
9
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Chimney
Termination
Cap
Storm
Collar
Roof
Flashing
Ceiling Support
Assembly
Slip
Adaptor
Chimney
Connector
6” x 24” 24-gage
black steel or 26
gage blued steel
single wall pipe
Using 6” Diameter Single Wall Connector Pipe or
Using 6” Diameter Type L-Vent Connector Pipe
(Recommended for Cold Climate Installations)
Figure 6 - Typical Installation
Floor
Protector
Fasten each stove pipe
connection with at least
3 sheet metal screws.
Single wall stove pipe
must not pass through
attics, closets, walls or
ceilings. It is used to
connect this appliance
to a factory built or
masonry chimney.
Fasten stove pipe to
flue collar with 3 sheet
metal screws.
Stove
Side View
TYPICAL INSTALLATIONS
Minimum of 12-15’
of Flue is required to
achieve a stable draft.
CHIMNEY INSTALLATION
• Install chimney as per manufacturer’s instructions. Some brands of
pipe may require removal of the spacer ring in the flue collar.
• All horizontal runs of pipe should be as short as possible and are
required by NFPA No. 211 to have an upward pitch or rise in the same
direction the smoke travels of no less than 1/4” to the linear foot. The
connector pipe must meet minimum clearances in any direction to
walls or other combustible materials. It must attach to a listed double
wall metal chimney at least 6” in diameter or to a masonry chimney
with a flue passage of at least 48 square inches.
• It is required that a chimney connector pipe not extend further than
the inner wall of the flue when it is connected to a masonry chimney
and that it either be cemented to the masonry or be installed without
cement in a thimble connected to the masonry wall. When the
connector is inserted into a thimble, the joint must be tight enough
so that it will not be dislodged in normal use.
• Chimney connector pipes should never pass through a floor, ceiling,
fire wall, partition, or combustible construction of any type unless
certain precautions are taken. The best method is to use a listed
thimble and a listed chimney in accordance with the manufacturer’s
directions. NFPA No. 211 gives approved methods for passing a flue
pipe through combustible constructions (see
Page 11
).
Approved Chimney -
Your stove is approved for use with Class A, UL
103 HT (U.S.) / ULC-S629 (Canada) Listed Residential Type and Building
Heating Appliance Chimney (HT chimney - 2100° Fahrenheit) and double
wall connector pipe
.
Approved chimney brands are Security Chimneys™,
Jakes Evans/GSW, Dura-vent, Metal Fab, Ameri-Tec, Metalbestos, Indus-
trial Chimney (ICC) and IHP Snap Pak.
Clearances to connector shall be measured from 6” flue collar. Restric-
tions apply! Read instructions before installing.
YOUR CHIMNEY INSTALLATION MUST COMPLY WITH LOCAL
BUILDING AND FIRE CODES.
INSTALL VENTING SYSTEM PER VENT MANUFACTURERS
INSTRUCTIONS!