Страница 2: ... mm length of straight duct 2 Sound attenuator with sound baffles Figure 4 Installation demands a length of straight duct A 2 x B 1 VAR Variable flow commissioning damper Figure 2 Variable flow commissioning damper VAR 1 with FSR fixing clamp 2 and sound attenuator 3 If the sound attenuator is equipped with a sound baffle or centre body it should be installed at a distance 2 x the duct diameter ØD...

Страница 3: ... airflow Wiring diagrams Figure 8 Wiring diagram for VAR 2 Figure 7 Wiring diagram for VAR 1 Colour codes 1 Black 2 Red 3 and 5 White Insulate any conductors not in use VAR 1 Belimo compact Supply voltage 24 V AC 20 50 60 Hz Supply voltage 24 V DC 10 Controller and motor 6 VA Input 3 resistance 100 kOhm Input 3 control signal 0 10 alt 2 10 V DC Output 5 true value 2 10 V DC max 0 6 mA Ambient air ...

Страница 4: ...SWN LMV D3 MP SWN NMV D3 MP SWN VRD3 SWN VAR VAR LMV D3 MP SWN NMV D3 MP SWN VRD3 SWN LMV D3 MP SWN NMV D3 MP SWN VRD3 SWN VAR VAR RTC RTCT Room thermostat Figure 10 The diagram shows how to wire the VART room ther mostat with simultaneous control of the extract air The figure also shows an alternative with RTCT duct temperature sensor 1 VAR Supply air 2 VAR Extract air CO2 and temperature control...

Страница 5: ...mo Compact 1 VAR Supply air 2 VAR Extract air Y LMV D3 MP SWN NMV D3 MP SWN LMV D3 MP SWN NMV D3 MP SWN DETECT O VAR VAR Y U U DETECT O VAR VAR Figure 14 Wiring diagram VAR 4 Siemens 1 VAR Supply air 2 VAR Extract air VRD2 Ser Actuator VRD3 Figure 13b Jumper configuration VAR 2 Belimo Universal VRD2 DETECT O controls to fully open damper VRD3 DETECT O controls to preset flow for V max Figure 13a W...

Страница 6: ...th VART 5 as master Figure 16 The diagram shows the connections between master slave unit In this wiring configuration the VAR slave controller should be set to a flow range of 0 100 of the nominal airflow 1 VAR Supply air 2 VAR Extract air LMV D3 MP SWN NMV D3 MP SWN VRD3 SWN LMV D3 MP SWN NMV D3 MP SWN VRD3 SWN DETECT O VAR VAR RTC VAV regulation with room thermostat and presence detector 1 VAR ...

Страница 7: ...direction should always be such that the damper is fitted down stream of the flow measuring device The unit s rating plate includes air direction arrows Control signals All the electronic VAR devices are designed for a signal range of 0 10V DC Any deviation from this range is indicated on the product rating plate If a direct wired room thermostat is used for controlling the airflow requirements th...

Страница 8: ... 5Pa Qnom max 120Pa K factor 1000 x 400 762 3735 341 0 1200 x 400 915 4480 409 0 1400 x 400 1069 5236 478 0 1600 x 400 1221 5981 546 0 500 x 500 479 2344 214 0 600 x 500 575 2815 257 0 700 x 500 671 3286 300 0 800 x 500 767 3757 343 0 1000 x 500 959 4699 429 0 1200 x 500 1149 5631 514 0 1400 x 500 1342 6573 600 0 1600 x 500 1534 7515 686 0 600 x 600 691 3385 309 0 700 x 600 807 3955 361 0 800 x 60...

Страница 9: ...r If this is not done you will destroy the output on the control equipment The damper will move to the open position Measure the voltage U and calculate the airflow using Formula 2 on page 7 Figure 21 Shows how to connect a voltmeter for checking the true value Figur 22 ZTH GEN hand held micro terminal VAR 1 as a constant flow controller VAR 1 can be used as a constant flow controller in two ways ...

Страница 10: ...u of the VAV controller Start Connect the cable provided to the VAV controller Reply The type of controller connected appears in the display window OK button The serial number of the controller is shown button The program version of the controller is shown Select fun ction Navigate forward backward to scroll between the various menu positions see table below Exit Disconnect the cable to the VAV co...

Страница 11: ...s 51 119 l s Qmax Qmax Qnom 119 170 0 70 70 Qmin Qmin Qnom 51 170 0 30 30 Qnom is read from Table 1 on page 9 Enter the settings directly in the controller No external instrument is needed but the settings can also be adjusted with Belimo s instrument ZTH GEN Configuration menu ZTH GEN Start Hold the OK button depressed and at the same time connect to the VAV controller HW Version SW Version Indic...

Страница 12: ...he controller will lose its positioning capability and you will have to de energize the unit for at least five seconds to remedy the situation If you want to test or force the commissioning damper use the jumper connections shown below or use the AST 10 hand held micro terminal Checking the min flow If possible zero volt is transmitted from the room unit or the main control system If this possibil...

Страница 13: ...n nect it to the same terminal that the motor conductors are connected to See the wiring diagram for the AST 10 supplied in the instrument case 1 Press on Vmax change to the required value with the buttons press SET to confirm the change 2 Press on Vmin change to the required value with the buttons press SET to confirm the change 3 With Y you can read the control voltage set point transmitted from...

Страница 14: ...1 2 6 3 9 125 124 472 245 61 77 180 401 2 9 4 0 160 159 472 285 61 60 215 401 3 3 4 8 200 199 472 335 61 40 255 401 4 0 5 8 250 249 522 395 61 15 305 452 4 9 7 8 315 314 552 465 61 370 452 6 5 9 7 400 399 684 553 61 462 614 10 7 14 9 500 499 810 653 61 565 740 15 7 21 3 250 Figure 34 VART 5 rectangular Figure 33 VAR 4 circular Figure 32 VAR 1 IR rectangular insulated casing Figure 31 VART 5 circul...

Отзывы: