Chapter 6: Advanced Chassis Setup
6-15
Release Tab
Figure 6-14. Changing the Power Supply
Changing the Power Supply
1. Unplug the AC power cord from the failed power supply.
2. With the system running, press the release tab at the top of the power supply
3. Push and hold the release tab on the back of the power supply.
4. Pull the power supply out using the handle provided.
5. Push the replacement power supply module into the chassis' power bay until
it clicks into the locked position.
6. Plug the AC power cord back into the power supply module and power- up
the nodes if needed (with a single power supply failure, the nodes should
continue to run).