background image

SuperiorFireplaces.us.com

126619-01_K

22

APPENDIX A 

Continued

Smoking –  Causes And Troubleshooting

To reduce the likelihood of smoking when opening the door, open 

the combustion air control or damper before opening the door.  

Your appliance has been designed and tested to provide smoke free 

operation. Occasionally, there may be a small amount of smoking 

upon lighting the fire, until the chimney heats up but this should not 

continue.  If the appliance continues to smoke it is probably for one 

of the following reasons:

A. Negative pressure in the house -

  As the fire burns, air goes up the chimney. This air must be 

replaced through leakage into the house or through the outside 

air duct.  When operating the appliance, open a nearby window 

temporarily to check if there is adequate replacement air supply.

B. Blowers operating (e.g.: range hood) - 

These blowers draw air 

out of the house and may actually cause a negative pressure in 

the house.  Turn off all blowers and open a nearby window to 

determine if this is the cause of the problem.

C. Wet wood -

 Wet or tarred wood will smoulder and smoke instead 

of burning properly. Your dealer can help you determine if you 

have properly seasoned wood for burning.

D. Dirty or blocked chimney -

 Check to make sure the chimney is 

clear and clean. If dirty call a certified chimney sweep or use a 

properly sized chimney brush to clean.

E. Chimney not long enough -

 The minimum chimney height is 

twelve (12) feet (3.7 m) not including the appliance height. The 

chimney must extend at least three (3) feet (915 mm) above 

its point of contact with the roof and at least two (2) feet (610 

mm) higher than any roof or wall within ten (10) feet (3 m) of 

it.  When installed with offsets, the minimum chimney height 

is fifteen (15) feet.  Additional height will increase draft and will 

decrease the tendency to smoke.

F.  Poor chimney draft -

 With no fire, there should be sufficient draft 

to exhaust cigarette smoke introduced under the baffle or flue baffle.  

Chimneys installed against an outside wall without protection may 

generate back draft problems which will cause start-up problems.  

To prevent this, open a nearby window, roll up a piece of paper 

and light it.  Then, hold it in the upper part of the firebox to warm 

up the chimney.  Wait until the draft is sufficient, then start the fire.

G. Blower for forced air kit operating (some models)  -

 Make 

sure that the blower is in the “off” position when you open the 

appliance door for reloading.

Locating The Appliance

The best location to install your appliance is determined by consid-

ering the location of windows, doors, and the traffic flow in the room 

where the appliance is located, allowing space in front of the unit for 

the hearth extension and the mantel, and taking into consideration 

the location of the hot air ducts (some models), outside air kit and 

chimney. 

If possible, you should choose a location where the chimney will pass 

through the house without cutting floor or roof joists.
When selecting the location, the chimney outlet position and the 

direction of the wind are important factor affecting the chimney per-

formance. To allow a maximum draft and to reduce wind turbulence, 

the chimney must:

•  Penetrate the highest part of the roof.

•  Be installed as far as possible of roof offsets, trees or any other 

obstructions that may cause wind turbulence and back drafts in 

the chimney.

•  The least amount of offsets (elbows) possible. 

NOTE:

 A maximum 

of 2 offsets is allowed.

4' 

4' 

8' 

Standard 

Cord of

Wood

8 Ft. 

(2.4M)

4 Ft. 

(1.2M)

4 Ft. (1.2M)

Marginal Location

Wind Direction

Location

Not

Recommended

Outside Air 

Intake

Facing the Wind

Location

Not 

Recommended

Location Recommended

Tree

Figure 1

Figure 2

Prohibited Fuels

These appliances are designed to burn natural well-seasoned wood. 

The wood fuel should be air dried seasoned hardwoods, as compared 

to softwoods or to green or freshly cut hardwoods. Burning artificial 

logs, in some model appliances is allowed (see Installation and Op-

eration manual); please read and follow the instructions provided by 

the manufacturer. DO NOT BURN:

NOTE: The use of a firewood moisture meter is recommended 

to ensure the firewood contains less than 20% moisture.

Seasoning Guide

Softwoods  -  6 months to 18 months

Hardwoods  -  12 months to 24 months
Logs that are 5” diameter across or larger should be split in half, 

three pieces if over 8 inches, and four pieces when over a foot 

across. If a tree has been dead for 2  -  4 years it still needs to be 

cut, split, and seasoned for 6 to 24 months depending on the wood.

• Garbage;

•  Lawn clippings or yard waste;

•  Materials containing rubber, 

including tires;

•  Materials containing plastic;

•  Waste petroleum products, 

paints or paint thinners, or 

asphalt products;

•  Materials containing asbestos;

•  Construction or demolition 

debris;

•  Railroad ties or pres-

sure-treated wood; woods that 

have been dipped in tar, pitch, 

pine tar, creosote, etc.

