22
Example 2
: Code B1
Computer output: 104091sssssss022sOsss1
If Option A3 set to 03: the hex digit will be stripped for 1
and 2-digit reporting codes including Varitech.
If Option A3 set to 04: the hex digit will be stripped for
BFSK.
NOTE:
This option will only work if Option A4 is
set to 01.
Example 1
: Code 21
Computer output: 604091sssssss022sAss21
Example 2
: Code B1
Computer output: 604091sssssss022sOsss1
If Option A3 is set to 05: the hex digit will be stripped
for 1-digit reporting and BFSK.
If Option A3 Is set to 06: the hex digit will be stripped
for 2-digit reporting and BFSK.
If Option A3 set to 07: the hex digit will be stripped for
1-digit, 2-digit and BFSK.
NOTE:
Option [70] must be left as an individual
event code when enabling this option.
Option [A4]: BFSK RS-232 - Default [00]
When programming Option [A4] as '00', the BFSK format
will be reported as Radionics 6500 BFSK mode to the
computer; the protocol identifier will be a 6.
Example 1:
Code 21
Computer Output: 604091 022sAsss1
Example 2:
Code B1
Computer Output: 604091 022sOsss1
When Option A4 set to 01, the BFSK will be reported as
a standard 3/1 extended format, the protocol identifier
will also be changed from 6 to 1.
Example 1:
Code 21
Computer Output: 104091 022sAss21
Example 2:
Code B1
Computer Output: 104091 022sOssB1
Option [A5]: Sescoa Super Speed - Default [01]
If set to 00 Sescoa Super Speed will be disabled and 4/2
with checksum will be enabled.
If set to 01, Sescoa Super Speed will be enabled and 4/2
with checksum will be disabled.
Option [A6]: ITI Adjust - Default [00]
When set to 01, the ITI account codes will be converted
to four digits by stripping the last digit off. For example,
a panel account of 23459 will become account 2345. If
the leading digit of the panel account is a 0 than it will
be stripped and replaced with a space. For example, if
02349 is sent then the receiver will output 234 for the
panel account.
Option [A7]: Silent Knight FSK2 RS-232 - Default [00]
The DRL2000 provides two possible outputs to the com-
puter for Silent Knight FSK2 format. The operation of
this option is explained below:
[A7] = 00
[A7] = 01
SKFSK disabled
SKFSK enabled for:
SKFSK1
ERRLLLssssssAAAAYYssss[DC4]
SKFSK2 Protocol #2
CRRLLLssssAAAAAAYYZZss[DC4]
[A7] = 02
SKFSK enabled for:
SKFSK1
ERRLLLssssssAAAAYYssss[DC4]
SKFSK2 Protocol #2
FRRLLLssssAAAAAAYYZZss[DC4]
Options [A8] - [AF]: Dial-out Number For 2-way
Audio Transfer - Default [00]
These 8 options are used to provide the dial-out number
if the user wishes to transfer the call to another exten-
sion. Up to 16 digits may be programmed including any
'Feature Command' digits. The values in these options
will be sent as DTMF tones on the phone line after the
following sequence takes place:
1
The DRL2000 has recognized the current call as a 2-
way audio account and alarm code.
2
The calling control panel has finished sending its alarms
and switched into 2-way audio mode.
3
The DRL2000 will perform a Hook-flash with the time
value as programmed in Option 11 and then start to
dial the digits programmed in Options A8-AF.
Options A8-AF must be programmed in the following
manner: Digits 1-9 are programmed as the numbers 1-9.
The digit ‘A’ must be programmed if a zero is needed any-
where in the dial string as the digit zero is used to indicate
to the line card that there are no more digits to dial. If a '*'
is needed, (e.g., *70, the transfer command in some PBX/
PABX switches) program a 'B'. Similarly, if a '#' is needed,
program a 'C'.
To get the line card to wait for 3 seconds in a dial string,
program a 'D'. For example: to have the line card transfer a
2-way audio call to Ext. 51386, with a 3 second pause
between the transfer command and dialing, Options A8-
AF would be programmed as the following:
A8 = B7
A9 = AE
AA = 51
AB = 38
AC = 60
AD = 00
AE = 00
AF = 00
firealarmresources.com
Содержание MLR2000
Страница 4: ...NOTE firealarmresources com...
Страница 8: ...4 Figure 2 72 Line Cards Configuration Expansion cabinet firealarmresources com...
Страница 11: ...7 2 1 4 Signaling Supervisory Connections Figure 5 60 Line Cards Configuration firealarmresources com...
Страница 12: ...8 Figure 6 72 Line Cards Configuration Expansion Cabinet firealarmresources com...