Sur-Gard SG-DV4420 Скачать руководство пользователя страница 4

4

INSTALLATION

running close to it, to avoid electrical noise causing
disturbance to the components.

You can use up to 5 SG-DV4420 on 1 F1/F2 subset
provided they are in the same location or 1 SG-DV4420
and 1 other subscribers control such as SG-DV1660, by
using the SUR- GARD SG-DS1 module (Y connector).
You have to connect together the 24V negative terminals
of both units, separate the ID codes and program a
different all call select for each one.

F1/F2 SUBSET

1. Remove power to the F1/F2 subset by unplugging the

A.C. adaptor from the 120 VAC outlet (if installed).
Do not remove the plug from the “Adapt" input of the
F1/F2 subset while the adaptor is powered as it may
cause an arc at the input and damage the F1/F2 subset.

2. If the telephone company installed a cable on the

"Terminal" input of the F1/F2 subset, disconnect it
and connect the 6 pin modular cable MCBL6 (6 ft.)
included with the SG-DV4420. Then connect the cable
to the SG-DV4420 Fire Transmitter. A custom length
6 pin modular cable(MCBL-C) is also available on
special order from Sur-Gard. The custom cable is
available in any length up to the maximum run length
of 50 feet. See the "F1/F2 Subset Connections" diagram
on page 10.

3. The F1/F2 subset should be installed close to the

control panel. However, if it is impossible, follow
these precautions:

Avoid cable runs close to noise generators like
power transformer, motor, fluorescent tube, etc...

If you can’t avoid this, or the F1/F2 subset is too
far from the control panel, it is necessary to use
low capacitance shielded cable to connect the
F1/F2 subset to the control panel.

RECOMMENDED MAXIMUM WIRE RUN
The RS-232 communication (Rx & Tx) has a
recommended maximum wire run of 50 feet, using Sur-
Gard's 6 pin modular cable.

The power supply (24Vdc) has a recommended maximum
wire run of 100 feet using:

#18 awg unshielded 4 conductor cable

#22 or #24 awg unshielded 4 conductor cable with
2 wires connected in parallel for each of the 24V

DC

Connections.

FOR LONGER DISTANCES
For RS-232 communication distances greater than 50 feet,
shielded cable with Sur-Gard's SG-DS1 connectors at
each end must be used. One SG-DS1 has to be installed
inside the Fire Transmitter cabinet and another one inside
the F1/F2 subset box, (see Appendix B for  theSG-DS1
wiring diagrams). The maximum distance maybe extended
by using a shielded cable such as those described below.

BENCH TESTING

The SG-DV4420 contains factory default programming.
Any additional programming required is done through
the SG-DVT1 tester. For many applications all that will
be required is to enter the ID number. If you need help,
talk to your Sur-Gard distributor.

Program the SG-DV4420 using the SG-DVT1 Tester
(with program version 5.0 or later) as an access terminal.
The SG-DVT1 is plugged into the SCHED-3A line modular
jack. The program select jumper J2 should be removed
from the SG-DV4420 circuit board.

Connect a 2.7K end of line resistor between the S1 input
terminal and the GND terminal. Connect a jumper on each
normaly closed supervisory zone S2, S3 and S4 input.
Connect 2 loops to the A1 and A2 Sprinkler/fire class A
input terminals - out to - in , and + out to + in. To
completely test your Fire system including the communicator
data, it is necessary to connect the unit to a test set, such
as the SG-DVT1 (see system testing procedure).

Connect a 14Vac, 20VA transformer to the AC  terminals.
Before plugging in the transformer, be sure the circuit
board is not resting on anything metallic which may
cause a short.

NOTE:

The SG-DV4420 will not start up if AC is OFF
and the battery is low.

MOUNTING THE PANEL

Select a dry location, close to an unswitched AC source,
close to a ground connection, and close to the F1/F2
subset (modem) location.

Remove the printed circuit board and mounting hardware
from the cardboard retainer inside the panel. Before
attaching the cabinet to the wall, press the five white
nylon printed circuit board mounting studs and the ground
connection screw into the cabinet from the back.

Pull all the cables into the cabinet and prepare them for
connection before mounting the circuit board to the
back of the cabinet. Press the circuit board down onto
the mounting studs.

With power off, wire the DV4420 as shown on fig. #1. All
normally closed (N/C) loops require a jumper if not used.
The connections to the F1/F2 subset are shown on fig.
#2. Avoid running  the  cable close to noise generators
like power transformer, motor, fluorescent tube, etc...

HOOK-UP PROCEDURE

DO NOT connect the transformer or battery until all other
wiring has been connected (See power-up procedure).

Connect a ground cable from the cabinet ground connection
by the shortest and most direct route to a grounding rod
and to the Earth Ground Terminal on the panel.

