Easy installation
PARASOL Zenith is built on a platform with very compact
dimensions. In many cases the design permits installation
in the existing T-bar system without the need of dismantling,
provided that there is at least 300 mm of space between
the suspended ceiling and the joists.
The slim design and lightweight result in simpler handling,
especially when handling the products on the site, which
gives less handling damage and a better working
environment. Parasol Zenith’s compact units fit most
common modular dimensions and fit most suspended
ceiling system on the market. As standard the units
include four mounting brackets. These are adjustable
+/- 20 mm in both directions and in doing so create the
adjustment range normally required during installation.
Figure 15. Installation in existing T-bar system
Hygienic design
PARASOL Zenith is available as a variant with a fold-out
coil for easy access to the complete heat exchanger.
A dust-free environment is especially important in rooms
with elevated hygiene demands. Over time large amounts
of room air pass through Parasol Zenith’s coil (heat
exchanger). Dust particles, which fasten on the coil, not
only result in less capacity, but also fail to comply with
the hygiene requirements that apply to the room. Parasol
Zentih has, as an option, the possibility of fold-out coils to
meet these requirements.
In addition to normal cleaning, by wiping off dust from
the white painted surfaces exactly as you clean other
surfaces in the room, the option of more thorough
cleaning is now possible.
1. It is recommended to vacuum clean the coil several
times a year. More frequently in a room with a lot of
textiles and a high rate of air change. The face plate
is opened or dismantled to gain access to the coil, see
figure 16.
2. In environments with elevated hygiene demands
additional cleaning of the comfort module may be a
requirement. The use of flexible connection hoses and
the possibility to fold out the coil permits cleaning of
the top of the coil in these instances, see figure 17.
Figure 16. Removing the face plate to access the coil
Figure 17. Removing the face plate and folding out the coil for
accurate cleaning in the event of high hygiene requirements.
Note! requires the product to be ordered with the accessory, fold-
out coil, and that flexible connection hoses are used on the water
side.