Superior SLBV-35 Скачать руководство пользователя страница 7

5 (127)

8-1/4

(209)

14

(356)

12 (305)

19 

(483)

8 (203)

2

(51)

4

(102)

6

(152)

8

(203)

10

(254)

12

(305)

10 (254)

14 (356)

18 (457)

16 (406)

12 (305)

Top of 

Appliance

inches (millimeters)

Mantel depth

Note - Hood shown 

as positioned.

Figure 6 - Minimum Mantel Clearances

Header

Figure 5 - Minimum Distance to Unprotected Side Wall

Top View of 

fireplace

 45

o

Protected wall 

shown in white

Inches (millimeters)

MINIMUM CLEARANCES TO COMBUSTIBLES

Appliance and Vent Clearances

The appliance is approved with zero clearance to combustible materials 

on all sides (as detailed in 

Table 6)

, with the following exception: 

When 

the unit is installed with one side flush with a wall, the wall on the 

other side of the unit must not extend beyond the front edge of the 

unit (see

 Figure 5

)

**Note: See Step 1 on Page 8 for clearance requirements to the nailing 

flange located at each side of the unit and any screw heads adjacent to it. 

Hearth Extension

A hearth extension is not required with this appliance. If a hearth extension 

is used, do not block the lower control compartment door. Any hearth 

extension used is for appearance only and does not have to conform to 

standard hearth extension installation requirements.

Wall finishes / Surrounds / Mantels

Note:

 Combustible wall finish materials and/or surround materials must 

not be allowed to encroach the area defined by the appliance front face 

(black sheet metal). 

Never allow combustible materials to be positioned 

in front of or overlapping the appliance face

 (see 

Figure 5

; also see 

Figure 30 on Page 23

).

Non-combustible materials, such as surrounds and other appliance trim, 

may be installed on the appliance face with these exceptions: they must 

not cover any portion of the removable glass panel.

Vertical installation clearances to combustible mantels vary according 

to the depth of the mantel. See 

Figure 6

. Mantels constructed of non-

combustible materials may be installed at any height above the appliance 

opening; however, do not allow anything to hang below the fireplace hood.

Note:

 We recommend the use of high-temperature paint (rated 175°F or 

higher) on the underside of the mantel.

Combustible materials 

may project beyond 

one side of the 

fireplace opening  

as long as they are 

kept within the shaded 

areas illustrated  here.

Combustible Materials 

Allowed In Shaded Area 

“Safe zone”

Combustible walls 

shown in dark gray.

At 14" minimum side 

wall clearance, a 

combustible wall can 

project to any length.

At 8-1/4" side 

wall clearance, a 

combustible wall 

can project 12".

MINIMUM CLEARANCES - Inches (millimeters)

Back

0 (0) to Standoffs or dimples

Sides

0 (0) to Standoffs or dimples**

Top

3 in (76 mm)

floor

0 (0)

from Bottom of Unit  

to Ceiling

64 in (1626 mm)

Vent

1 in (25.4 mm)

SERVICE CLEARANCES

front

3 ft (0.9 m)

Table 6

SUPERIOR

®

 B-VENT GAS FIREPLACES  •  MODELS SLBV-35, SLBV-40  •  INSTALLATION INSTRUCTIONS

7

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Содержание SLBV-35

Страница 1: ...PEUT CAUSER DES BR LURES LAISSER REFROIDIR LA SURFACE VITR E AVANT D Y TOUCHER NE PERMETTEZ JAMAIS UN ENFANT DE TOUCHER LA SURFACE VITR E EL VIDRIO CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNCA TOCAR EL...

Страница 2: ...on system No external electrical power is required to operate these appliances however 120V AC is recommended see Step 4 Install Field Wiring on Page 12 Use Only These Approved Vent Components These v...

Страница 3: ...localcodesor intheabsenceoflocalcodes with the USA National Electrical Code ANSI NFPA 70 latest edition or in Canada the Canadian Electrical Code CSA C22 1 latest edition Provide adequate clearances a...

Страница 4: ...Table 3 Requirements for the Commonwealth of Massachusetts Thesefireplacesareapprovedforinstallationin the US state of Massachusetts if the following additional requirements are met Install this appli...

Страница 5: ...rom furniture and draperies Figure 3 En raison des temp ratures lev es l appareil devrait tre install dans un endroit o il y a peu de circulation et loin du mobilier et des tentures Figure 3 The locat...

Страница 6: ...a chimney vent servicing a solid fuel fireplace provided the B vent cap is at least 2 ft 0 6 m away from the nearest point of the chimney opening Gas Vent Rule Gas vent caps are not permitted within 8...

Страница 7: ...appliance front face blacksheetmetal Neverallowcombustiblematerialstobepositioned in front of or overlapping the appliance face see Figure 5 also see Figure 30 on Page 23 Non combustible materials su...

Страница 8: ...raming Frame the appliance as illustrated in Figures 8 1 and 8 2 All framing details must allow for a minimum clearance to combustible framing members as shown in Table 6 Page 7 If the appliance is to...

Страница 9: ...Figure 8 1 Framing Dimensions Model No A B C SLBV 35 in 35 1 4 35 1 4 16 mm 895 895 406 SLBV 40 in 40 1 4 40 1 4 16 mm 1022 1022 406 C is the required framing depth dimension when the finish material...

Страница 10: ...VER PLATE with KNOCKOUT Right Side 16 in 406 mm Hood Left Side View 5 7 8 in 149 mm NOTE It is recommended that gas be stubbed in from LEFT side only 3 in 76 mm 9 1 2 in 241 mm GAS INLET KNOCKOUT 7 3...

Страница 11: ...ions Allappliancesarefactory equippedwithaflex ible gas line connector and 1 2 inch shutoff valve See Step 6 on Page 15 Never use galvanized or plastic pipe Gas lines must be routed constructed and ma...

Страница 12: ...through the knockout opening and into the unit junction box 5 Connect the black power supply wire to the lower outlet s red pigtail lead and the white power supply wire to the common terminal of the...

Страница 13: ...tion Instructions TRANSFORMER 3V BROWN BROWN BLACK BATTERY BACK UP BLACK SENSOR BLACK IGNITER IGNITER MODULE 3V RED PILOT IN OUT VENT LO HI TH TP TH TP IN ORANGE THTP BLACK TP GREEN TH HIGH LIMIT SWIT...

Страница 14: ...the lower control compartment opening See Figure 15 To open the outside air shutter open the bottom controlaccesspanel reachintothecontrolcom partment and pull the outside air control lever all the wa...

Страница 15: ...the gas flex line Using pipe dressing materials appropriate for the gas type securely affix the shut off valve to this determined pipe length at a convenient location outside of the appliance lower co...

Страница 16: ...appliances only Note Lighting Instructions are also found on the literature tag tied to the gas piping next to the gas valve To access the tag open the lower control compartment door by pulling the pa...

Страница 17: ...2 Separate the glowing ember material into pieces about the size of a quarter Keep the pieces fluffed up not matted Distribute the pieces over the sur face of the burner as shown in Figures 23 and 24...

Страница 18: ...le at the bottom of log 4 over the nub of log 2 as shown 4 2 SLBV Firebox Accessories Parts Cat No Model No Description H7244 SLBV 35 Log Set Assembly 88L53 FGE Bag of Glowing Embers Rockwool 80L42 FD...

Страница 19: ...ent sooting make sure logs do not cover any burner openings Step 4 Align the hole at the bottom of log 5 over the Nub of log 3 as shown 3 5 Step 2 Align hole at the bottom of left front log 2 over the...

Страница 20: ...ing on both sides is even and equal Control Compartment Panel Hood Glass Door Header Spacing Top Standoffs Flush Nailing Flange 1 2 Nailing Flange 5 8 Nailing Flange Glass Door Spring Latch Control Co...

Страница 21: ...en tally to a more open position until the proper flame appearance is achieved If flame stays lowered blue adjust the air shutter incrementally to a more closed position until the proper flame appeara...

Страница 22: ...ician inspect the fireplace and venting for these conditions and repair as needed To RESET the safety limit switch push the reset button located between the wire terminals on the back of the switch Fo...

Страница 23: ...ished wall position framework to accom modate the thickness of the finished wall Figure 30 For Cold Climate Insulation see Page 5 For Clearances see Page 7 Top of Appliance 1 in 25 mm min Figure 30 Co...

Страница 24: ...sa Nettoyez soigneusement la plaque murale de l interrupteur pour liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui con...

Страница 25: ...screws b Remove the pressure regulator spring poppet diaphragm and bushing c Discard all removed components d Make sure the rubber gasket in stalled on the back of the replace ment pressure regulator...

Страница 26: ...version label provided in the conversion kit next to the rat ing plate on the appliance Step 13 Turn on gas supply and test for gas leaks refer to Page 16 Always test pressures with the valve regulato...

Страница 27: ...Notes SUPERIOR B VENTGASFIREPLACES MODELS SLBV 35 SLBV 40 INSTALLATION INSTRUCTIONS 27 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE...

Страница 28: ...es at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information SUPERIOR B VENT...

Отзывы: