Installation must include an equipment shutoff 
valve, union, and plugged 1/8" NPT tap. Lo-
cate NPT tap within reach for test gauge hook 
up. NPT tap must be upstream from 

fi

 replace 

(see Figure 18).
IMPORTANT

Install equipment shutoff valve 

in an accessible location. The equipment 
shutoff valve is for turning on or shutting off 
the gas to the appliance.
Check your building codes for any special 
requirements for locating equipment shutoff 
valve to 

fi

 replaces.

Apply pipe joint sealant lightly to male NPT 
threads. This will prevent excess sealant from 
going into pipe. Excess sealant in pipe could 
result in clogged 

fi

 replace valves. Never use 

sealant on 

fl

 are threads.

 WARNING: Use pipe joint 

sealant that is resistant to liquid 
petroleum (LP) gas.

We recommend that you install a sediment 
trap in supply line as shown in 

Figure 18

Locate sediment trap where it is within reach 
for cleaning. Install in piping system between 
fuel supply and 

fi

 replace. Locate sediment 

trap where trapped matter is not likely to 
freeze. A sediment trap traps moisture and 
contaminants. This keeps them from going 
into 

fi

 replace gas controls. If sediment trap 

is not installed or is installed wrong, 

fi

 replace 

may not run properly.

INSTALLATION

Continued

Figure 17 - External Regulator on 

Propane/LP Supply Tank with Vent 

Pointing Down

External 
Regulator

Propane/LP 
Supply Tank

Vent Pointing Down 

CONNECTING FIREPLACE TO GAS 
SUPPLY

Installation Items Needed

•  5/16" hex socket wrench or nut-driver
• Phillips screwdriver
•  sealant (resistant to propane/LP gas, not 

provided)

1. Remove 

fi

 replace screen. Remove two 

screws that hold 

fi

 replace screen in place 

for shipping. These screws are located 
near top of screen. Discard screws. Push 
the bottom corners of the screen in and 
release. The screen will pop out at the 
bottom. Grasp the bottom of the screen, 
lift the screen up and pull out to remove.

2.  Remove screws that attach log base as-

sembly to 

fi

 replace 

(see Figure 19, Page 

16)

. Carefully lift up log base assembly 

and remove from 

fi

 replace 

(see Figure 19, 

Page 16)

.

3.  Route gas line (provided by installer) 

from equipment shutoff valve to 

fi

 replace. 

Route 

fl

 exible gas supply line through one 

of the access holes.

4. Attach 

the 

fl

 exible gas line to gas supply 

(see  Figure 20, Page 16)

. Check tight-

ness of 

fl

 exible gas line attached to gas 

regulator of 

fi

 replace 

(see  Figure 20, 

Page 16)

.

5.  Check all gas connections for leaks. See 

Checking Gas Connections

Page 16.

6.  Replace log base assembly back into 

fi

 replace. Feed 

fl

 exible gas line into

** Minimum inlet pressure for purpose of input 
adjustment.

Figure 18 - Gas Connection

3" Minimum

Natural Gas

From Gas 
Meter
(5" W.C.** to 
10.5" W.C. 
Pressure)

Propane/LP

From External 
Regulator
(11" W.C.** 
to 14" W.C. 
Pressure)

Sediment Trap

Cap Pipe  Tee
 Nipple 

Joint

Содержание LBG18BM

Страница 1: ...d gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section...

Страница 2: ...manual for reference It is your guide to safe and proper operation of this heater WARNING FIRE EXPLOSION AND ASPHYXIATION HAZARD Improperadjustment alteration service maintenance orinstallationofthis...

Страница 3: ...s heater with the fireplace screen and hood in place before running heater The fireplace screen shall have openings for introduction of combus tion air Keeptheapplianceareaclearandfreefrom combustible...

Страница 4: ...e powder residue within burner box or on adjacent walls or furniture 10 This fireplace needs fresh air ventilation to run properly This fireplace has an Oxygen Depletion Sensing ODS safety shutoff sys...

Страница 5: ...e connector used shall not exceed 36 inches 92 centimeters in length The individual manual shut off must be a T handle type valve Unvented appliances may NOT be installed in bedrooms or bathrooms A wo...

Страница 6: ...kup heat SAFETY DEVICE This fireplace has a pilot with an Oxygen Depletion Sensing ODS safety shutoff system The ODS pilot is a required feature for vent free room heaters The ODS pilot system shuts o...

Страница 7: ...confined Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them DETERMINING FRESH AIR FLOW FOR FIREPLACE LOCATION Determining if You Have a Confine...

