background image

Superiorfireplaces.US.com

127055-01C

11

VENTING INSTALLATION 

Continued

CHASE INSTALLATIONS

Instructions for chase installations are included with chase style ter-

mination chosen. In a multiple chase installation, be sure to provide 

adequate distance between terminations to prevent smoke spillage 

from one termination to another. We suggest that terminations be 

separated at least 24", center to center and stacked at a vertical height 

difference of 18" (see Figure 16).

Note:

 If a decorative shroud is to be installed, contact manufacturer 

for specifications.

24" Min.

24" Min.

18" 

Min.

Figure 16 - Multiple Chase Installation

10'

2' Min.

10'

3' Min.

2' Min.

3' Min.

Level of 

Flue Gas 

Outlet

Figure 17 - 10 Foot Rule

10 FOOT RULE

All flue gas outlet chimney terminations must extend a minimum of 

3 feet in height above highest point where it passes through roof and 

must be at least 2 feet above highest point of the roof that is within 

a horizontal distance of 10 feet (see Figure 17).

FINISHING FIREPLACE

Combustible materials, such as wallboard, gypsum board, sheet 

rock, drywall, plywood, etc., may make direct contact with sides and 

top around fireplace face. It is important that combustible materials 

do not overlap face itself. Brick, glass, tile or other noncombustible 

materials may overlap front face provided they do not obstruct es-

sential openings such as louvered slots. When overlapping with a 

noncombustible facing material, use only noncombustible mortar 

or adhesive.

Storm Collar Installation (SC1)

Place storm collar over pipe and slide down until it is snug against 

open edge of flashing (see Figure 14). Use SC1 for all round termina

-

tions. Apply waterproof caulk around perimeter of collar to provide 

a proper seal.

Figure 14 - Storm Collar

Chimney 

Pipe

Waterproof 

Caulk

Storm 

Collar

Flashing

Terminations/Spark Arrestor

Fireplace system must be terminated with listed round top or chase 

terminations. In any case, refer to installation instructions supplied 

with termination. Terminations approved for this fireplace are RT-

8DM, RTL -8DM and RLT-8DM that can be used for flashing or chase 

and ET-8DM, ETO-8DM, ETL-8DM and ETLO-8DM for chase style ter

-

mination only. Figure 18 shows an RTL-8DM round top termination.

 CAUTION: Do not seal openings on the rooftop 

flashing. Follow the installation instructions provided 

with the termination being used.

Terminations with 16" slip pipe sections are available. RTT-8DM, 

RTTL-8DM and RLTT-8DM are approved for flashing installations. 

When needed, these adjustable terminations may be used in combi

-

nation with pipe assembly to achieve correct chimney height.

Note:

 In the rare instance there is a problem with side driven rain or 

wind or chimney is not drafting properly, an ADS-8DM (Anti-Draft 

Shield) can be used with round terminations.

Attach Bracket 

Tabs to 

Outer Pipe 

(3 Places) 

Secure with 

Screws

RTL-8DM

Level of Flue 

Gas Outlet

Caulk

Collar

Flashing

Underlap Shingles 

Bottom Only

Figure 15 - Termination

Overlap 

Shingles Top 

and Sides

Flue Pipe of 

RTL-8DM 

Inside Inner 

Pipe of 

Chimney

Содержание WRE3036RH

Страница 1: ...explosion may result causing property damage personal injury or death AVERTISSEMENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incindie...

Страница 2: ...er control b Use of any component part not manufactured or approved by IHP in combination with an IHP fireplace system Proper installation is the most important step in ensuring safe and continuous op...

Страница 3: ...treat insects and fungus When burned thesechemicalscanposeasignificanthazard WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide...

Страница 4: ...COMBUSTIBLE WALL BOARD TOP SPACERS 0 TO 1 AIRSPACE TO COMBUSTIBLE MATERIAL NO COMBUSTIBLE MATERIAL ON FACE NO COMBUSTIBLE MATERIAL BELOW TOP SPACERS GAS LINE KNOCK OUT AIR KIT KNOCK OUTS GAS LINE STA...

Страница 5: ...Height for Outdoor Installation The minimum height of the chimney measured from the base of the fireplace to the flue gas outlet of the termination is 8 feet minimum of 4 feet of chimney pipe sections...

Страница 6: ...f Combustible Materials Fireplace Opening Non Combustible Materials Below Top Spacer Upper Section of Fireplace DRAIN PAN DP42 For outdoor installations the fireplace enclosure must allow for adequate...

Страница 7: ...gained after fitting overlaps must be taken into consideration lineal gain and are given in lineal gain chart see Figure 6 Lineal gain is actual measurable length of a part after two or more parts are...

Страница 8: ...R 30 Offset return elbow A section or sections of chimney may be used between offsets and return elbow Transition pipe must be used after elbow offset is attached 1 To achieve desired offset you may i...

Страница 9: ...ntinued Figure 8 Typical Offset Installation 30E 8DM Return Elbow 30E 8DM Return Elbow 30E 8DM Offset Elbow 30E 8DM Offset Elbow 30E 12DMO 8DMR Offset Elbow 30E 12DMO 8DMR Offset Elbow 30E 12DMO 8DMR...

Страница 10: ...ening into a living space above firestop must be placed onto ceiling from below as shown in Figure 10 They also provide complete separation from one floor space to an other or attic space as required...

Страница 11: ...aterial use only noncombustible mortar or adhesive Storm Collar Installation SC1 Place storm collar over pipe and slide down until it is snug against open edge of flashing see Figure 14 Use SC1 for al...

Страница 12: ...ne conduit sleeve if using a raised platform add height Provide sufficient gas line into fireplace chamber for fitting OPTIONAL GAS LINE INSTALLATION VENTING INSTALLATION Continued connection see Figu...

Страница 13: ...lass WARNING FIREPLACESEQUIPPEDWITHDOORS SHOULD BE OPERATED ONLY WITH DOORS FULLY OPENORDOORSFULLYCLOSED IFDOORSARELEFT PARTLYOPEN GASANDFLAMEMAYBEDRAWNOUT OF THE FIREPLACE OPENING CREATING RISKS OF B...

Страница 14: ...t These coverplatesmustbekeptintheproperlocationpriortousingthefireplace See Figure 23 For further operating guidelines instructions and warranty informa tion please refer to your homeowner s guide or...

Страница 15: ...Refractory Textured Red Herringbone 1 11 107816 03 Rear Refractory Textured White Brick 1 108171 03 Rear Refractory Textured White Herringbone 1 107816 02 Rear Refractory Textured Red Brick 1 108171...

Страница 16: ...27 4 32 34 19 12 25 20 30 17 8 1 5 21 2 35 18 11 14 3 13 22 10 6 39 31 7 37 38 36 28 29 24 23 15 PARTS WOOD BURNING FIREPLACE MODELS WRE3042WS WRE3042WH WRE3042RS WRE3042RH MODEL NO CATALOG NO WRE3042...

Страница 17: ...ge 15 Bottom Rear Refractory 1 13 See Page 15 Bottom Front Refractory 1 14 106683 01 Firebox Support Leg 4 15 Damper Can Collar 1 16 107839 01 Screen Rod 2 17 Firebox Top Assembly 1 18 106703 01 Air K...

Страница 18: ...WITH SLIP SECTION RTT 8DM MESH ROUND TOP TERMINATIONS WITH SLIP SECTION RTTL 8DM ACCESSORIES DOUBLE WALL PIPE 12 8DM 12 8HT 18 8DM 18 8 HT 24 8DM 24 8HT 36 8DM 36 8HT 48 8DM 48 8HT ROOF FLASHING 0 TO...

Страница 19: ...delivery services IMPORTANT NOTICE A manufactured shroud which has been approved by a national testing agency for use with this fireplace may be used if installed in accordance with the instruc tions...

Страница 20: ...n design materials specifications pricesandalsotodiscontinuecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2013 IHP LLC P N 127055 01 Rev C 06...

Отзывы: