APPENDIX A -- Command Reference
Command
Response
Comments
?!
a<CR><LF>
Request Address
Note: SDI-12 AnalogPlus module should be the
only sensor on the SDI-12 bus when this
command is given, otherwise this will cause
response from all SDI devices resulting in
communications collision
a!
a<CR><LF>
Acknowledge active
aI!
Send Identification
13
supports SDI version 1.3
commands
SUTRON
manufacturer
1248-1
model number
1.0
hardware revision level
sssssss
reserved
Svvv
the software revision
aAb!
b: new address
b<CR><LF>
Set SDI-12 address
Voltage Measurement on AN1 through AN4
aM!
aC!
a00034<CR><LF>
a000304<CR><LF>
A successive aD0! Command returns
a+w+x+y+z<CR><LF>
w : Voltage on AN1 w.r.t. ground
x : Voltage on AN2 w.r.t. ground
y : Voltage on AN3 w.r.t. ground
z : Voltage on AN4 w.r.t. ground
if it is aMC or aCC command, then CRC is
appended after z
Configurable Measurements
aM1!, aC1!
aM2!, aC2!
aM3!, aC3!
aM4!, aC4!
aM5!, aC5!
aM6!, aC6!
aM7!, aC7!
aM8!, aC8!
aM9!, aC9!
a0tt1<CR><LF> if M cmd
a0tt01<CR><LF> if C cmd
where tt is represents number of
seconds that depends upon Vref time,
SW'D voltage time & Averaging time for
analog measurements, and depens on
measurement-time
for
digital
measurements
A successive aD0! Command returns
a+v<CR><LF>
Where
,
v : Measurement result based on what is
configured for this measurement number
if it is aMC or aCC command, then CRC is
appended after v
Verify Command
aV!
(To clear the values, use extended command
aXDV+1!)
a00015<CR><LF>
A successive aD0! Command returns
a+p+c+w+i+u<CR><LF>
p: Number of power-up resets
c: Number of clock monitor resets
w: Number of watchdog resets
i: Number of Illegal instruction resets
u: Number of unknown resets