11.Check and adjust CPR(only suitable for unit with CPR)
Commissioning: CPR adjustment
CPR
KX-350K
R404A
2.1bar
1.Connect manifold to KVL fitting.
2.Start the unit in Heating or Defrost mode.
3.Check compressor speed: 2400 rpm.
4.Remove KVL cap.
5.Adjust KVL to get gauge pressure value with hexagonal
socket head wrenches (n°8) :
■
To raise the suction pressure : turn the setting screw
clockwise
■
To lower the suction pressure: turn the setting screw
counter clockwise.
6.
When the setting has been adjusted, tighten the jam
nut securely against the setting screw to prevent any
movement of the setting screw due to vibrations in the
unit.
7.
Replace the cap.