Heatseeker UniPanel®
Solar Pool Heating
13
Installer Setup
TO ACCESS MENU PRESS ENTER AND SCROLL DOWN TO SYSTEM AND PRESS THE MODE BUTTON
WARNING PROFESSIONAL ONLY SETTINGS!
SYSTEM SUB-MENU
RESTORE DEFAULTS
Restore back to factory defaults.
RUN
When the roof temperature rises to pool + RUN then the solar will start.
END
When the roof drops below pool + END then the solar will stop.
FRZ?
Anti freeze function, when switched to ON will start the pump when the roof temperature
drops to the selected temperature and operates for 3 minutes every 30 minutes until the roof
temperature rises above the selected temperature.
BOIL?
Anti boil function, when switched to ON will start the pump when the roof temperature rises to the
selected temperature and operates for 5 minutes every 15 minutes until the roof temperature rises
above the selected temperature. Switched to OFF and USE PIPE PROTECTION option will be offered.
PIPE PROTECTION
For use when Heatseeker UniPanels® cannot drain down and will require a wetted roof sensor for
this mode.
CAL
Calibrate the pool sensor.
Additional Information
1. If any of the menu items are left unattended for 3 minutes the menu will time out and
automatically save all settings and return to automatic operation.
2. If a sensor fault is detected the controller will display which sensor and what the fault is.
3. Should power be interrupted for any reason, the controller will resume normal operation
when power is restored. All information will have been kept for up to 10 days.
4. If the controller has stopped pumping and is displaying a higher temperature than expected
it may be caused by a pump which is failing to prime, check the pump and if necessary prime
the pump as per the pump manufacturers’ instructions then reset the controller by turning it
off/on.
5. Maximum combined rated output load for the 240V socket(s) is 9.98 Amps / 2395 Watts.
6. Degree of protection against moisture: IP33.
7. Store pool chemicals at least 3 metres safely away from all pool equipment.
8. If the power cord is damaged, do not use the controller; return the unit to the supplier for
repair.