P Line Maritim HMI
Installation and Commissioning
23
2.3
Connecting the Device
2.3.1
Supply Voltage
The supply voltage is supplied via pin strip X1. A suitable socket strip is supplied.
Refer to the technical data for the permissible supply voltage of the operating de-
vice.
Connector in the operating device: 3 pin pin strip
Use the following procedure to connect the device to the supply voltage:
1. Strip approx. 30 mm (1.181") off the outer cable sheath and approx. 5 mm
(0.197") off the wires.
Figure 2-14 Preparing the cable
2. Fit the wires with wire end ferrules and connect the wires to the socket strip.
3. Plug the socket strip onto pin strip X1.
4. Secure the socket strip in place with a screw-type locking to prevent it from
slipping out.
The device has reverse polarity protection. In case of wrong polarity, the device
will not operate.
This is a protection class I device. For safe operation, safety extra-low voltage
(SELV) in accordance with DIN EN 61131 must be used for the supply voltage.
Table 2-1 Pin assignment supply voltage
Pin
Designation
Function
1
Noiseless ground / functional earth ground (FE)
2
0 V
Supply voltage 0 V (GND)
3
24 V
Supply voltage
24 V
DANGER: Hazardous voltages
Hazardous voltages can exist inside electrical installations that can pose a dan-
ger to humans. Coming in contact with live parts may result in electric shock!
NOTICE: Damage
Cables with finely stranded copper conductors with a minimum cross-section of
0.75 mm² (18 AWG) and a maximum cross-section of 2.5 mm² (14 AWG) must
be used for the supply voltage.
You must adhere to the following torques at the connector:
Screw connection of terminal blocks: 0.22 Nm (minimal) to 0.25 Nm (maximum)
Screw flange: 0.3 Nm (maximum)
Содержание TPEM070ZGW
Страница 5: ...M Line Maritim HMI Overall Table of Contents 5 6 10 TPEM150ZGX 71 7 Ordering Data 73 A Index 75...
Страница 6: ...Overall Table of Contents M Line Maritim HMI 6...
Страница 32: ...Control and Display Elements P Line Maritim HMI 32...
Страница 48: ...Interfaces of the Device P Line Maritim HMI 48...
Страница 52: ...Maintenance and Servicing P Line Maritim HMI 52...
Страница 74: ...Ordering Data P Line Maritim HMI 74...
Страница 76: ...76...
Страница 77: ......