• Manure or animal remains;

• Salt water driftwood or 

other previously salt water 

saturated materials;

• Unseasoned wood;

• Christmas tree branches;

• Paper products, colored 

paper, cardboard, plywood, 

or particleboard; 

• Gasoline;

• Naphtha;

• Engine Oil; 

• Flammable Liquids; 

• Solvents;

• Grease; or

• Charcoal or Coal

Содержание Pro Series

Страница 1: ...ge 20 FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit POUR LE CANADA L autorité compétente comme le service municipal du bâtiment les pompiers etc doit être contacté avant l installation afin de déterminer la nécessité d obtenir un permis This appliance may be...

Страница 2: ...d tested for the fireplace system you may cause a fire hazard The IHP warranty will be voided by and IHP disclaims any respon sibility for the following actions a Modification of the fireplace components doors air inlet system and damper control b Use of any component part not manufactured or approved by IHP in combination with an IHP fireplace system Proper installation is the most important step...

Страница 3: ...anposeasignificanthazard IMPORTANT See appendix A page 21 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide Poisoning Early signs of carbon monoxidepoisoningresemblethefluwithheadaches dizziness or nausea If you have these signs get fre...

Страница 4: ... 8 232 mm 3 1 2 89 mm 3 1 2 89 mm 11 1 2 292 mm 22 559 mm 29 737 mm 41 1042 mm 1 26 mm 1 26 mm 21 534 mm 8 204 mm 35 889 mm 37 940 mm 41 1042 mm 1 26 mm AIRSPACE TO COMBUSTIBLE MATERIAL 0 0 mm TO TOP SPACERS 0 0 mm TO BOTTOM 8 204 mm EACH SIDE NO COMBUSTIBLE MATERIAL ON FACE HEARTH EXTENSION 51 X 16 1296 mm X 407 mm COMBUSTIBLE WALL BOARD NOT LESS THAN 12 305 mm TO PERPENDICULAR SIDEWALL OUTSIDE A...

Страница 5: ... nailing flanges touch side framing 4 Check level of fireplace and shim with sheet metal if necessary 5 Before securing fireplace to prepared framing ember protector must be placed between hearth extension not included and under bottom front edge of fireplace to protect against glowing embers falling through If fireplace is to be installed on a raised platform a Z type ember protector not included...

Страница 6: ...ess than 12 from top opening of fireplace NFPA 211 Section Clearance from Combustible Material Mantels or any other combustible material also may come up to side edge of black metal face of fireplace as long as projections from front face fall within limit shown in Figure 5a 12 1 4 312 mm Ref 15 381 mm Min 12 305 mm Min 6 153 mm Ref 11 2 38 mm Max 3 77 mm Nom 33 Combustible Material Safe Zone for ...

Страница 7: ...attic space The maximum height for the air vent can not exceed 3 feet below the flue gas outlet of the termination CHIMNEY PIPE WARNING Label part number 900599 01 must be applied by the installer to all chimney pipe sections but is not required on sections that will be visible after the installation is complete Label must wrap around the circumference of the pipe See accessories page 20 for Kit F...

Страница 8: ...ce inner flue pipe section must be installed first with lanced side up Outer pipe section can then be installed over flue pipe section with hemmed end up Press down on each pipe section until lances securely engage hem on fireplace starter Wire will assure proper spacing between inner and outer pipe sections Note For Canada use chimney parts designated HT Continue to assemble chimney sections as o...

Страница 9: ...g Support Pipe 12S 8DM 1 26 mm Min Straps Straps Straps Straps Detail A Return Elbow Detail B Angle Firestop See Detail A See Detail B Ceiling Support Pipe 12S 8DM VENTING INSTALLATION Continued Offset Elbow Offset Elbow Offset Elbow Offset Elbow Offset Elbow 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m Ceiling Support Pipe 12S 8DM ...

Страница 10: ...in Figure 13 Figure 12 Firestop Spacer with Living Space Above Ceiling Figure 13 Firestop Spacer with Attic Space Above Ceiling If area above is a living space install firestop below framed hole If area above is an attic or insulated area install firestop above framed hole PENETRATING ROOF To maintain a 1 clearance to pipe on a roof with a pitch a rectangular opening must be cut 1 Determine center...

Страница 11: ...na tions Apply waterproof caulk around perimeter of collar to provide a proper seal Figure 16 Storm Collar Chimney Pipe Waterproof Caulk Storm Collar Flashing Terminations Spark Arrestor Fireplace system must be terminated with listed round top or chase terminations In any case refer to installation instructions supplied with termination Terminations approved for this fireplace are RT 8DM and RLT ...

Страница 12: ...ials such as wallboard sheet rock drywall ply wood etc may make direct contact with sides and top around fire place face It is important that combustible materials do not overlap face itself Brick glass tile or other noncombustible materials may overlap front face provided they do not obstruct essential openings such as louvered slots When overlapping with a noncombustible facing material use only...

Страница 13: ...ment Install gas appliance or cap off gas line if desired CAUTION All gas piping and connections must be tested for leaks after installation is completed After ensuring that gas valve is on apply soap and water solutiontoallconnectionsandjoints Bubblesforming show a leak Correct all leaks at once DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPERATE ANY APPLIANCE IF A LEAK IS DETECTED LEAK ...

Страница 14: ...ass doors operates much differently than a fireplace with an open front A fireplace with glass doors has a limited amount of air for combustion Excessive heat within fireplace can result if too large a fire is built or if combustion air gate is not completely open The following tips should be used to assure that both fireplace and glass door retain their beauty and function properly Both the flue ...

Страница 15: ...e used if installed in accordance with the instructions by its manufacturer A locally fabricated shroud may be used with IHP Shroud Leg Spacer Kit SLK in accor dance with instructions provided with the shroud NOTICE The firebox canopy hood must not be modified or replaced with a canopy that may be provided with the unvented decorative room heater CAUTION THE STRUCTURAL INTEGRITY OF THE MANU FACTUR...

Страница 16: ...RTS WOOD BURNING FIREPLACE MODELS MODEL CATALOG NO WRT3036WS F0659 WRT3036WSI F0660 WRT3036WH F0661 WCT3036WS F0662 WCT3036WSI F0663 WCT3036WH F0664 9 4 28 29 19 12 20 26 17 8 1 5 21 2 30 18 11 14 3 13 22 10 6 27 7 32 33 31 34 24 25 15 16 16 23 ...

Страница 17: ...amper Can Collar 1 16 J8007 Screen Assembly Kit 1 17 Firebox Top Assembly 1 18 Air Kit Door Assembly 1 19 Face Weldment 1 20 J3991 Smoke Deflector 1 21 Fireplace Top Insulation 1 22 Access Panel 1 23 J4381 Grate 1 24 Collar Insulation 1 25 J6893 Chimney Starter Collar 1 26 J6895 Refractory Retainer 2 27 J7003 Grate Retainer 2 28 Door Stop 1 29 J6905 Spring Clip 2 30 J6918 Top Standoff 4 31 J6934 C...

Страница 18: ...Right Stacked White 1 4 Refractory Rear Stacked White 1 5 Refractory Bottom Rear White 1 6 Refractory Bottom Front White 1 WARNING Contact an IHP dealer to obtain any of these parts Never use substitute materials not approved by IHP Use of non approved parts can result in poor performance and safety hazards REFRACTORY STAIN KITS Use the refractory stain kits to give white refractory panels a new l...

Страница 19: ...8HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock 30 OFFSET AND RETURN F0900 30E 8DM 30 Degree Offset and Return F0886 30E 8HT 30 Degree Hi Temp Offset and Return OPTIONAL OUTSIDE AIR KIT FOR FLOOR INSTALLATION F1091 AK4 Co...

Страница 20: ...p Section F0893 ETL 8HT Hi Temp Large Pyramid Top with Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE TOP TERMINATION WITH SLIP SECTION F0923 ETLO 8DM Square Top with Mesh and Slip Section ADJUSTABLE HOOD Required when installing a vent free gas log in this fireplace F1764 GA6050 Black Fireplace Hood F1766 GA6053 Brushed Brass Fireplace Hood FAN KIT F1083 B...

Страница 21: ...onditions inadequate chimney heights adversewindconditionsand orunusualenvironmental factors or conditions beyond our control take into account all variables within the installation and install the appliance in such a manner that satisfies the draft requirements of the appliance See Chimney Guidelines to assist you in selecting the proper venting system for your installation American National Stan...

Страница 22: ...iance The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of the unit for the hearth extension and the mantel and taking into consideration the location of the hot air ducts some models outside air kit and chimney Ifpossible youshouldchoosealocationwherethechi...

Страница 23: ... be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burning characteristics including but not limited to fuel such as driftwood coal or plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the Pro...

Страница 24: ...26619 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A 2013 Innovative Hearth Products LLC P N 126619 01 Rev K 02 2019 1769 East Lawrence Street Russellville AL 35654 ...

Отзывы: