![SurgeX SX-1115ip-X Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/surgex/sx-1115ip-x/sx-1115ip-x_user-manual_1407299018.webp)
iControl Manual
17
get voltage
Get the measured voltage of the local iControl.
Yes
get device <#1
‐
#16/devname> voltage
Get the measured voltage of the selected iControl.
set main a vcalibration <nnn.nn>
Set the voltmeter calibration. From 105.00 to 150.00 in 0.01 V
increments.
Yes
get voltage alarm
High and Low alarms are used to monitor voltage conditions and send
an alert by email, SNMP and syslog when the high or low thresholds
are exceeded.
Adjustable in 1 V increments.
Yes
Highalarm:
135-150 V
Lowalarm:
90-105 V
get device <#1
‐
#16/devname> voltage alarm
set main a hvalarm <nnn>
set device <#1
‐
#16/devname> main a
hvalarm <nnn>
set main a lvalarm <nnn>
set device <#1
‐
#16/devname> main a
lvalarm <nnn>
get console
Displays the current console configuration, Timeout, and Baud Rate.
Yes
set console timeout <30
‐
3600/disable>
Console can be set to automatically logout with no activity for 30
seconds to 1 hr in seconds, or disabled.
Yes
120
set console baudrate
<400/4800/9600/19200/38400/57600/115200>
The baud rate of the serial port.
400,4800,9600,19200,38400,57600,115200 bps
Yes
115200
get modem
Gets the current settings of the modem. (modem models only)
Yes
set modem countrycode <countrycode>
Sets the modem country code. (modem models only)
See Appendix for a list of country codes.
Yes
181 (USA)
set device <0
‐
16>
Get / Set the device ID for cluster applications. Set a device ID of 0 for
single iControl applications. A device ID of 1 makes the unit a master,
and a device ID of 2-16 makes the iControl a remote in cluster
configurations. These commands are only valid when directly
connected to the iControl, rather than as remote units in a cluster.
Yes
0
get device