Caution:
Mounting Option:
Wiring:
This product must be installed by a qualified electrician. Use approved wiring connectors. Ensure
power supply has been turned off before installation.
Inside a Junction Box
Outside a Junction Box
The wiring diagram shows two power packs connected together to control lighting. Adjust the number of
device according to your requirement. Refer to Maximum Load and Power Supply to the Sensor in the
Specification section to determine the number of lights and sensors that a power pack could support.
AC
AC
Line
Line
DC
Line
DC
Line
Note: A 5cm EMT nipple could be used for the external mount. Ensure the wires are tightly fastened to the connectors and the wiring is not exposed.
Note:
i.
Occupancy sensors should only be implemented based upon Auto On/Off function [Blue Wire] or Auto Off Only function [White Wire], not both
ii. Where there are conflicts in the controls, the order of priority applied (high to low) include: Toggle On/Off [Brown Wire] >> System Override Off [Orange Wire] >> System Override
On [Yellow Wire] >> Auto Off Only [White Wire] or Auto On/Off [Blue Wire]
iii. Power packs can be added by connecting the control and black (-) wires of each power pack together. Do not connect the red (+) wires
Implementation Options:
: Connect occupancy sensor A to the power pack as shown in the wiring diagram
: Connect occupancy sensor A and momentary switch to the power pack. This function may be required to turn light off when the room is
occupied during presentations. The light will remain in the selected state while presence is detected. The power pack reverts to automatic mode when presence is no longer detected
: Connect occupancy sensor B and momentary switch to the power pack
: Connect the Normal Open relay from a timer or a lighting control system to the power pack. Closing the relay enforces the override.
: Connect the momentary switch to the power pack. Connection of an occupancy sensor is not mandatory
Automatic Switching On/Off
Automatic Switching with Manual Override
Manual Switching with Automatic Off Only
System Override On/Off
Multi-Location Switching
PS-212 | PS-224
Installation
SURE
N
©
2011 SUREN Systems, Ltd.. All rights reserved. SUREN
™
, HDIR
™
are trademarks of SUREN.
SUREN Part no.: N-ML00-0044-03-1
Rev.1
Printed in China
w w w . s u r e n s y s t e m s . c o m
Sensor(s)
Sensor(s)
Light(s)
Light(s)
Load
Load
Red
Black
Blue
White
Yellow
Orange
Brown
Red
Black
Blue
White
Yellow
Orange
Brown
+
-
Auto On/Off
Auto Off Only
System Override On
System Override Off
Toggle On/Off
Live Black
Neutral White
Live Black
Neutral White
Live
Neutral
Live
Neutral
Momentary
Switch(es)
Timer or Lighting
Control System
Blue Blue
Blue Blue
Power
Pack
Power
Pack
A (i) B
A (i) B
(ii)
(iii)