![SurgeX SX-1115ip-X Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/surgex/sx-1115ip-x/sx-1115ip-x_user-manual_1407299034.webp)
iControl Manual
33
SPECIFICATIONS
Load Rating:
15/20 Amps at 120 Volts (SX-1115ip-X/SX-1120ip-X)
Power Requirement (no load):
4 Watts
Surge Let-through Voltage (6000 Volt surge):
0 Volts
UL 1449 Adjunct Classification Test Results:
1000 surges, 6000 Volts, 3000 Amps, B3 pulse; measured
suppressed voltage, 170 Volts; no failures
Federal Guidelines:
Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode (50 Ohm load):
40 dB @ 100 KHz, 50dB @ 300 KHz, 50 dB @ 3 MHz, 50 dB @
30 MHz
EMI/RFI Filter, Common Mode (50 Ohm load):
18dB @ 300 KHz, 30 dB @ 1 MHz, 50 dB @ 5 MHz, 50 dB @
20 MHz
Maximum Applied Surge Voltage:
6000 Volts *
Maximum Applied Surge Current:
Unlimited (due to current limiting) *
Maximum Applied Surge Energy:
Unlimited (due to current limiting) *
Endurance (C62.41-1991 category B3 pulses):
1 KV > 500,000; 3 KV > 10,000; 6 KV > 1000
Undervoltage Shutdown:
Adjustable from 90 Volts to 105 Volts
Overvoltage Shutdown:
Adjustable from 135 Volts to 150 Volts
Network Port:
10/100 Base T Ethernet connection on Female RJ-45
Modem Port:
V.92 and below on Female RJ-11 (for models with internal modem option)
Serial Port:
115,200 bps on Female 9-pin D-subminiature
Dimensions:
19” W x 12.25” D x 1.75” H (Single Rack Space)
Weight:
13.0 lb.
Temperature Range:
5C to 35C
Humidity Range:
0% to 95% R.H. Non-condensing
Agency Listings:
ETL and cETL (UL 1449, 3rd Edition; CSA C22.2 No.8-M1986, R2000)
* 1.2 x 50 microsecond industry standard combination wave surge as per IEEE C62.41
*CAUTION: Do not install this device if there is not at least 10 meters (30 feet) or more
between the electrical outlet and the electrical service panel.