4-9
Chapter 4 Chassis Setup and Maintenance
Six heavy duty fans provide cooling for the chassis. These fans circulate air through
the chassis as a means of lowering the chassis internal temperature.
4-7 System Fans
Figure 4-16: System Fan
Release Tab
Replacing a system fan
1. If necessary, open the chassis while the power is running to determine which
fan has failed. (Never run the server for an extended period of time with the
chassis open.)
2. Turn off the power to the system and unplug the system from the outlet.
3. Remove the failed fan's power cord from the motherboard.
4. Press the fan release tab to lift the failed fan from the chassis and pull it com-
pletely from the chassis.
5. Place the new fan into the vacant space in the housing while making sure the
arrows on the top of the fan (indicating air direction) point in the same direction
as the arrows on the other fans.
6. Power up the system and check that the fan is working properly before replac-
ing the chassis cover.
Содержание Supero SC933E1-R760B
Страница 1: ...SC933 CHASSIS SERIES SUPER USER S MANUAL 2 0 SC933S1 R760B SC933T R760B SC933E1 R760B SC933E2 R760B ...
Страница 4: ...SC933 Chassis Manual iv Notes ...
Страница 6: ...SC933 Chassis Manual vi Notes ...
Страница 10: ...SC933 Chassis Manual x Notes ...
Страница 14: ...SC933 Chassis Manual 1 4 Notes ...
Страница 32: ...SC933 Chassis Manual 4 10 Figure 4 5 Placing the System Fan ...
Страница 36: ...SC933 Chassis Manual 4 14 Notes ...
Страница 43: ...5 7 Chapter 5 Rack Installation Figure 5 4 Installing the Outer Rails to the Server Rack ...
Страница 46: ...xxx Chassis Manual 2 Notes ...
Страница 52: ...SC933 Chassis Manual B 2 Notes ...
Страница 58: ...1 2 Backplane User s Guide Notes ...
Страница 84: ...3 18 Backplane User s Guide Notes ...