21
No.
Sign
Range
Default
Description
Set
205
dL
0.0~5.0
0.5
DO Bounce-back Delay Time
[s]
Used for avoiding that the DO alarm switch turns on
and off frequently with its related real-time data
being at the critical point.
Min. Interval Time for Peak Value Detection
[s]
Only after the time delayed, the triggered peak
value detection process is allowed to be stopped by
‘Weight
≤
Non-load Zero Range’. And only after
the time delayed, the stopped peak value detection
process is allowed to be triggered again by
‘Weight > Non-load Zero Range’.
Weight-checking Anti-bounce Time
[s]
After the weight-checking process triggered, if
‘Weight
≤
Non-load Zero Range’ in this time, then
the weight-checking process will be invalid.
206
Ao
0~1
0
AO Signal
0. nEt
[Real-time Weight]
1. PnEt
[Peak Value or Checking-weight Value]
207
AE
0.00~21.00
4.00
AO Current Low Limit Value
[mA]
208
AF
0.00~21.00
20.00
AO Current High Limit Value
[mA]
209
VE
0.00~10.00
0.00
AO V
oltage
Low Limit Value
[V]
210
VF
0.00~10.00
10.00
AO V
oltage
High Limit Value
[V]
211
AC
1~99999
10000
Max. Weight Value for AO Output
Weight
≥
[211]: AO= High Limit Value.
Weight
≤
0: AO=Low Limit Value.
212
CHC
0.00~9.99
1.00
Weight-checking Timeout
[s]
Once ‘Weight-checking Time
≥
Set Value’, the
weight-checking process will end automatically.