Страница 8: ...200 Btu Hr maximum the space can support 73 000 Btu Hr actual amount of Btu Hr used The space in the example is a confined space because the actual Btu Hr used is more than the maximum Btu Hr the spac...

Страница 9: ...rings or operating heater where impurities such as but not limited to tobacco smoke aromatic candles cleaning fluids oil or kerosene lamps etc in the air exist may discolor walls or cause odors WARNIN...

Страница 10: ...not permitted ELECTRICAL HOOKUP This fireplace includes a blower which must be connected to either a wall receptacle or the electrical receptacle that is included within the fireplace If the receptacl...

Страница 11: ...ce gas regulator to gas supply See Connecting Fireplace to Gas Supply Page 15 9 Route blower electrical cord through ac cess holes in either side of fireplace CONVENTIONAL FIREPLACE INSTALLATION Conve...

Страница 12: ...talling a mantel above the fireplace you must follow the clearances shown in Figure 16 Page 13 Follow the instructions below to install the fireplace in this manner 1 Frame in rough opening Use dimens...

Страница 13: ...ssembly WARNING Do not allow noncombustible materials to cover any necessary openings like louvered slots WARNING Useonlynoncom bustiblemortaroradhesiveswhen overlapping the front facing with noncombu...

Страница 14: ...Use only new black iron or steel pipe Inter nally tinned copper tubing may be used in certain areas Check your local codes Use pipe of 1 2 diameter or greater to allow proper gas volume to fireplace...

Страница 15: ...ulator on Propane LP Supply Tank with Vent Pointing Down External Regulator Propane LP Supply Tank Vent Pointing Down CONNECTING FIREPLACE TO GAS SUPPLY Installation Items Needed 5 16 hex socket wrenc...

Страница 16: ...eaks after installing or servicing Correct all leaks at once WARNING Never use an open flame to check for a leak Applyanoncorrosiveleakdetec tion fluid to all joints Bubbles forming show a leak Correc...

Страница 17: ...off Valve Figure 23 Checking Gas Joints for Propane LP Gas Propane LP Supply Tank Figure 22 Checking Gas Joints for Natural Gas Gas Control Valve Equipment Shutoff Valve Equipment Shutoff Valve Gas Me...

Страница 18: ...contain important safety and warranty information 1 Place fiber ramp log in center of chassis as shown in Figure 28 The fiber ramp log can be identified by the shape and much lighter weight when compa...

Страница 19: ...ke sure the flame from the ember pan does not touch the ember bed log Figure 31 Installing Right Ember Bed Log VRT4036 Right Ember Bed Log Hole Underneath Grate Prong 5 The left middle log has a groov...

Страница 20: ...the rear log and the left middle log Make sure to place the projection on the bottom of the left top log into the recessed areas on the rear and left middle logs see Figure 36 10 Rest the middle cros...

Страница 21: ...bossed on the back of each piece for identification purposes Please note that VRT4032 series burner systems do not include ember chunks 2 Two ember materials are supplied with this log set Platinum Br...

Страница 22: ...ee Page 44 for part numbers 4 Installfireplacescreenbyplacingthescreen brackets on top of the fireplace screen brackets as shown in Figure 42 Push the bottom of the screen inward against the magnetic...

Страница 23: ...ll come on automatically within one minute when the selector switchisintheONpositionafter the pilot is lit 3 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you...

Страница 24: ...nate the backlight will not respond to associated zone function To activate any command the backlight for the screen must be on and the command must be touched before the backlight goes off Powered vi...

Страница 25: ...Intermittent Pilot Ignition IPI Spark to Pilot only continuous standing pilot not allowed Pilot flame will be ignited before turn Main Flame ON LCD Displays MODE Zone ON is displayed ROOM TEMP Zone Me...

Страница 26: ...E Zone Blank THERMOSTAT ON LCD Displays MODE Zone THERMO and ON are displayed ROOM TEMP Zone Measured tempera ture is displayed SET TEMP Zone SET TEMP is dis played TIME PROG Zone Current day indicato...

Страница 27: ...setting To enter Program Setup touch and hold the TIME PROG Zone for 5 seconds Program OFF LCD Displays MODE Zone OFF ROOM TEMP Zone Measured tempera ture is displayed SET TEMP Zone Blank TIME PROG Z...

Страница 28: ...s the control back ON and the room temperature is still 95F or greater the transmitter will switch to back manual OFF and send another OFF command the next time the transmitter reads updates the room...

Страница 29: ...replace is shut off the blower will continue to operate until the fire place temperature cools The blower also includes a variable speed control Turn the knob clockwise to turn the blower to the high...

Страница 30: ...d by fireplace causing brief patches of orange flame Figure 48 shows the correct burner flame The front ember burner should have a small blue flame When the ember material is ap plied the embers will...

Страница 31: ...e Keep these holes clear of dust dirt lint and pet hair Clean these air in let holes prior to each heating season Blocked air holes will create soot We recommend that you clean the unit every three mo...

Страница 32: ...t Outlet Thermocouple To S Terminal on Main Module Main Burner Battery Pack Primary or Backup Dry Contact Switches To Pilot Igniter From Pilot Thermocouple Regulator Inlet Gas Valve Valve Step Motor B...

Страница 33: ...Ignition Electronic Manifold Pressure 8 W C Inlet Gas Pressure in of water Max 14 W C Min 11 W C For purpose of input adjustment SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit bur...

Страница 34: ...tion sequence and observe the voltage while the system is lighting under load The system will not function under 3 8 volts and batteries should be replaced if the voltage is under 4 0 volts 2 Plug pow...

Страница 35: ...ower supply box 7 Check the igniter connection at both the control module and the ODS pilot Connect if loose 8 Free igniter cable if pinched by any metal or tubing Keep igniter cable dry 9 Replace wir...

Страница 36: ...ould be hand tight plus 1 4 to 1 2 turn You should not be able to loosen the thermocouple at the control valve with your hand Check the thermocouple terminal connec tion at the control module If it is...

Страница 37: ...while the system is lighting under load The system will not function under 3 8 volts and batteries should be replaced if the voltage is under 4 0 volts 3 Check thermocouple terminal connection at the...

Страница 38: ...uld work within 20 feet of the burner system If it does not re place the batteries in the remote and battery supply box Burner system shuts off Control module sounds 1 long beep 1 Control module is to...

Страница 39: ...ator Slight smoke or odor during initial operation 1 Residues from manufacturing processes and logs curing 1 Problem will stop after a few hours of operation Heater produces a whistling noise when bur...

Страница 40: ...ng Gas Connections Page 16 2 Replace control valve or gas control Gas odor during combustion 1 Foreign matter between control valve and burner 2 Gas leak See Warning state ment at top of Page 1 Take a...

Страница 41: ...TAGE FIBER LINER KITS Cat No H9076 Model SBLQ32SVF 32 Cat No H9077 Model SBLQ36SVF 36 PERIMETER TRIM ACCESSORY Cat No F1039 Model PT32 Black 32 Cat No F1040 Model PT32B Brass 32 Cat No F1041 Model PT3...

Страница 42: ...8 44 18 17 25 20 35 34 12 12 13 39 38 28 7 6 5 1 10 14 12 23 24 3 4 37 26 32 11 9 Cat No Model F1199 VRT4032ZEN F1201 VRT4032ZEP F1203 VRT4036ZEN F1205 VRT4036ZEP WARNING Contact an IHP dealer to obt...

Страница 43: ...71 Orifice 075 1 90 mm Middle 1 16 J3675 Orifice 0453 1 15 mm Middle 1 17 J8079 Orifice 0 028 0 711 mm Pan 1 17 F3135 Orifice 0 052 1 321 mm Pan 1 17 J3619 Orifice 0 038 0 965 mm Pan 1 18 J6127 Orific...

Страница 44: ...26 Cord Power Supply 1 J3795 Wire Harness 1 J3658 Plate Warning 1 J6207 Kit Platinum Embers 1 J6208 Kit Glowing Embers rockwool 1 F2950 Remote Control ODS Touchscreen 1 F2957 ODS Spark Wire 1 J6585 Pl...

Страница 45: ...5 ASM 32 Fireplace System Screen 1 J6776 ASM 36 Fireplace System Screen 1 7 J6492 Magnet Door Latch 2 8 J6778 Hood 32 Fireplace System 1 J6779 Hood 36 Fireplace System 1 9 J5458 Blower 1 10 J6783 Line...

Страница 46: ...3 J6646 Log Left Middle 1 7 F2944 K2008 Log Right Middle 1 8 J6636 J6647 Log Rear Middle 1 9 J7518 J6648 Log Rear 1 10 J6637 J6637 Log Left Top 1 11 J6638 J6650 Log Middle Crossover 1 12 J6639 J6651 L...

Страница 47: ...tural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a re hazard c da...

Страница 48: ...tributor for fireplace code information Printed in U S A 2016 Innovative Hearth Products P N 900719 00 REV C 04 2018 1508 Elm Hill Pike Suite 108 Nashville TN 37210 SuperiorFireplaces us com Record th...

Отзывы: