background image

20

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Figure 34 

- Typical Horizontal Vent Installation

 

The unitized design of the 

Secure Vent

 compo-

nents will engage and seal both the inner and 

outer pipe elements with the same procedure.  

Sealant and securing screws are not required.

NOTE:

 An elbow may also be attached to the 

appliance collar.  Attach in the same manner as 

you would a vent section. 

E.  Attach vent components to each other -

 Other 

vent sections may be added to the previously 

installed section in accordance with the require-

ments of the vent tables.  To add another vent 

component to a length of vent run, align the 

dimpled end of the component over the inclined 

channel end of the previously installed section, 

adjusting the radial alignment until the four lock-

ing dimples are aligned with the inlets of the four 

incline channels of the previous section.  Push 

the vent component against the previous section 

until it fully engages, then twist the component 

clockwise running the dimples down and along 

the incline channels until they seat at the end of 

the channels.

This seating position is indicated 

by the alignment of the arrow and dimple as 

shown in

 

Figure 22 

on 

Page 16.

F.

 

Install firestop/spacer at ceiling - 

When using Secure Vent, use SV4.5VF firestop/

spacer at ceiling joists; when using Secure Flex, 

use SF4.5VF firestop/spacer. If there is living 

space above the ceiling level, the firestop/ 

spacer must be installed on the bottom side of 

the ceiling. If attic space is above the ceiling, 

the firestop/ spacer must be installed on the 

top side of the joist.  Route the vent sections 

through the framed opening and secure the 

firestop/spacer with 8d nails or other appropri-

ate fasteners at each corner. The gap between 

the vent pipe and a firestop can be sealed with 

noncombustible caulking.

Remember to maintain 1" (25 mm) clearance 

to combustibles, framing members, and attic 

or ceiling insulation when running vertical 

chimney sections

.

G.

 

Support the vertical run sections - 

On the vertical run, support the venting sys-

tem every 8 feet (2.4m) above the fireplace 

vent outlet with field provided support straps 

(Plumber's tape). 

 

Attach the straps to the vent 

pipe and secure to the framing members with 

nails or screws.

 

See 

 

Figure 23 on Page 16

.

H. Change vent direction - 

 At transition from or 

to a horizontal/inclined run, install the SV4.5E45 

and SV4.5E90 elbows in the same manner as 

the straight vent sections.  The elbows feature 

a twist section to allow them to be routed about 

the center axis of their initial collar section to 

align with the required direction of the next 

vent run element. 

Twist elbow sections in a 

clockwise direction only so as to avoid the 

possiblity of unlocking any of the previously 

connected vent sections.

 See 

Figure 24 

on 

Page 17

.

I.

 

Continue installation of horizontal/inclined 

sections -

  Continue with the installation of the 

straight vent sections in horizontal/inclined run 

as described in 

Step E

. Install support straps 

every 5 ft. (1.52 m) along horizontal/inclined 

vent runs using conventional plumber’s tape. 

See 

Figure 34. 

It is very important that the 

horizontal/inclined run be maintained in a 

straight (no dips), slightly elevated plane. 

The recommended incline is approximately 

1/4" per foot (20 mm per meter) horizontal, 

in a direction away from the fireplace. The 

rise per foot run ratios that are smaller are 

acceptable all the way down to at or near 

level. 

 Use a carpenter’s level to measure 

from a constant surface and adjust the support 

straps as necessary. 

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all 

sides for all vertical runs; and 3" (76 mm) at 

the top, 1" (25 mm) at sides, and 1" (25 mm) 

at the bottom for all horizontal/inclined runs

HORIZONTAL (OUTSIDE WALL) 

TERMINATION SYSTEM 

Figures 34, and Figures 38 to 43 

on

 Pages 

22 To 24 

and their associated  Horizontal Vent 

Table illustrate the various horizontal venting 

configurations that are possible for use with 

these appliances.  

Secure Vent

®

 pipe applica-

tions are shown in these figures; 

Secure Flex

®

 

pipe may also be used. A Horizontal Vent Table 

summarizes each system’s minimum and 

maximum vertical and horizontal length values 

that can be used to design and install the vent 

components in a variety of applications. 
Both of these horizontal vent systems terminate 

through an outside wall. Building Codes limit 

or prohibit terminating in specific areas. Refer 

to 

Figure 7

 

on 

Page 9

 for location guidelines.

Secure Vent

 SV4.5 direct vent system components 

are unitized concentric pipe components featuring 

positive twist lock connection, (

refer to 

Figure 22

 

on 

Page 16

)

.  All of the appliances covered in this 

document are fitted with collars having locking 

inclined channels. The dimpled end of the vent 

components fit over the appliance collar to create 

the positive twist lock connection.

A.

 

Plan the vent run -

 

Analyze the vent routing and determine the types 

and quantities of sections required      4-1/2" (114 

mm), 10-1/2" (267 mm), 22 -1/2" (572 mm), 34-

1/2" (876 mm) and 46-1/2" (1181 mm) net section 

lengths are available.  It is recommended that you 

plan the venting so that a joint does not occur in the 

ceiling or roof joists.  Allow for elbows as indicated 

in 

Figure 24

 on 

Page 17

Maintain a minimum 1" (25 mm) clearance to 

combustibles on the vertical sections. Clearances 

for the horizontal runs are; 3" (76 mm) on top, 1" 

(25 mm) on sides, and 1" (25 mm) at the bottom.
B.

 

Frame exterior wall opening -

 

Locate the center of the vent outlet on the ex-

terior wall according to the dimensions shown 

in 

Figure 14

 

on

 

Page 12

.  Cut and/or frame an 

opening, 10-1/2" x 12 -1/8" (267 mm x 308mm) 

inside dimensions, about this center.

C.

 

Frame ceiling opening -

 If the vertical route 

is to penetrate a ceiling, use plumb line to locate 

the center above the appliance. Cut and/or frame 

an opening, 10-1/2" x 10-1/2" (267 mm x 267 

mm) inside dimensions, about this center (refer 

to 

Figure 21

 on 

Page 16

)

.

D. Attach vent components to appliance - 

To 

attach a vent component to the appliance collar, 

align the dimpled end over the collar, adjusting the 

radial alignment until the four locking dimples are 

aligned with the inlets of the four incline channels 

on the collar (

refer to 

Figure 22

  

on 

Page 16

)

.

Push the vent component against the collar until it 

fully engages, then twist the component clockwise, 

running the dimples down and along the incline 

channels until they seat at the end of the channels. 

Vertical

Rise

SV4.5E90

Elbow

Horizontal / Inclined Run

SV4.5HT-2

Termination

Firestop/Spacer

SV4.5L6/12/24/36/48

Vent Sections

Support bracket spacing

every 5 ft (1.52 m)

Vertical Vent

SV4.5HT-2

Termination

Support

Brackets

Building

Support

Framing

Ceiling

Fireplace

Exterior

Wall

Exterior

Wall

TYPICAL HORIZONTAL VENT INSTALLATION

See 

Figure 23 on Page 14

 for 

vertical vent section support

Installation and Operation Instructions

900357-00, 06/2015

Innovative Hearth Products
Superior

TM

 DRT40 Direct Vent Gas Fireplace

Содержание DRT4040DEN

Страница 1: ...ignal tique Cet appareil ne peut tre converti d autres gaz sauf si une trousse de conversion est utils e Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or a...

Страница 2: ...ER LA VITRE L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude et doit tre install pour la protection Des enfants et Des personnes...

Страница 3: ...tengaalosni osalejadosde lachimeneaenfuncionamiento Superviseenformacercanaalos ni osencualquiercuartodondehaya unachimeneafuncionandopara impedirelcontactoconelvidrio Mantenga la ropa mobiliario gaso...

Страница 4: ...designedto operateonnaturalorpropanegas Anelectronic intermittentpilotignitionsystemprovidessafe efficient operation External electrical power is required to operate these units Children and adults sh...

Страница 5: ...of local codes with the National Electrical Code ANSI NFPA 70 latest edition or the Canadian Electrical Code CSA C22 1 latest edition Provide adequate clearances around air open ings and adequate acce...

Страница 6: ...Natural Gas 4 5 WC 1 12 kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 2 Gas Pressure All Models Tables 2 and 3 show the appliances inlet and manifold gas pressure requirements...

Страница 7: ...ible material and wherever cold air could enter the room It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground lev...

Страница 8: ...46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10 12 to 11 12 3 25 0 99 11 12 to 12 12 4 0 1 22 12 12 to 14 12 5 0 1 52 14 12 to 16 12 6 0 1 83 16 12 to 18 12 7 0 2 13 18 12 to 20 12 7 5 2 29 20 12 t...

Страница 9: ...y 36 910 mm within a height of 15 ft above the meter regulator assembly I Clearance to service regulator vent outlet 36 910 mm 36 910 mm J Clearance to nonmechanical air supply inlet to building or th...

Страница 10: ...t a utility shelf in this fashion is shown in Figure 8 Wall Finishes Surrounds Mantels NOTE Combustiblewallfinishmaterialsand orsurroundmaterialsmustnot be allowed to encroach the area defined by the...

Страница 11: ...27 Make connection to gas supply Step8 Page28 Verifyingapplianceoperation Step 9 Page 28 Install the logs decorative volcanic stone and glowing embers Figure 13 Side Nailing Flanges Figure 12 Top Stan...

Страница 12: ...ted of 2x4 or larger lumber Vent Framing Top Vent With One 90 Elbow Based on CSA P 4 1 09 WARNING Failure to position the parts in accordance with these diagrams orfailuretouseonlypartsspecifi callyap...

Страница 13: ...e installed per requirements outlined in the National Fuel Gas Code NFPA 54 latest edition USA or CAN CGA B149 1 latest edition Canada Also see Figure 14 on Page 10 Figure 16 Route Gas Line Step 2 ROU...

Страница 14: ...les ships uninstalled in literature bag 1 U shaped vent restrictor ships uninstalled in literature bag 1 top vent flue restrictor ships uninstalled and taped to log set in firebox Vent Restrictor Inst...

Страница 15: ...5 7 9 1 1 0 0 0 5 6 5 1 4 2 5 2 1 0 2 0 0 0 7 0 7 6 4 2 5 0 2 1 0 0 7 0 8 2 5 2 1 2 0 1 0 7 0 8 4 6 2 2 2 0 0 1 7 0 8 6 7 2 3 2 0 0 0 8 0 8 9 7 2 5 2 3 2 0 0 0 0 6 6 5 0 8 2 5 7 3 3 2 1 0 0 8 0 9 5 3...

Страница 16: ...d of a standard SV4 5 vent component the required distance and secure with three screws Maintain a minimum 1 25 mm clearance to combustiblematerialsforallverticalelements Clearances for all horizontal...

Страница 17: ...king anyofthepreviouslyconnectedventsections See Figure 24 Figure 24 SV4 5E90 90 Elbow 8 1 8 206 mm Swivel Joint 360 swivel 4 13 16 122 mm SV4 5E45 45 Elbow Swivel Joint 360 swivel C D Storm Collar K...

Страница 18: ...llowed2feetof H horizontalrun upto a maximum horizontal run of 8 feet TABLE A H Maximum V Minimum feet feet 2 0 610 1 0 305 4 1 219 2 0 610 6 1 829 3 0 914 8 2 438 4 1 219 V H 40 feet 12 2 meters Max...

Страница 19: ...le If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V verti cal you are allowed 5 feet of H...

Страница 20: ...un ratios that are smaller are acceptable all the way down to at or near level Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to...

Страница 21: ...The SVHRK cap is for use with flex vent Theverticaldistancebetweentheinletandoutlet of the cap is 28 711 mm pipe IMPORTANT The vent termination is hot while in operation and for a period of time follo...

Страница 22: ...y from the fireplace The rise per foot run ratios that are smaller are acceptable all the way down to at or near level See Table 8 as an aid in venting component selection for a particular range of ex...

Страница 23: ...For every 1 foot of V vertical you are allowed 5 feet of H horizontal run up to a maximum horizontal run of 20 feet See Table 8 on page 22 as an aid in venting component selection for a particular ran...

Страница 24: ...to a maximum horizontal run of 20 feet An elbow is acceptable as 1 foot of verti cal rise except where an elbow is the only vertical component in the system See Figure 38 V Minimum feet feet 5 1 524...

Страница 25: ...verthepreviouslyinstalledsectionorappliance collar adjusting the radial alignment until the four locking dimples of the adaptor are aligned with the inlets of the four incline channels of the last ven...

Страница 26: ...fois l entretien termin Refer to Section A for millivolt appliances and Section B for electronic appliances The gas valve is set in place and pre wired at the factory on both models A Millivolt Wiring...

Страница 27: ...er control compartment door see Figure 51 by lifting up approximately 1 2 and then swinging the door open The door is hinged at the bottom Remove the bottom compartment door by sliding the hinge pin l...

Страница 28: ...When the gas lines are tested and leak free be sure to rinse off the leak testing solution TEST ALL CONNECTIONS FOR GAS LEAKS FACTORY AND FIELD WARNING Never use an open flame to check for leaks MILLI...

Страница 29: ...at rest on lower logs do so over notches indentsornubs Properlogplacement is critical to prevent sooting Logs should be placedinthegapsbetweentheflamepeaksand should be positioned so they do not impin...

Страница 30: ...gnTheHolesInOneEndOfLogs2and3OverThe Locating Pins And Align The Grooves On The Other End Over The Grate And Push It Toward The Rear Locating Pin 2 3 Align The Groove In The Bottom Of Log 4 Over The G...

Страница 31: ...ide of the frame Gasket surface must be clean free of irregularities and seated firmly Position the door in front of the firebox opening with the bottom of the door held away from the fireplace Figure...

Страница 32: ...serving the flame continu ously to ensure that the proper flame ap pearancehasbeenachieved Ifthefollowing conditions are present adjust accordingly If flame appears weak or sooty adjust the air shutte...

Страница 33: ...ral qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 S...

Страница 34: ...ervicing an appliance must be replaced priortooperatingtheappliance NOTE If the barrier becomes damaged the barrier shall be replaced with the manufacturer s barrier for this appliance Forusewithbarri...

Страница 35: ...tion Guard Hori zontal Square 12 pack Ref instr 750109M 87L02 SV4 5HGS Termination Guard for Horizontal Square Termi nation Deluxe 1 pack Ref instr 750055M H5820 SV4 5HTSK Termination Shroud Guard for...

Страница 36: ...he door diagonally to the left away from the fireplace Step3 Removethefrontglassdoor framefrom the appliance see instructions on Page 30 Step 4 Carefully remove the logs Exercise care so as not to bre...

Страница 37: ...e the burner and hold the venturi tube above the orifice Place the shutter adjusting rod in the propane slot of the shutter arm see Figure 62 on Page 31 Set the burner assembly into its position and s...

Страница 38: ...est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le installez une barri re de s curit cette mesure emp chera les tou...

Страница 39: ...ueta enlasuperficiedelaplacadelinterruptorquecontrola la chimenea Figura A o en el termostato de pared Figura B Seleccione el idioma que m s se habla en la casa 2 Si se usa un control remoto para cont...

Страница 40: ...ce ou autres liquides produisant des vapeur inflammables loin de l appareil APPLIANCE INSTALLATION SERVICE AND MAINTENANCE NOTICES WARNING Improper installation adjustment alteration service or mainte...

Страница 41: ...ead inlet and outlet side of the valve refer to Figures 68 and 69 Propane tanks are at pressures that will cause damage to valve components Verify that the tanks have step down regulators to reduce th...

Страница 42: ...t side to the right until it disengages from the left corner post hole Pull the door diagonally to the left away from the fireplace To close the hinged drop down panel rotate the panel back into an up...

Страница 43: ...ll control the appliance ON OFF operation To operate Toggle the switch between its ON and OFF positions If your millivolt appliance is equipped with an optional remote wall switch or remote control ki...

Страница 44: ...include ensuring that exhaust or intake passages are unobstructed and vent components are properly assembled and not damaged Homeowner must contact a qualified service technician at once if any abnor...

Страница 45: ...Door Spring Latch Glass Door Firebox Floor Bottom Vee flange Glass Door Frame Top Flange Glass Door Frame WARNING Donotattempttosubstitutethe materialsusedonthesedoors or replace cracked or broken gl...

Страница 46: ...edinthegapsbetweentheflamepeaksand should be positioned so they do not impinge the flames Step5 Positiontheindividuallogsasshownin Figure 73 Logs should be placed in the order shown All logs that have...

Страница 47: ...he Holes In One End Of Logs 2 3 Over The Locating Pins And Align The Grooves On The Other End Over The Grate And Push It Toward The Rear Locating Pin 2 3 Align The Groove In The Bottom Of Log 4 Over T...

Страница 48: ...ke or soot present first check the log set positioning to ensure that the flames are not impinging on any of the logs If the log set is properly positioned and a sooting condition still exists then th...

Страница 49: ...ition and the burner OFF ON switch OFF and remote switches if applicable 5 When satisfied that the burner flame appear ance is normal re install the lower control compartment door then proceed to fini...

Страница 50: ...________________________________ Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the appliance 2 The...

Страница 51: ...ndlowvoltageelectronic ignition controls Kit includes Remote and Receiver Wall Thermostat Wall surface mounted Thermostat or manual ON OFF operation Large LCD screen to display room and set temperatur...

Страница 52: ...unit mounted switch Unit Mountable ON OFF Rocker Switch Kit Millivolt systems only The rocker switch may be used to provide ON OFF operation as an alternative to the optional wall switch The rocker sw...

Страница 53: ...ces Order to replace materials as part of the periodic maintenance of the appliance Firebox Accessories Parts Cat No Model No Description 88L53 FGE Bag of Glowing Embers 80L42 FDVS Bag of Decorative V...

Страница 54: ...ssive condensation can be caused by long lateral runs too many elbows and or exterior portions of the system being exposed to cold weather Also inspect the wall straps or plumbers s tape to ensure the...

Страница 55: ...S TO APPLIANCE If the pilot will not stay lit after several tries turn the gas control knob to OFF and call your service technician or gas supplier 10 Turn gas control knob counterclockwise to ON 11 C...

Страница 56: ...z Si la veilleuse ne reste pas allum e apr s plusieurs tentatives r glez la manette d admission du gaz la position OFF et appelez un technicien qualifi ou le fournisseur de gaz 10 Tournez le bouton de...

Страница 57: ...besoin 8 Placez l interrupteur du r cepteur en position REMOTE ou l interrupteur mural en position ON 9 Si applicable Appuyez sur le bouton ON OFF pour s lectionner ON 10 Si applicable Ajustez le ther...

Страница 58: ...embly 3 Turn off all electric power to the appliance if service is to be performed Note The control may have a battery backup remove batteries if installed 4 Close the main line gas shut off valve 1 S...

Страница 59: ...ection between the valve and thermocouple are tight and secure 3 Pilot burning no gas to burner Valve knob ON and the standard burner OFF ON switch is ON Read impor tant note below IMPORTANT NOTE If a...

Страница 60: ...ng the sensor Call a service technician D Obstructed vent system Call a service technician 4 Soot is present on the glass and panels A Initial fireplace operation A white film may develop on the glass...

Страница 61: ...Gasket Venturi Tube Mounting 43K85 1 43K85 1 20 Gas Line Flexible Connector 93L32 1 93L32 1 WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifi...

Страница 62: ...SCALE REPLACEMENT PARTS 4 8 14 7 40 31 33 32 34 36 35 16 30 13 17 19 11 9 1 12 21 10 15 20 40 AND 45 41 42 43 6 Installation and Operation Instructions 900357 00 06 2015 Innovative Hearth Products Su...

Страница 63: ...tional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide pro...

Страница 64: ...2015 Innovative Hearth Products SuperiorTM DRT40 Direct Vent Gas Fireplace P900357 00 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials speci...

Отзывы: