6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Test gauge connections are provided on the
front of the millivolt and electronic gas control
valve (identified IN for the inlet and OUT for the
manifold side). The control valves have a 3/8"
(10mm) NPT thread inlet and outlet side of the
valve (refer to
Figures 1 and 2
)
.
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step down regulators to reduce the
pressure to safe levels.
In Canada - CAN/CGA-2.17-M91 (R2009)
(high altitude):
THE CONVERSION SHALL BE CARRIED
OUT BY A MANUFACTURER’S AUTHO-
RIZED REPRESENTATIVE, IN ACCOR-
DANCE WITH THE REQUIREMENTS OF
THE MANUFACTURER, PROVINCIAL OR
TERRITORIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE
WITH THE REQUIREMENTS OF THE
CAN/CGA-B149.1 OR CAN/CGA-B149.2
INSTALLATION CODES.
Gas Valve Diagrams
See
Figure 1
for Millivolt models and
Figure 2
For Electronic Models.
Orifice Sizes - Sea Level to High Altitude
(All Models)
These appliances are tested and approved for
installation at elevations of 0-4500 feet (0-1372
meters) above sea level using the standard burner
orifice sizes (marked with an "*" in
Table 4)
.
For elevations above 4500 feet, contact your
gas supplier or qualified service technician.
Manifold Gas Supply Pressure
(all models)
Fuel #
Low
High
Natural
Gas
(Lo) 2.2" WC
(0.55 kPa)
(Hi) 3.5" WC
(0.87 kPa)
Propane (Lo) 6.3" WC
(1.57 kPa)
(Hi) 10.0" WC
(2.49 kPa)
Table 3
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of
1/2 psi (3.5 kPa).
The appliance must be isolated from the
gas supply piping system by closing its
equipment shutoff valve during any pressure
testing of the gas supply piping system at
test pressures
equal to or less than
1/2 psi
(3.5 kPa).
Deration -
At higher elevations, the amount
of BTU fuel value delivered must be reduced
by either:
• Using gas that has been derated by the gas
company.
• Changing the burner orifice to a smaller size
as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel
Gas Code NFPA 54/ANSI Z223.1 - latest
edition or, in Canada, the CAN/CGA-B149.1
codes - latest edition.
Flame breadth, height and width will diminish
4% for every 1,000 feet of altitude.
Inlet Gas Supply Pressure
(all models)
Fuel #
Minimum
Maximum
Natural Gas
4.5" WC
(1.12 kPa)
10.5" WC
(2.61 kPa)
Propane
11.0" WC
(2.74 kPa)
13.0" WC
(3.23 kPa)
Table 2
Gas Pressure - All Models
Tables 2 and 3
show the appliances' inlet and
manifold gas pressure requirements:
Figure 2 - SIT Electronic Gas Valve
Main Gas Inlet
3/8" NPT
Inlet (IN)
Test Port
Manifold
(OUT)
Test Port
Green Wire
(From DFC Wire
Harness)
Yellow Ground Wire
(From DFC Wire
Harness)
Hi/Lo Flame
Control Knob
Orange
Wire
(From DFC
Wire
Harness)
COMMONWEALTH OF MASSACHUSETTS
REQUIREMENTS
These appliances are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R. Sections 4.00 through 8.00.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
• The flexible gas line connector used shall
not exceed 36 inches (92 centimeters) in
length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, hori-
zontal terminations installed less than seven
(7) feet above the finished grade must comply
with the following additional requirements:
• A hard wired carbon monoxide detector
with an alarm and battery back-up must be
installed on the floor level where the gas
fireplace is installed. The carbon monoxide
detector must comply with NFPA 720, be
ANSI/UL 2034 listed and be ISA certified..
• A metal or plastic identification plate must
be permanently mounted to the exterior of
the building at a minimum height of eight (8)
feet above grade and be directly in line with
the horizontal termination. The sign must
read, in print size no less than one-half (1/2)
inch in size,
GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS.
NEW YORK CITY, NEW YORK (MEA)
Installation of these fireplaces are approved
for installation in New York City in the US state
of New York.
H I
LO
W
HT
PT
HT
PT
PILO
T
PI
LO
T
ON
it
OFF
IN
OUT
HI/LO Variable
Flame Height
Adjustment
Figure 1 -
SIT Millivolt Gas Valve
Manifold Pressure Tap
Inlet Pressure Tap
Pilot Adjustment
Screw
Main Gas Control Knob
OFF/PILOT/ON
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model
Series
Nat.Gas
drill size (inches)
Propane
drill size (inches)
40"
#40 (0.0980")*
69L96 •
#53 (0.0595")*
39L10•
45"
#37 (0.1040")*
24M10 •
(0.0620")*
21L01 •
Table 4
* Standard size installed at factory
• Part /Cat. Number
Installation and Operation Instructions
900357-00, 06/2015
Innovative Hearth Products
Superior
TM
DRT40 Direct Vent Gas Fireplace