SC846 Chassis Manual
4-18
Locate the power distributor between the power supply and the fan row.
Remove the two screws securing the power distributor housing to the chassis
wall
Remove the three screws securing the power distributor to the housing.
Gently pull the power distributor and houseing from the chassis. Carefully
guide all the cables through the power distributor housing.
Remove the power distributor from the housing.
Slide the new power distributor module into the power distributor housing.
Make that you slide the cables through the bottom of the housing.
Reconnect all the power cables, replace the power supply, and insert the plug
into the wall.
3.
4.
5.
6.
7.
8.
9.
Figure 4-20: Removing the Power Distributor and Housing