SYSTEM OVERVIEW

The SG-DV4420 is intended for use as a fire transmitter
only, for connection to a sprinkler riser or to output relay
contacts of an existing fire alarm control panel. This unit
does not include U.L.C. requirements for a complete
building fire alarm system such as multi-zone with alarm
and trouble indicators.

INPUTS

2 Class A zones

1 ELR supervisory zon

3 Normally closed Supervisory zones

OUTPUTS

Power supply Vaux 12V at 250mA w/15 Ah
battery 24V at 50mA output to power modem

Operation controlled through program options

1 Programmable output PGM 1: Switched to
ground with current limiting resistor

ELECTRICAL SPECIFICATIONS

MAXIMUM LOOP RESISTANCE PER CONDUCTOR
Class-A loops
A1, A2 – 100 ohms

Supervisory loops
S1 – 2700 ohms ELR +/- up to 250  ohms

S2,S3,S4 – 500 ohms.

Eprom part number:

Type 27C256.

Nominal current draw:

260mA with fully charged
battery and F1/F2 subset
powered.

Battery Required:

6.5 Amp hr minimum to 15
Amp hr rechargeable gel-cell
or sealed lead-acid battery
mounted in panel.

TRANSFORMER
Built-in, 16,5 Vac, 37VA Class 2 Transformer.

Dimensions: 29cm(W) x 35.5cm(H) x 12.5cm(D)

Weight: 3.7Kg

FEATURES

POWER SUPPLY

The SG-DV4420 has a built-in 12VDC to 24VDC
regulated converter power supply, to operate the F1F2
subset modem, a one Amp 12VDC power supply and
battery charger. The auxiliary power supply can be used
to power smoke detectors and other devices requiring
12VDC. 800mA 12VDC is available from the AUX
(positive) and GND  (negative) terminals. It also includes
AC failure and low battery detector.

EEPROM NON-VOLATILE MEMORY

The EEPROM non-volatile memory is used to store the
programmable data needed for each installation such
as the ID code, the all call response, etc...

SERIAL OUTPUT

The serial output to the F1F2 subset modem is on a 6
position modular jack. A 6 foot modular cable is supplied
with the unit.

LOW BATTERY DETECTION

When the battery voltage falls below about 11V, this
internal circuit will be activated and the programmed
low battery code will be transmitted to the central station.

WATCH DOG CIRCUIT

The Watch Dog reset circuit continously monitors the
operation of the microprocessor.  If a malfunction occurs
(due to lightning or other unusual event) this circuit will
restart the microprocessor in less than 10 seconds.

LOW BATTERY DISCONNECT CIRCUIT (NOT
ON BOARD ONLY VERSION)

If the battery voltage fall below about 10.5V, the system
will electrically disconnect the battery to prevent it from
being deep discharged. The system remains disconnected
from the battery until the AC power comes back ON or
until the dead battery is replaced  with a sufficiently
charged battery.

CLASS A FIRE ZONES: “A1” & “A2”

The Fire zones A1 and A2 are supervised (normally
open alarm initiating contacts) Class A circuits designed
to accept sprinkler switches, manual pull stations, building
fire alarm control panel, alarm output relay contacts or
latching  four-wire smoke detectors.

Circuit A1 has an “retard” activation delay. On alarm,
(fire loop shorted) once the activation delay has expired,
the alarm is transmitted to the central station. The “retard”
activation delay is programmed at location 21. If the fire
input A1 returns to normal or swings  before the activation
delay has expired, there will be no transmitted alarm.
This activation delay feature makes it possible to use
vane type waterflow switches without false alarms from
pressure surges. There is also a restore delay time
programmable at location 22, to avoid nuisance repeat
alarms.

Содержание SG-DV4420

Страница 1: ...receiver at the central station It includes the 12V power supply battery charger and the 24V power supply for the F1 F2 modem The standby power is obtained from a 12V battery The EEPROM programming is...

Страница 2: ...for each installation such as the ID code the all call response etc SERIAL OUTPUT The serial output to the F1F2 subset modem is on a 6 position modular jack A 6 foot modular cable is supplied with the...

Страница 3: ...y loop S1 is an End of Line Resistor loop The supervisory loop S1 must have a 2 7K end of line resistor This is not a Class B fire circuit since either a short or an open circuit condition causes the...

Страница 4: ...ESTING The SG DV4420 contains factory default programming Any additional programming required is done through the SG DVT1 tester For many applications all that will be required is to enter the ID numb...

Страница 5: ...tput command takes priority over any command that output point was already executing A For 50 feet to 100 feet Use 18 awg shielded 4 conductor cable such as Provo Cat Num 1782 21 or Belden Cat Num 981...

Страница 6: ...6 SG DV4420 WIRING DIAGRAM N O T USED 14VAC 20VA 14V 14V 14V 14V 14VA C A C A C A C A C...

Страница 7: ...7 F1 F2 SUBSET CONNECTION DIAGRAM...

Страница 8: ...8 SG DVT1 CONNECTION DIAGRAM...

Страница 9: ...ting Factory Writing Factory Writing Factory Writing Factory and Writing COMPLETE Writing COMPLETE Writing COMPLETE Writing COMPLETE Writing COMPLETE Defaults Wait Defaults Wait Defaults Wait Defaults...

Страница 10: ...at that address will show SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 01 1 1 1 1 The flashing cu...

Страница 11: ...l data shown are generally in Decimal Values Except for alarm restore codes which may be in Hex value The locations are in Hex value LOCATION 00 IDENTIFICATION CODE You may change the account identifi...

Страница 12: ...programmable output can be activated as indicated below DEFAULT 04 LEFT DIGIT 0X NO INDICATION 1X ALARM ON A1 INDICATION 2X ALARM ON A2 INDICATION 3X ALARM ON A1 OR A2 INDICATION 4X LINE FAULT INDICA...

Страница 13: ...sion Select for FIRE TROUBLE A2 02 I____ ____ 07 Transmission Select for SUPERVISORY S1 02 I____ ____ 08 Transmission Select for SUPERVISORY S2 02 I____ ____ 09 Transmission Select for SUPERVISORY S3...

Страница 14: ...lm Zn 02 0E 01 18 37 Other Trb Zn D8 Fire A2 0F 03 19 50 Alm Zn 03 0F 01 19 0C Fire Alm Zn 10 Trouble A2 10 04 1A 50 Alm Zn 04 10 02 1A 37 Other Trb Zn D9 Sup 1 11 05 1B 50 Alm Zn 05 11 01 1B 35 Lpres...

Страница 15: ...It should be between 24 and 26VDC If more than one panel is connected to the same modem negatives of the panel 24 volts modem power supplies must be connected together 3 Verify the connections betwee...

Страница 16: ...polling 7 If there is some but unsatisfactory communication have the telephone company measure the distortion on the leg Each bit transmitted should be near 6 6mS long Distortion can cause bits eg sp...

Страница 17: ...17 APPENDIX A SG DS1 WIRING DIAGRAMS...

Страница 18: ...18 APPENDIX B SG DV4420 PROGRAMMING FLOW CHART V6 0 V6 0 V6 0...

Страница 19: ...is and shall be in lieu of any and all other warranties whether expressed or implied and of all other obligations or liabilities on the part of Sur Gard Security Systems Ltd This warranty contains th...

Страница 20: ...1999 SG Security Communications 401 Magnetic Drive Units 24 28 Downsview OntarioCanadaM3J3H9 Tel 416 665 4494 Fax 416 665 4222 TollFree1 800 418 7618 www sur gard com 29000633R001 Printed in Canada...

Страница 21: ...INSTRUCTION MANUAL SG DV4420 Software Version 1 1...

Страница 22: ...4 MOUNTING THE PANEL 4 HOOK UP PROCEDURE 4 POWER UP PROCEDURE 5 SYSTEMTESTING 5 REQUIREMENTS FOR ULC INSTALLATION APPROVAL 5 CONTROL POINT INFORMATION 5 SG DV4420 WIRING DIAGRAM 6 F1 F2 SUBSET CONNEC...

Страница 23: ...24...

Отзывы: