background image

INSTALLATION INSTRUCTIONS FOR MASONRY APPLICATIONS FOR 

BOTH UNITED STATES AND CANADA
WARNING: Before starting the installation, the masonry chimney must 

be inspected by a qualified chimney sweep.

The following requirements must be followed:

1.  The chimney must be absolutely clear of any soot residue or creosote.  

Check for cracks, loose or missing bricks that could inhibit correct 

installation of the liner.

2.  The clearance to combustible must be a minimum of 1” between the 

outside of the masonry and any wood framing or loose insulation.

3. The chimney must be built in accordance with the current building 

code.

4. No other appliance can be connected to the same chimney. 

5. The clearances to combustible for these fireplace connectors are 2” 

on the side and bottom and 16” at the top.

6.  The connector parts are not necessary if the connection between the 

insulated length and the stainless steel liner is done within the masonry 

chimney.

Installation:

Rigid stainless liner or stainless flex must be used and listed to UL-1777 

for US applications and ULC-S635 for existing masonry  or ULC-S640M 

for new masonry applications in Canada. The steel rigid or flex liner must 

be rated at 2100º F (1100º C).

Follow these steps:

1.  Position the fireplace in its location.  Temporarily install the 30° insu-

lated elbow on the top of the fireplace and, using a level, mark with an 

oval the location where the flue liner will enter the masonry chimney.

2. In the middle of the oval, drill a hole in the masonry chimney at 30º.

3.  Increase the size of the hole until a 30º liner elbow can be easily slipped 

through.

4. Slide the liner down from the top of the masonry chimney until you 

reach the hole level.

5. Slip through the hole a 30º liner elbow and connect it to the liner.

6.  Add a small liner section to the other end of the liner elbow which will 

allow the liner to extend at least 12” (measured at the top of the liner) 

from the masonry chimney.   

7. Seal the opening around the liner with high temperature refractory 

cement. 

8. The next steps must be done in the following order: 

See typical installation illustrated below (Figure 40).

A. Select the insulated pipe length that will fit between the 30° insulated 

elbow on top of the appliance and the exposed liner so that it will slide 

at least 2” over the liner section (You may need to cut the liner for a 

better fit).

B. Take that section and attach the pipe to the insulated liner connector 

and slide it over the liner.  Make sure you have enough opening to be 

able to install the elbow without difficulty.

C. Install the 30º elbow on the fireplace.

D. Slide the length section back down on the elbow and twist lock the 

two together.

E.  Pull the cover down over the length and install the insulation pad over 

the liner; be careful to cover the liner completely.

F.  Slide back the cover over the insulation and fix it in place using the 3 

metal screws supplied.

Figure 40

FIREPLACE

1” Clearance

* Insulated Elbow

*

 

ASHT or

3 Screws

Insulation 

Pad & Cover

(BISUMA)

High-Temp. 

Cement

Firestop

Tubinox

*

 or Projet SS 

*

 

Stainless Steel Liner 

**

Insulated

Length

Masonry Chimney, 

New or Existing

Tubinox or Projet SS

*

 Liner 

Must Slide at Least 2” 

Inside Length 

**

6’ 8”

22

Содержание WCT4820

Страница 1: ...hot during operation and will retain heat for a while after shutting off the appli ance Severe burns may result Carefully supervise children in the same room as appliance If small children are presen...

Страница 2: ...gths Elbows where necessary Associated components as per these installation instructions 6 diameter chimney Canada Models ASHT S2100 manufacture by Security Chimneys or DuraTech Canada DTC manufacture...

Страница 3: ...ys ensure that the air inlet to the fireplace is free from debris and any other obstructions that can block the entrance of air WARNING Neither the manufacturer nor the seller warrants smoke free oper...

Страница 4: ...the primary air and air boost controls fully openedduring10to20minutesafterreloading depending on the heat and on the moisture content of the wood Onceyouhavereachedthedesiredtemperature the air boost...

Страница 5: ...mmended Carbon Monoxide Poisoning Early signs of carbonmonoxidepoisoningaresimilartotheflu withheadaches dizzinessand ornausea Ifyou have these signs obtain fresh air immediately Somepeoplearemoreaffe...

Страница 6: ...The use of a firewood moisture meter is rec ommended to ensure the firewood contains less than 20 moisture Seasoning Guide Softwoods 6 months to 18 months Hardwoods 12 months to 24 months Logsthatare5...

Страница 7: ...ng the hinge screws Figure 5 Figure 6 Door Installation Figure 7 Hinge Screws Gasket Adjustment Screw 1 2 3 7 6 5 4 WARNING Use only a IHP glass doors specifically designed for the WCT4820WS fireplace...

Страница 8: ...of the fireplace The combustible floor in front of the fireplace must be covered with a non combustible ma terial tile marble stone etc See Figure 9 COLD CLIMATE INSTALLATIONS Climates where temperat...

Страница 9: ...ols closed the glass will tend to get dirty unless the fuel firebox and glass are maintained at hot temperatures see RefuelingForBestPerformance Tocleanthe glass there are a number of specially design...

Страница 10: ...ion instructions Productdesigns materials dimensions specifications colors and pricesaresubjecttochangeordiscontinu ance without notice All framing dimensions calculated for 1 2 dry wall at the firepl...

Страница 11: ...t Be Used To Cover Chase Opening 8 Level 8 2 4 m Level Outside Base Insulation Thermal Barrier Solid Continuous Surface NOTE Itisrecommendedthatthechasewalls andfloorbeinsulatedinthesamemanner usingth...

Страница 12: ...e than ten 10 feet 3050 mm above the base of the fireplace C The fresh air must come from outside the house Theairintakemustnotdrawairfrom the attic basement or garage D The air intake should be insta...

Страница 13: ...Phillips screwdriver GENERAL INFORMATION If you encounter any problems need clarification of these instructions or are not qualified to properly install this kit contact you local distribu tor or dea...

Страница 14: ...Min Duct Ring Duct Adaptor Tab It is recommended that the ducted flex kit duct system be installed in the following order 1 Plan and frame fireplace and outlet locations prior to ducted flex kit insta...

Страница 15: ...grill The minimum height from thebottomoftheunittothecenteroftheoutletis68 1 7m with the minimum distance from the center of outlet to the ceiling and for the center of the outlet to a side wall of 1...

Страница 16: ...chieved by having the chimney supported by the supports The maximum chimney length that can be supported by the fireplace is nine 9 feet 2 75 m 6 The chimney must extend at least three 3 feet 915 mm a...

Страница 17: ...er of equal size to the joist should be used Figure 26 FEMALE END MALE END BUTTON LOCK ATTACH FOR LOCK Figure 27 INSULATION SHIELD CAT NO SPIS NAIL FIRESTOP CAT NO SPFS Chimney Flue Diameter 6 A 12 7...

Страница 18: ...ance to combustibles AT THIS POINT TIGHTEN CLAMPS 11 Slide IHP chimney pipe into top of tee Align male and female ends Push down on pipe sec tions until locked As sections are added it will be necessa...

Страница 19: ...all the next SP chimney section through the roof See Figure 32 NOTE If your roof is already shingled be sure to slide the upper edge under the shingles to prevent leakage 3 Install a bead of caulk aro...

Страница 20: ...verse wind conditions etc may create a need for a taller chimney should smoking occur Additional support is required above the roof if the chimney height exceeds four 4 feet Select the proper support...

Страница 21: ...d with a chimney adaptor suitable for use with IHP SnapPak venting In Canada the use of Security Chimneys ASHT adaptor is required Security part number 6IHP1 or 6IHP2 One inch wall Two inch wall Figur...

Страница 22: ...chimney at 30 3 Increase the size of the hole until a 30 liner elbow can be easily slipped through 4 Slide the liner down from the top of the masonry chimney until you reach the hole level 5 Slip thro...

Страница 23: ...90 OPTIONAL INSTALLATION ACCESSORIES Fireplace Kits Description Cat Part No Blower heat activated on off pre wired UZY5 UZY5 Blower motor speed control wall mount VRUW VRUW Central Forced Air Kit Acce...

Страница 24: ...c blower VTU Bracket secondary air tube PR SR2214 Hinge assembly fireplace and door PR SR2395UL Door handle rod and mechanism PR SR2118 Door handle and brass cap PR SR2325 Door handle brass cap POIGNE...

Страница 25: ...and Misc Chimney Components 8 length 6 Dia 6DTC 08SS 12 length 6 Dia 6DTC 12SS 18 length 6 Dia 6DTC 18SS 24 length 6 Dia 6DTC 24SS 36 length 6 Dia 6DTC 36SS 48 length 6 Dia 6DTC 48SS Adjustable Length...

Страница 26: ...NERIE TEL QUE D CRIT DANS LE MANUEL D INSTALLATION LES COMPOSANTES UTILIS ES AVEC LE FOYER DOIVENT TRE HO MOLOGU ES VOIR LA LISTE DANS LE MANUEL D INSTALLATION REMPLACER LA VITRE AVEC UN VERRE C RAMIQ...

Страница 27: ...l use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burning cha...

Страница 28: ...or any questions or concerns REPLACEMENT PARTS See Page 24 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your IHP di...

Отзывы: