4-13
Chapter 4 Chassis Setup and Maintenance
To change the power distributor
Server chassis that are 2U or more high require a power distributor. The power
distributor provides failover and power supply redundancy. In the unlikely event you
must change the power distributor, do following
1. Power down the server and remove the plug from the wall socket or power
strip.
2. Remove all cable connections to the power supply from the motherboard,
backplane, and other components. Also, remove both power supplies.
3. Locate the power distributor between the power supply and the fan row.
4. Remove the three screws securing the power supply.
5. Gently pull the power distributor from the chassis. Gently guide all the cables
through the power distributor housing.
6. Slide the new power distributor module into the power distributor housing.
Make that you slide the cables through the bottom of the housing.
7. Reconnect all the power cables, replace the power supply, and insert the plug
into the wall.
Figure 4-7: Changing the Power Distributor
Содержание Supero SC933E1-R760B
Страница 1: ...SC933 CHASSIS SERIES SUPER USER S MANUAL 2 0 SC933S1 R760B SC933T R760B SC933E1 R760B SC933E2 R760B ...
Страница 4: ...SC933 Chassis Manual iv Notes ...
Страница 6: ...SC933 Chassis Manual vi Notes ...
Страница 10: ...SC933 Chassis Manual x Notes ...
Страница 14: ...SC933 Chassis Manual 1 4 Notes ...
Страница 32: ...SC933 Chassis Manual 4 10 Figure 4 5 Placing the System Fan ...
Страница 36: ...SC933 Chassis Manual 4 14 Notes ...
Страница 43: ...5 7 Chapter 5 Rack Installation Figure 5 4 Installing the Outer Rails to the Server Rack ...
Страница 46: ...xxx Chassis Manual 2 Notes ...
Страница 52: ...SC933 Chassis Manual B 2 Notes ...
Страница 58: ...1 2 Backplane User s Guide Notes ...
Страница 84: ...3 18 Backplane User s Guide Notes ...