[03] TO [0C] TRANSMISSION SELECT
It is possible to select, for each zone, no transmission,
alarm transmission only or alarm and restore transmission.
This feature provides for by-passing zones you don’t
want transmitted to the receiver.

00 = NO TRANSMISSION.

01  = TRANSMISSION OF ALARM ONLY.

02 = TRANSMISSION OF ALARM AND RESTORE

DEFAULT

[03]

Transmission Select for FIRE INPUT A1

02

[04]

Transmission Select for FIRE TROUBLE A1

02

[05]

Transmission Select for FIRE INPUT A2

02

[06]

Transmission Select for FIRE TROUBLE A2

02

[07]

Transmission Select for SUPERVISORY S1

02

[08]

Transmission Select for SUPERVISORY S2

02

[09]

Transmission Select for SUPERVISORY S3

02

[0A]

Transmission Select for SUPERVISORY S4

02

[0B]

Transmission Select for LOW BATT. DETECT 02

[0C]

Transmission Select for AC FAIL DETECT

02

[0D] TO [16] ZONE ASSIGNMENT
This feature permits each zone to be assigned to the
zone number desired, taking full advantage of the receiver
line card decoding.

DEFAULT

[0D]

Zone Assignment for FIRE INPUT A1

01

[0E]

Zone Assignment for FIRE TROUBLE A1

02

[0F]

Zone Assignment for FIRE INPUT A2

03

[10]

Zone Assignment for FIRE TROUBLE A2

04

[11]

Zone Assignment for SUPERVISORY S1

05

[12]

Zone Assignment for SUPERVISORY S2

06

[13]

Zone Assignment for SUPERVISORY S3

07

[14]

Zone Assignment for SUPERVISORY S4

08

[15]

Zone Assignment for LOW BATT. DETECT

01

[16]

Zone Assignment for AC FAIL DETECT

02

[17] TO [20] FUNCTION BYTE
This feature permits each zone to be assigned to the
zone description desired, taking full advantage of the
receiver line card decoding for central station without
automation.

DEFAULT

[17]

Function Byte for FIRE INPUT A1

50

[18]

Function Byte for FIRE TROUBLE A1

50

[19]

Function Byte for FIRE INPUT A2

50

[1A]

Function Byte for FIRE TROUBLE A2

50

[1B]

Function Byte for SUPERVISORY S1

50

[1C]

Function Byte for SUPERVISORY S2

50

[1D]

Function Byte for SUPERVISORY S3

50

[1E]

Function Byte for SUPERVISORY S4

50

[1F]

Function Byte for LOW BATT. DETECT

51

[20]

Function Byte for AC FAIL DETECT

51

PROGRAMMING GUIDE

NOTE:

All data shown are generally in Decimal
Values (Except for alarm/restore codes which
may be in Hex value). The locations are in
Hex value.

LOCATION

[00] IDENTIFICATION CODE
You may change the account identification code by
entering a two digit number in hex. (DEFAULT 01).

[01] OPTION 1 - ALL CALL SELECT
An “All Call” is a command sent by the central station’s
receiver after each scanning of 8 identification codes.
If a transmitter has an alarm at this moment, it can be
sent immediately to the central station, if the unit is
programmed to respond to that “All Call”. With this feature,
it is usually not necessery for that transmitter to wait for
its turn to be polled, before it is able to send an alarm
to the central station.

00 = NO RESPONSE ON ALL CALL,

01 = RESPONSE ON ALL CALL #1 ONLY,

02 = RESPONSE ON ALL CALL #2 ONLY,

03  = RESPONSE ON BOTH ALL CALLS ( #1 AND #2 ).

04 = RESPONSE ON ALL CALL #1 IF ID CODE IS

ODD AND ON ALL CALL #2 IF ID CODE IS EVEN.

NOTE:

A number programmed higher than 04 gives
the same selection as 04. When 2 transmitters
are used on the same F1F2 subset, each
must have a different All Call. (DEFAULT 04).

Example of receiver scanning

01-02-03..08-ALL CALL #1-09-0A-0B..10-ALL CALL #2-
..

It is recommended that just 1 All Call be selected, and
the choice of All Call be divided evenly over the installations.
In this way, approximately an equal number of subscribers
will be programmed for All Calls #1 and #2.

If two units are connected on the same modem (F1F2
subset): Skip at least 2 codes between your 2 identification
codes. (ex: #01,#04 so that 02 and 03 are used at other
locations.) Each unit should have a different All Call
selected.  So with automatic all call selection, you should
have an odd and an even identification code. No response
on All Call should be used for lower security installations,
and when more than two units are connected to one
modem - for the 3rd and additional units.

[02] OPTION 2 - ALL CALL ANSWER SELECT
00  = ALL CALL ANSWER ON ALARM AND RESTORE.

01 = ALL CALL ANSWER ON ALARM ONLY.

The unit can send an alarm and a restore on All Call,
but it is possible and preferable to limit it to sending
only the alarms and wait for the polling of its account
code before sending the restores. (DEFAULT 01).

Содержание SG-DV4420

Страница 1: ...receiver at the central station It includes the 12V power supply battery charger and the 24V power supply for the F1 F2 modem The standby power is obtained from a 12V battery The EEPROM programming is...

Страница 2: ...for each installation such as the ID code the all call response etc SERIAL OUTPUT The serial output to the F1F2 subset modem is on a 6 position modular jack A 6 foot modular cable is supplied with the...

Страница 3: ...y loop S1 is an End of Line Resistor loop The supervisory loop S1 must have a 2 7K end of line resistor This is not a Class B fire circuit since either a short or an open circuit condition causes the...

Страница 4: ...ESTING The SG DV4420 contains factory default programming Any additional programming required is done through the SG DVT1 tester For many applications all that will be required is to enter the ID numb...

Страница 5: ...tput command takes priority over any command that output point was already executing A For 50 feet to 100 feet Use 18 awg shielded 4 conductor cable such as Provo Cat Num 1782 21 or Belden Cat Num 981...

Страница 6: ...6 SG DV4420 WIRING DIAGRAM N O T USED 14VAC 20VA 14V 14V 14V 14V 14VA C A C A C A C A C...

Страница 7: ...7 F1 F2 SUBSET CONNECTION DIAGRAM...

Страница 8: ...8 SG DVT1 CONNECTION DIAGRAM...

Страница 9: ...ting Factory Writing Factory Writing Factory Writing Factory and Writing COMPLETE Writing COMPLETE Writing COMPLETE Writing COMPLETE Writing COMPLETE Defaults Wait Defaults Wait Defaults Wait Defaults...

Страница 10: ...at that address will show SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 01 1 1 1 1 The flashing cu...

Страница 11: ...l data shown are generally in Decimal Values Except for alarm restore codes which may be in Hex value The locations are in Hex value LOCATION 00 IDENTIFICATION CODE You may change the account identifi...

Страница 12: ...programmable output can be activated as indicated below DEFAULT 04 LEFT DIGIT 0X NO INDICATION 1X ALARM ON A1 INDICATION 2X ALARM ON A2 INDICATION 3X ALARM ON A1 OR A2 INDICATION 4X LINE FAULT INDICA...

Страница 13: ...sion Select for FIRE TROUBLE A2 02 I____ ____ 07 Transmission Select for SUPERVISORY S1 02 I____ ____ 08 Transmission Select for SUPERVISORY S2 02 I____ ____ 09 Transmission Select for SUPERVISORY S3...

Страница 14: ...lm Zn 02 0E 01 18 37 Other Trb Zn D8 Fire A2 0F 03 19 50 Alm Zn 03 0F 01 19 0C Fire Alm Zn 10 Trouble A2 10 04 1A 50 Alm Zn 04 10 02 1A 37 Other Trb Zn D9 Sup 1 11 05 1B 50 Alm Zn 05 11 01 1B 35 Lpres...

Страница 15: ...It should be between 24 and 26VDC If more than one panel is connected to the same modem negatives of the panel 24 volts modem power supplies must be connected together 3 Verify the connections betwee...

Страница 16: ...polling 7 If there is some but unsatisfactory communication have the telephone company measure the distortion on the leg Each bit transmitted should be near 6 6mS long Distortion can cause bits eg sp...

Страница 17: ...17 APPENDIX A SG DS1 WIRING DIAGRAMS...

Страница 18: ...18 APPENDIX B SG DV4420 PROGRAMMING FLOW CHART V6 0 V6 0 V6 0...

Страница 19: ...is and shall be in lieu of any and all other warranties whether expressed or implied and of all other obligations or liabilities on the part of Sur Gard Security Systems Ltd This warranty contains th...

Страница 20: ...1999 SG Security Communications 401 Magnetic Drive Units 24 28 Downsview OntarioCanadaM3J3H9 Tel 416 665 4494 Fax 416 665 4222 TollFree1 800 418 7618 www sur gard com 29000633R001 Printed in Canada...

Страница 21: ...INSTRUCTION MANUAL SG DV4420 Software Version 1 1...

Страница 22: ...4 MOUNTING THE PANEL 4 HOOK UP PROCEDURE 4 POWER UP PROCEDURE 5 SYSTEMTESTING 5 REQUIREMENTS FOR ULC INSTALLATION APPROVAL 5 CONTROL POINT INFORMATION 5 SG DV4420 WIRING DIAGRAM 6 F1 F2 SUBSET CONNEC...

Страница 23: ...24...

Отзывы: