Operations
60 Modular UPS 25KVA~900KVA User Manual
ESC Mute
Transfer to Bypass
B
I
Fig.5-4 Battery maintenance
2.
Auto discharging. The system can maintenance the battery automatically when the
setting is done. The setting procedures are as follows.
(a) Enable battery auto discharge. Enter the “CONFIGURE” page of the menu
Setting, tick the “Battery Auto Discharge” and confirm (This needs to be done by
factory).
(b) Setting period for battery auto discharge. Enter the “BATTERY “page of the
Setting (See Fig.5-5), Set the period time in the item “Auto Maintenance Discharge
Period” and confirm.
6480
Fig.5-5 Setting period for battery auto discharge
Warning
The load for the auto maintenance discharge should be 20%-100%
,
if not, the system will not start
the process automatically
.