VENTING INSTALLATION 

Continued

FIRESTOP SPACERS (FS-10, 1100EFS-10DM FOR 36" MODELS)

Firestop spacers are required at each point where the chimney penetrates 

a floor space. Their purpose is to establish and maintain the required 

clearance between the chimney and the combustible materials. When 

the pipe passes through a framed opening into a living space above, the 

firestop must be placed onto the ceiling from below as shown in Figure 13.
They also provide complete separation from one floor space to another 

or attic space as required by most codes. When the double wall pipe 

passes through a framed opening into an attic space, the firestop must 

be placed into an attic floor as shown in Figure 14.

Figure 12 - Typical Offset Terminations

Figure 13 - Firestop Spacer with Living Space Above Ceiling

Figure 14 - Firestop Spacer with Attic Space Above Ceiling

Existing 

Ceiling 

Frame

Firestop 

Spacer

Screws or 

Staples (Min. 

of 8)

Firestop 

Spacer

Screws or Staples 

(Min. of 8)

Existing 

Ceiling 

Frame

IMPORTANT NOTICE

When penetrating a ceiling into an attic, a firestop 

thimble (FST10) is required to avoid intrusion by insu-

lation and recommended to negotiate a joist.

Firestop Thimble FST10

Figure 14a - Firestop Thimble

PENETRATING ROOF

To maintain a 1" (36" Models) or 2" (42/50" Models) clearance to the 

pipe on a roof with a pitch, a rectangular opening must be cut.
1.  Determine center point through which pipe will penetrate roof.
2.  Determine center point of roof. Pitch is distance the roof drops 

over a given span, usually 12". A 6/12 pitch means that roof drops 

6" for each 12" measured horizontally down from roof rafters.

3.  Use roof opening chart (Figure 15, page 12) to determine correct 

opening length and flashing required.

4.  Remove shingles around opening measured. Cut out this section.
5.  Add next sections of pipe until end penetrates roof line. Check 

to see that proper clearances are maintained. Extend chimney by 

adding sections of double wall pipe until pipe is minimum of 30" 

above highest point of roof cutout. Termination and chimney must 

extend a minimum of 36" above highest point where it passes 

through roof.

Return 

Elbow

Offset 

Elbow

Return 

Elbow

Offset 

Elbow

6' (1.88 m) 

Max.

6' (1.88 m) 

Max.

6' (1.88 m) 

Max.

6' (1.88 m) 

Max.

6' (1.88 m) 

Max.

6' (1.88 m) 

Max.

Return 

Elbow

Offset 

Elbow

Offset 

Elbow

Return 

Elbow

A

B

C

Offset 

Elbow

Ceiling 

Support Pipe

12S-12DM

Return 

Elbow

Содержание F4222

Страница 1: ...1 2 standard FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit...

Страница 2: ...state this fireplace has been tested for use with this insert FOR YOUR SAFETY Do not store or use gasoline or any other flammable vapors or liquids in the vicinity of this or any other appliance Due...

Страница 3: ...ing causes and troubleshooting WARNING BURNINGIMPROPERFUEL I E CHAR COAL CAN RESULT IN CARBON MONOXIDE POISON ING WHICH MAY LEAD TO DEATH Carbon Monoxide Poisoning Early signs of carbon monoxidepoison...

Страница 4: ...mm 1 1 4 32 mm 20 1 4 515 mm Ref 14 1 2 369 mm 4 1 2 115 mm 10 1 2 267 mm 9 1 2 242 mm 3 1 2 89 mm 4 1 2 115 mm 45 1 8 1159 mm 36 915 mm 30 762 mm 49 1245 mm 67 1702 mm 11 280 mm 7 178 mm 61 1550 mm 1...

Страница 5: ...1 4 32 mm 23 585 mm Ref 21 3 4 553 mm 15 3 4 400 mm 4 3 8 112 mm 10 1 2 267 mm 9 1 2 242 mm 3 1 2 89 mm 4 1 2 115 mm 51 1 8 1299 mm 42 1067 mm 30 762 mm 49 1245 mm 67 1702 mm 11 280 mm 7 178 mm 61 15...

Страница 6: ...m 59 1 4 1505 mm 1 26 mm 11 280 mm 7 178 mm 67 1702 mm 61 1550 mm 58 1474 mm 49 1245 mm 30 762 mm 9 1 2 242 mm 10 1 2 267 mm 13 331 mm 50 1270 mm 34 3 8 874 mm 38 1 2 978 mm 28 1 2 724 mm 17 5 8 448 m...

Страница 7: ...himney pipe sections required for outdoor installation FRAMING 1 Frame opening for fireplace using dimensions shown in Figures 4 and 5 2 If fireplace is to be installed directly on carpeting tile or a...

Страница 8: ...eplace Front Ember Protector Fireplace Front Raised Hearth Fireplace Front Elevated Ember Protector Ember Protector Seal Gap Hearth Extension MANTELS A mantel may be installed if desired see Figure 7...

Страница 9: ...HT Pipe Section 34 5 8 48 12DM 48 12HT Pipe Section 46 5 8 RLT 12D RLT 12HT Round Termina tion 7 3 4 STL 12D Square Chase Top with Slip Section 7 to 15 The lineal gain for the terminations is measured...

Страница 10: ...outer pipe only see Figure 10 Do not penetrate the inner stainless Figure 11 Ceiling Support Pipe 12S 12DM Straps Straps Straps Straps Detail A Return Elbow Detail B Angle Firestop See Detail A See D...

Страница 11: ...le FST10 is required to avoid intrusion by insu lation and recommended to negotiate a joist Firestop Thimble FST10 Figure 14a Firestop Thimble PENETRATING ROOF To maintain a 1 36 Models or 2 42 50 Mod...

Страница 12: ...rm Collar Flashing FLASHING INSTALLATION V6F 10DM OR V12F 10DM Determine the flashing to be used with the roof opening chart Slide flashing over pipe until base is flat against roof Replace as many sh...

Страница 13: ...d stacked at a vertical height difference of 18 see Figure 19 Note If a decorative shroud is to be installed contact the manufacturer for specifications 10 FOOT RULE All flue gas outlet chimney termin...

Страница 14: ...talling Termination Cap 1 Noncombustible Spacer Note Do Not Seal Ventilation Openings 1 Space Chase Facia 1 4 Screen Chase Top Sheet Metal Screw Termination 36 915 mm Min 3 77 mm Min 2 51 mm Min 1 Spa...

Страница 15: ...ey outlet see Figure 29 6 Attach storm collar where chimney pierces opening in flash ing Caulk where storm collar touches outer chimney pipe see Figure 29 Figure 26 Constructing Chase Top Flashing As...

Страница 16: ...anels Hearth Panel Side leading brick Panel 4 Secure the firebrick wall using 2 of the retainers provided The bracket will slip underneath the metal lip on the top of the wall and screw into the inner...

Страница 17: ...not dry out before use 5 Grout all joints where two firebrick walls come together 6 Using a trowel remove excess grout mixture by moving trowel in the direction of the joint Grout mixture in the joint...

Страница 18: ...on for reuse Replace screws 3 Run a 1 2 black iron gas line into fireplace through the rear at gas line conduit sleeve if using a raised platform add height Provide sufficient gas line into fireplace...

Страница 19: ...ed gas log sets which have been found to comply with the standard for unvented room heaters ANSI Z21 11 2 are to be installed in this fireplace WARNING If the fireplace has been used for wood burning...

Страница 20: ...ors ifleftpartlyopen maydraw gas and flame out of the fireplace opening creating risks of both fire and smoke WARNING Do not slam or strike doors Damage can result in a hazardous condition WARNING Dis...

Страница 21: ...ntacting your dealer please have your model and serial numbers of your fireplace ready You can also visit our web site at SuperiorFireplaces us com REPLACEMENT PARTS See Pages 22 to 24 for a complete...

Страница 22: ...SuperiorFireplaces us com 901008 00_NC 22 PARTS MODELS 36 42 AND 50 1 20 19 5 6 7 10 9 11 12 13 16 17 15 14 8 23 22 3 24 18 2 21 4 MODEL CATALOG NO WRE6036 F4222 WRE6042 F4223 WRE6050 F4224...

Страница 23: ...ACE TOP ASSEMBLY 42 1 FIREPLACE TOP ASSEMBLY 50 1 10 J6997 SPACER FIREPLACE TOP 42MC 4 11 FIREPLACE SURROUND ASSEMBLY 1 12 J4362 SPACER CLEARANCE 36 42 50 6 13 J5329 BRACKET F P HANDLE 4 14 J6900 PLAT...

Страница 24: ...plit F0350 Mosaic50M2 Red Full Stacked F0351 Mosaic50M4 Red Split Stacked F0352 Mosaic50M2 Ivory Full Stacked F0353 Mosaic50M4 Ivory Split Stacked F0354 Mosaic50M3 Red Herr Full F0355 Mosaic50M5 Red H...

Страница 25: ...S DOOR 42 PLATINUM F1008 BD50 GLASS DOOR 50 BLACK F1009 BD50B GLASS DOOR 50 BRUSHED BRASS F1010 BD50P GLASS DOOR 50 PLATINUM DOUBLE WALL PIPE F0932 12 12DM 12 Section Double Wall Pipe Snap Lock F0933...

Страница 26: ...h Slip Section Pre Painted Black ROUND TOP TERMINATIONS F0947 RLT 12D Round Top Termination with Louvered Screen F0960 RLT 12HT Hi Temp Round Top Termination with Louvered Screen FIRESTOP THIMBLE F094...

Страница 27: ...T Chimney Support F0960 RLT 12HT Round Top w Louvers F0961 AP 12HT Anchor Plate Collar Assembly Masonry Fireplaces F0951 CAK 12 Cold Air Collar Kit When ordered alone this part cannot ship via parcel...

Страница 28: ...nditions inadequate chimney heights adversewindconditionsand orunusualenvironmental factors or conditions beyond our control take into account all variables within the installation and install the app...

Страница 29: ...ance The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of...

Страница 30: ...___________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Страница 31: ...be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with a...

Страница 32: ...1008 00 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult yo...

Отзывы: