= 100 Pa
Figure 27. Knob seen from below
Figure 26. Knob placement
K-factor table
Knob
19
23/03/2019 Swegon reserves the right to alter specifications.
PARASOL
Zenith b
0
10
20
30
40
50
60
70
80
90
D
E
p = [Pa]
i
( )
k
q
2
p
i
[Pa]
q [l/s]
k
=
k-factor
i
√
q = k· p [l/s]
i
√
p = k
q
K-factor setting
You can easily set the required k-factor with the help of
the knob located on the short side opposite the short side
with water connections.
Example: To achieve the required flow of 25 l/s at
100 Pa, requires k-factor 2.5
A
:
Find the product’s length and air connection diameter
from left-hand side of the k-factor table.
B
:
Read the required k-factor on the row in question.
C
:
Follow the vertical row and read the number of degrees
at the bottom.
D
:
Loosen the screw located in the knob’s groove (the
knob then moves to the fully open position, 90°) Turn
the knob until the marking “D” reaches the required
number of degrees.
E
:
In the example from the table for a PARASOL Zenith
with length 1200, ø125, k-factor 2.5, turn the knob to 44°.
The right to design changes is reserved.
Current data according to product selection program .
81878101
p
q=k*
degrees
10 20 30 40 50 60 70 80 90
max
k-factor PARASOL Zenith
1200
d125
600
d125
d160
1200
d160
1800
d200
1 2 3 4 5 6 7 8 9 10 11 12 13
1 2 3 4 5 6 7 8 9 10
0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5
0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5
C
A
B