16
6.3 F1-SET Parameter Setting
6.3.1 Weighing Parameters (SCAL)
No.
Sign
Range
Default
Description
Set
100
Ut
0~3
1
Weight Unit
0: None
1: kg
2: t
3: g
101
dt
0~4
ooo.oo
Decimal Point Position
0: ooooo
1: oooo.o
2: ooo.oo
3: oo.ooo
4: o.oooo
102
SL
1~99999
10000
Scale Capacity
Max. allowed loading weight of the load receptor.
Scale Capacity
≤
(Loadcell Capacity × Loadcell
Quantity) – Self-weight of Load Receptor.
103
dV
1~500
1
Scale Division
1, 2, 5, 10, 20, 50, 100, 200, 500
104
ZE
-99999~
+99999
0
[*]
Zero Value
Only for query.
105
SP
>0
1.0000
[*]
Span Coefficient
Max. display value: 9.9999.
Only for query.
106
Sr
0~5
0
Stability Range
[Division]
Set value = 0: No ‘Stability Judging’.
Set value > 0: Weight Variance per [107] ‘Stability
Time’ being in [106] ‘Stability Range’ means
‘Weight is stable’.
107
St
0.1~9.9
0.5
Stability Time
[s]
[*]: ‘RAM Reset’ operation has no effect on the parameter.