Connect zone cables to zone loop inputs and put jumpers
or end of line resistors as required on any unused zones.
Connect wires supplying power to detectors to the auxiliary
supply. Make sure that the PC board is clear of wire

Содержание SG-DV4420

Страница 1: ...receiver at the central station It includes the 12V power supply battery charger and the 24V power supply for the F1 F2 modem The standby power is obtained from a 12V battery The EEPROM programming is...

Страница 2: ...for each installation such as the ID code the all call response etc SERIAL OUTPUT The serial output to the F1F2 subset modem is on a 6 position modular jack A 6 foot modular cable is supplied with the...

Страница 3: ...y loop S1 is an End of Line Resistor loop The supervisory loop S1 must have a 2 7K end of line resistor This is not a Class B fire circuit since either a short or an open circuit condition causes the...

Страница 4: ...ESTING The SG DV4420 contains factory default programming Any additional programming required is done through the SG DVT1 tester For many applications all that will be required is to enter the ID numb...

Страница 5: ...tput command takes priority over any command that output point was already executing A For 50 feet to 100 feet Use 18 awg shielded 4 conductor cable such as Provo Cat Num 1782 21 or Belden Cat Num 981...

Страница 6: ...6 SG DV4420 WIRING DIAGRAM N O T USED 14VAC 20VA 14V 14V 14V 14V 14VA C A C A C A C A C...

Страница 7: ...7 F1 F2 SUBSET CONNECTION DIAGRAM...

Страница 8: ...8 SG DVT1 CONNECTION DIAGRAM...

Страница 9: ...ting Factory Writing Factory Writing Factory Writing Factory and Writing COMPLETE Writing COMPLETE Writing COMPLETE Writing COMPLETE Writing COMPLETE Defaults Wait Defaults Wait Defaults Wait Defaults...

Страница 10: ...at that address will show SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 01 1 1 1 1 The flashing cu...

Страница 11: ...l data shown are generally in Decimal Values Except for alarm restore codes which may be in Hex value The locations are in Hex value LOCATION 00 IDENTIFICATION CODE You may change the account identifi...

Страница 12: ...programmable output can be activated as indicated below DEFAULT 04 LEFT DIGIT 0X NO INDICATION 1X ALARM ON A1 INDICATION 2X ALARM ON A2 INDICATION 3X ALARM ON A1 OR A2 INDICATION 4X LINE FAULT INDICA...

Страница 13: ...sion Select for FIRE TROUBLE A2 02 I____ ____ 07 Transmission Select for SUPERVISORY S1 02 I____ ____ 08 Transmission Select for SUPERVISORY S2 02 I____ ____ 09 Transmission Select for SUPERVISORY S3...

Страница 14: ...lm Zn 02 0E 01 18 37 Other Trb Zn D8 Fire A2 0F 03 19 50 Alm Zn 03 0F 01 19 0C Fire Alm Zn 10 Trouble A2 10 04 1A 50 Alm Zn 04 10 02 1A 37 Other Trb Zn D9 Sup 1 11 05 1B 50 Alm Zn 05 11 01 1B 35 Lpres...

Страница 15: ...It should be between 24 and 26VDC If more than one panel is connected to the same modem negatives of the panel 24 volts modem power supplies must be connected together 3 Verify the connections betwee...

Страница 16: ...polling 7 If there is some but unsatisfactory communication have the telephone company measure the distortion on the leg Each bit transmitted should be near 6 6mS long Distortion can cause bits eg sp...

Страница 17: ...17 APPENDIX A SG DS1 WIRING DIAGRAMS...

Страница 18: ...18 APPENDIX B SG DV4420 PROGRAMMING FLOW CHART V6 0 V6 0 V6 0...

Страница 19: ...is and shall be in lieu of any and all other warranties whether expressed or implied and of all other obligations or liabilities on the part of Sur Gard Security Systems Ltd This warranty contains th...

Страница 20: ...1999 SG Security Communications 401 Magnetic Drive Units 24 28 Downsview OntarioCanadaM3J3H9 Tel 416 665 4494 Fax 416 665 4222 TollFree1 800 418 7618 www sur gard com 29000633R001 Printed in Canada...

Страница 21: ...INSTRUCTION MANUAL SG DV4420 Software Version 1 1...

Страница 22: ...4 MOUNTING THE PANEL 4 HOOK UP PROCEDURE 4 POWER UP PROCEDURE 5 SYSTEMTESTING 5 REQUIREMENTS FOR ULC INSTALLATION APPROVAL 5 CONTROL POINT INFORMATION 5 SG DV4420 WIRING DIAGRAM 6 F1 F2 SUBSET CONNEC...

Страница 23: ...24...

Отзывы: