background image

Superiorfireplaces.US.com

127055-01C

12

A gas line or gas log lighter may be installed for the purpose of 

installing a vented or vent-free decorative gas appliance incorporat-

ing an automatic shutoff device and complying with the Standard 

for Decorative Gas Appliances for Installation in Vented Fireplaces, 

ANSI Z21.60 or American Gas Association draft requirements for 

Gas Fired Log Lighters for Wood Burning Fireplaces, Draft NO. 4 

dated August, 1993.

If  you  wish  to  install  an  unvented  (vent-free)  gas  log  set,  only 

unvented gas log sets which have been found to comply with the 

standard for unvented room heaters, ANSI Z21.11.2 are to be installed 

in this fireplace.
Gas line hook up should be done by your supplier or a qualified 

service person.

Note:

 Before you proceed, make sure your gas supply is turned off.

Use only a 1/2" black iron pipe and appropriate fittings.
1.  Remove knockout indentation on refractory or firebrick wall 

located above refractory hearth floor. Knockout indentation must 

be firmly tapped with any solid object, such as a 1/2" dowel, until 

it is released. Remove fragmented portions of refractory (see 

Figure 19, page 13).

2.  Remove gas line cover plate located on either side of fireplace and 

pull out insulation from gas line conduit sleeve. Save insulation 

for reuse.

3.  Run a 1/2" black iron gas line into fireplace through rear at 

gas line conduit sleeve (if using a raised platform, add height). 

Provide sufficient gas line into fireplace chamber for fitting 

OPTIONAL GAS LINE INSTALLATION

VENTING INSTALLATION 

Continued

connection (see Figure 20, page 13).

  Note: Secure incoming gas line to wood framing to provide rigidity 

for threaded end.

4.  Repack insulation around gas line and into sleeve opening. Seal 

any gaps between gas line and refractory knockout hole with 

refractory cement or commercial furnace cement. Install gas 

appliance or cap off gas line if desired.

 CAUTION: All gas piping and connections must be 

tested for leaks after installation is completed. After 

ensuring that gas valve is on, apply soap and water 

solution to all connections and joints. Bubbles forming 

show a leak. Correct all leaks at once. DO NOT USE 

AN OPEN FLAME FOR LEAK TESTING AND DO NOT 

OPERATE ANY APPLIANCE IF A LEAK IS DETECTED. 

LEAK TESTING SHOULD BE DONE BY A QUALIFIED 

SERVICE PERSON.

Note: 

An IHP hood must be installed when using an unvented gas 

log set (see 

Accessories

 on page 18).

 WARNING: Do not operate an unvented gas log 

set in this fireplace with chimney removed.

30E-12DMO-8DMR

30E-12DMO-8DMR

30E-12DMO-8DMR

EFFECTIVE HEIGHT 

OF TERMINATION CAP

EFFECTIVE HEIGHT 

OF TERMINATION CAP

EFFECTIVE HEIGHT 

OF TERMINATION CAP

EFFECTIVE HEIGHT 

OF TERMINATION CAP

MINIMUM

HEIGHT

14 

1

/

2

  

FT.

14 

1

/

2

  

FT.

MINIMUM

UP TO 

6FT. MAX.

UP TO 

6FT. MAX.

HEIGHT

STARTER

SECTION

STARTER

SECTION

MIN. HEIGHT 

OF 22 FT. (WITH

2 ELBOW SETS)

MAX. HEIGHT OF

50 FT.

MAX. HEIGHT

50 FT.

(ANY SYSTEM)

STARTER

SECTION

Figure 21 - Typical Residential Installations

Содержание WRE3036RH

Страница 1: ...explosion may result causing property damage personal injury or death AVERTISSEMENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incindie...

Страница 2: ...er control b Use of any component part not manufactured or approved by IHP in combination with an IHP fireplace system Proper installation is the most important step in ensuring safe and continuous op...

Страница 3: ...treat insects and fungus When burned thesechemicalscanposeasignificanthazard WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide...

Страница 4: ...COMBUSTIBLE WALL BOARD TOP SPACERS 0 TO 1 AIRSPACE TO COMBUSTIBLE MATERIAL NO COMBUSTIBLE MATERIAL ON FACE NO COMBUSTIBLE MATERIAL BELOW TOP SPACERS GAS LINE KNOCK OUT AIR KIT KNOCK OUTS GAS LINE STA...

Страница 5: ...Height for Outdoor Installation The minimum height of the chimney measured from the base of the fireplace to the flue gas outlet of the termination is 8 feet minimum of 4 feet of chimney pipe sections...

Страница 6: ...f Combustible Materials Fireplace Opening Non Combustible Materials Below Top Spacer Upper Section of Fireplace DRAIN PAN DP42 For outdoor installations the fireplace enclosure must allow for adequate...

Страница 7: ...gained after fitting overlaps must be taken into consideration lineal gain and are given in lineal gain chart see Figure 6 Lineal gain is actual measurable length of a part after two or more parts are...

Страница 8: ...R 30 Offset return elbow A section or sections of chimney may be used between offsets and return elbow Transition pipe must be used after elbow offset is attached 1 To achieve desired offset you may i...

Страница 9: ...ntinued Figure 8 Typical Offset Installation 30E 8DM Return Elbow 30E 8DM Return Elbow 30E 8DM Offset Elbow 30E 8DM Offset Elbow 30E 12DMO 8DMR Offset Elbow 30E 12DMO 8DMR Offset Elbow 30E 12DMO 8DMR...

Страница 10: ...ening into a living space above firestop must be placed onto ceiling from below as shown in Figure 10 They also provide complete separation from one floor space to an other or attic space as required...

Страница 11: ...aterial use only noncombustible mortar or adhesive Storm Collar Installation SC1 Place storm collar over pipe and slide down until it is snug against open edge of flashing see Figure 14 Use SC1 for al...

Страница 12: ...ne conduit sleeve if using a raised platform add height Provide sufficient gas line into fireplace chamber for fitting OPTIONAL GAS LINE INSTALLATION VENTING INSTALLATION Continued connection see Figu...

Страница 13: ...lass WARNING FIREPLACESEQUIPPEDWITHDOORS SHOULD BE OPERATED ONLY WITH DOORS FULLY OPENORDOORSFULLYCLOSED IFDOORSARELEFT PARTLYOPEN GASANDFLAMEMAYBEDRAWNOUT OF THE FIREPLACE OPENING CREATING RISKS OF B...

Страница 14: ...t These coverplatesmustbekeptintheproperlocationpriortousingthefireplace See Figure 23 For further operating guidelines instructions and warranty informa tion please refer to your homeowner s guide or...

Страница 15: ...Refractory Textured Red Herringbone 1 11 107816 03 Rear Refractory Textured White Brick 1 108171 03 Rear Refractory Textured White Herringbone 1 107816 02 Rear Refractory Textured Red Brick 1 108171...

Страница 16: ...27 4 32 34 19 12 25 20 30 17 8 1 5 21 2 35 18 11 14 3 13 22 10 6 39 31 7 37 38 36 28 29 24 23 15 PARTS WOOD BURNING FIREPLACE MODELS WRE3042WS WRE3042WH WRE3042RS WRE3042RH MODEL NO CATALOG NO WRE3042...

Страница 17: ...ge 15 Bottom Rear Refractory 1 13 See Page 15 Bottom Front Refractory 1 14 106683 01 Firebox Support Leg 4 15 Damper Can Collar 1 16 107839 01 Screen Rod 2 17 Firebox Top Assembly 1 18 106703 01 Air K...

Страница 18: ...WITH SLIP SECTION RTT 8DM MESH ROUND TOP TERMINATIONS WITH SLIP SECTION RTTL 8DM ACCESSORIES DOUBLE WALL PIPE 12 8DM 12 8HT 18 8DM 18 8 HT 24 8DM 24 8HT 36 8DM 36 8HT 48 8DM 48 8HT ROOF FLASHING 0 TO...

Страница 19: ...delivery services IMPORTANT NOTICE A manufactured shroud which has been approved by a national testing agency for use with this fireplace may be used if installed in accordance with the instruc tions...

Страница 20: ...n design materials specifications pricesandalsotodiscontinuecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2013 IHP LLC P N 127055 01 Rev C 06...

Отзывы: