background image

Operation 

900966-00B, 04/2019 

Innovative Hearth Products
DRT3000-C Series Direct-Vent Gas Fireplaces

64

 WARNING

The door should easily close without needing to be pressed down. If it has to be pressed 

down to close, the gasket in the top of the door should be dressed so it lays on the glass.

Installing the glass door

1.  Visually inspect the gasket on the backside of the glass door.

NOTE: The gasket surface must be clean, free of irregularities, and seated firmly. Ensure it is properly located. 

Make sure the bead is not rolled into the channel at the top of the door, but remains flat against the top of the 

glass.

2.  Position the door in front of the firebox opening with the bottom of the door held away from the fireplace at a 

45° angle (Figure 62). Hook the top flange of the door frame over the top of the firebox frame.

NOTE: Ensure the glass door is centered—with even spacing on each side.

3.  Let the bottom of the glass door swing gently in towards the fireplace ensuring that the gasket seats evenly 

as the door draws shut. Securely fasten the two (2) latches beneath the firebox floor to the door V-flange. 

IMPORTANT NOTE: The door must close without force.  When installed properly, the bottom of the door should 

not have interference with the fireplace in order to close.  If it does, remove the door and inspect the door gasket 

to ensure it is even and not rolled up at the top. SEE WARNING IN FIGURE 62.

4.  Install the barrier.

5.  Close the control compartment door.

Removing the glass door

1.  Open the control compartment door

2.  Remove the barrier. Place the barrier in a safe location for later reinstallation.

3.  Detach the two (2) door latches beneath the firebox floor.

4.  Swing the bottom of the glass door away from the fireplace to a 45° angle (Figure 62)

5.  Carefully grip the door at the top and bottom, and remove it from the fireplace. Place the door in a safe location 

for later reinstallation.

Figure 62 - Glass Door

Latch

Glass 

Door

Figure 63 - Barrier

NOTE: When installing the glass door, ensure the spacing on both sides is even and equal.

1

2

INSPECT GASKET AND ADJUST IF NECESSARY (see pictures above)

(1) Ensure the gasket is properly positioned, and area to keep clear, is as shown.

(2) Inspect gasket after installation to ensure it appears as shown above.

Inside view 

of glass door 

showing 

proper gasket 

positioning

With door installed, 

ensure gasket is po-

sitioned as shown.

Gasket

Gasket

SEE WARNING BELOW

35” Barrier - Cat. No. F1839
40” Barrier - Cat. No. F1840
45” Barrier - Cat. No. F1903

NOTICE: All DRT3000-C series fireplaces require 

barrier (provided) to reduce the risk of burns from the 

hot viewing glass. The barrier must be installed prior 

to operation.
Replacement barrier catalog numbers are shown here.

Содержание DRT3000-C Series

Страница 1: ...du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installationetl entretiendoivent treassur spar un installateur ou un service d entretien qualifi ou...

Страница 2: ...pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude et doit tre install pour la protection Des enfants et Des personnes risques Vea el vol...

Страница 3: ...si se toca Mantenga a los ni os alejados de la chimenea en funcionamiento Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el...

Страница 4: ...irements 12 Location 12 Vent Termination Clearances 13 Minimum Clearances to Combustibles 15 Wall Finishes Surrounds Mantels 16 Installation Preparation 16 Installation Installation Sequence 17 Constr...

Страница 5: ...t subir des br lures s ils viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou u...

Страница 6: ...dangerous Improper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning CARBON MONOXIDE POISONING Early signs of carbon monoxi...

Страница 7: ...te accessibility clearance for service and proper operation Never obstruct the front openings of the appliance These appliances are designed as supplemental heaters Therefore it is advisable to have a...

Страница 8: ...re l objet d une inspection par un technicien professionnel avant d tre utilis et au moins une fois l an par la suite Des nettoyages plus fr quents peuvent tre n cessaires si les tapis la literie et c...

Страница 9: ...that the tanks have step down regulators to reduce the pressure to safe levels The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure...

Страница 10: ...0 1372 m Model Natural Gas drill size Propane drill size 35 Models 45 0 082 Cat No 39L66 0 048 Cat No 99K78 40 Models 43 0 089 Cat No 99K75 54 0 055 Cat No 99K79 45 Models 40 0 098 Cat No 69L96 53 0 0...

Страница 11: ...n monoxide detector must comply with NFPA 720 be ANSI UL 2034 listed and be ISA certified A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minim...

Страница 12: ...are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace Utility shelves like these are commonly used for locating television sets and decorative plants...

Страница 13: ...22 m 12 12 to 14 12 5 0 ft 1 52 m 14 12 to 16 12 6 0 ft 1 83 m 16 12 to 18 12 7 0 ft 2 13 m 18 12 to 20 12 7 5 ft 2 29 m 20 12 to 21 12 8 0 ft 2 44 m 12 X Roof pitch is X 12 2 ft minimum 2 ft minimum...

Страница 14: ...to nonmechanical air supply inlet to building or the combustion air inlet to any other fireplace 6 150 mm for fireplaces 10 000 Btu h 3 kW 9 230 mm for fireplaces 10 000 Btu h 3 kW and 50 000 Btu h 1...

Страница 15: ...d at each side of the unit and any screw heads adjacent to it When in top vent mode no combustible material shall be allowed to contact the rear flue cap cover Hearth Extension A hearth extension is n...

Страница 16: ...e the fireplace NOTE To avoid heat related finish damage we recommend the use of high temperature paint rated 175 F or higher on the underside of the mantel INSTALLATION PREPARATION The fireplace is s...

Страница 17: ...g Page 37 Gas Connection 12 Connect the Gas Line Page 39 13 Verify Proper Fireplace Operation Page 40 Finishing 14 Optional Accessory see Page 68 for ordering information Install the Firebox Liners Pa...

Страница 18: ...inimum height of rear vent installations Minimum opening size additional 1 8 per side is recommended NOTE Framing specifications do NOT apply for flexible venting When using flexible venting refer to...

Страница 19: ...ly line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code NFPA 54 latest edition USA or CAN CGA B149 1 latest edition...

Страница 20: ...rlap of drywall or other material of portions of the fireplace that may be prone to the buildup of heat It is supported by a middle bracket and two side brackets Header Shield Standoffs Screw Header S...

Страница 21: ...nd identify the exterior termination location The following sections describe vertical roof and horizontal exterior wall vent applications Use only approved vent components See Pages 28 29 vertical an...

Страница 22: ...ons When horizontally terminating a vent system with a vertical vent run up to 4 ft through an exterior wall no vent restrictor is required If installing more than 6 ft of vertical venting install the...

Страница 23: ...opic vent section SV4 5LA may be used to provide the installer with an option to install in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesir...

Страница 24: ...3 465 38 75 0 0 0 0 10 10 69 5 75 0 0 0 2 0 2 475 5 39 625 0 1 0 0 10 11 73 5 6 125 1 0 0 2 0 3 480 40 1 1 0 0 10 12 79 5 6 625 0 1 0 2 0 3 492 41 1 0 1 0 10 12 81 6 75 0 0 0 1 1 2 499 5 41 625 0 0 0...

Страница 25: ...figures Secure Flex pipe may also be used A table summarizes each configuration s minimum and maximum vertical and horizontal length parameters for a variety of applications 1 Refer to Figure 23 and...

Страница 26: ...there is living space above the ceiling level the firestop spacer must be installed on the bottom side of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the t...

Страница 27: ...eal the top and both sides of the flashing with waterproof caulking The flashing must overlap the roofing material along the bottom 11 Install the storm collar Install the storm collar supplied with t...

Страница 28: ...ARNING Do NOT join separate sections of concentric flexible vent pipe Figure 23 Top Vent Straight Table 16 Rear Vent One 90 Elbow Ceiling firestop spacer SV4 5VF When using Secure Flex use ceiling fir...

Страница 29: ...1 H Ceiling firestop spacer SV4 5VF H1 H 8 ft 2 4 m maximum H H1 20 ft 6 1 m maximum V V1 H H1 60 ft 18 3 m maximum Install the U shaped vent restrictor in any vent run with more than 6 ft of vertical...

Страница 30: ...and determine the number of vent sections and elbows required See Effective Vent Length on Pages 23 24 for more information Plan the venting so that a joint does not occur in the ceiling or roof joist...

Страница 31: ...Attach the termination adaptor Attach the adaptor SV4 5RCH provided with the termination to the vent section or telescoping vent section elbow or fireplace collar Figure 25 12 Install the firestop sp...

Страница 32: ...n the exterior side of the wall The firestop may be caulked with mill base caulk such as 10K81 or high temperature silicone Figure 26 Venting Connection and Exterior Wall Recessing of the Horizontal T...

Страница 33: ...ry NOTE SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used any time vent pipe passes through a combustible floor or ceiling SV4 5HF Secure Vent SF4 5HF Secure Flex firestop spacer mu...

Страница 34: ...icular range of exterior wall thicknesses If 25 ft of H horizontal vent run is needed then 5 ft minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 ft of V vert...

Страница 35: ...wall firestop spacer SF4 5HF Wall firestop spacer SV4 5HF Ceiling firestop spacer SV4 5VF H V H1 H2 Table 27 Top Vent Three 90 Elbows H Maximum V Minimum feet meters feet meters 5 1 524 Elbow only 5...

Страница 36: ...the inner and outer adaptor collars NOTE Outer vent pipe is pulled away to show inner vent pipe details Adaptor SV4 5RF Attach adaptor to vent collar or Secure Vent sections 1 3 4 44 mm flexible vent...

Страница 37: ...ations or Secure Vent adaptor for Secure Flex components Secure Flex termination and adaptor collars are a different circumference than Secure Vent collars Secure Flex vent has an longer center tube t...

Страница 38: ...hermostat mount it in a convenient location on a wall near the fireplace 2 Wire the control switch within the millivolt control circuit using the 15 ft of 2 conductor wire supplied with the unit Figur...

Страница 39: ...B B B R B B SIT Electronic Gas Valve See the Operation section on Page 51 for more details NOTE Electronic models must be connected to the main power supply 1 Route a 3 wire 120 Vac 60 Hz 1 ph power s...

Страница 40: ...Flare shutoff valve 3 8 Flex tubing Gas stub 1 2 x 3 8 Reducer These fireplaces are equipped with a gas flex line for use where permitted in connecting the unit to the gas line A gas flex line is pro...

Страница 41: ...3 74 NOTE When lighting the fireplace for the first time it will take a few minutes for the gas line to purge itself of air When purged the pilot and burner will light and operate as indicated Subsequ...

Страница 42: ...f the air shutter opening is closed too far sooting may develop Sooting is indicated by black puffs developing at the tips of very long orange flames Sooting results in black deposits forming on the l...

Страница 43: ...on by pulling rod down especially on LP gas 1 Move the adjustment rod down to increase air flow and up to decrease it The rod is located in the lower control compartment Position the air shutter to th...

Страница 44: ...djustment It is suggested that the center screw should be installed first and the ends last 1 Attach hood using three screws as shown here WARNING Reinstall any barrier removed before operating the fi...

Страница 45: ...ats into the Barrier Support Bracket Installation see Figures 36A and 36B 1 Slide barrier into upper trim panel NOTE This panel will rotate for ease of installation BARRIER INSTALLATION 2 Lower barrie...

Страница 46: ...ch the Safety in Operation Warning Labels 1 Attach the furnished safety instruction labels at all fireplace operation and control points Page 47 NOTE The installer MUST ensure these warnings are prope...

Страница 47: ...huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl e dans la r...

Страница 48: ...4 5FB 7 12 to 12 12 Adjustable Flashing 77L81 SV4 5SC6 Storm Collar 6 pack H6183 SV4 5HF5 Firestop Spacer 5 rigid H6184 SF4 5HF5 Firestop Spacer 5 flex H2246 SV4 5HF 10 Firestop Spacer Horizontal rigi...

Страница 49: ...re Termination for flex with 24 610 mm of compressed flex vent see 750204M 94L07 SFKIT36SS Small Square Termination for flex with 36 914 mm of compressed flex vent see 750204M 94L08 SFKIT48SS SmallSqu...

Страница 50: ...selon les instructions du fabricant fournies avec la trousse Le fournisseur de service qualifi ayant r alis l installation assume les responsabilit s li es la conversion In Canada The conversion shall...

Страница 51: ...ted by carbon monoxide than others including pregnant women people with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes NOTE Do not place furniture or...

Страница 52: ...rruptor opera la chimenea encendi ndola y apag ndola Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta enlasuperficiedelaplacadelinterruptorquecontrola la ch...

Страница 53: ...front during the first few fires as part of the burn in period The glass should be kept clean during the burn in period to prevent the film from baking on making it very difficult to remove Cleaning...

Страница 54: ...you local distributor or dealer Readthisinstructionsheetinitsentiretybeforebeginningtheinstallation ALL WARNINGS AND PRECAUTIONS IN THE INSTALLATION AND OPERA TION MANUAL PROVIDED WITH THE APPLIANCE...

Страница 55: ...Direct Vent Gas Fireplaces 55 Figure 39D Figure 39C Insert Bent Bracket Bracket Insert Top Leg Of Bracket Between Lintel And Top Panel Example of Pre Bent Bracket Before Insertion Figure 39F Brackets...

Страница 56: ...in incomplete combustion sooting and poor flame quality Logs get very hot and remain hot for up to one hour after the gas supply is turned OFF Handle the logs only when cool This appliance is not desi...

Страница 57: ...Description 1 Rear Log 2 Left Twig Log 3 Right Twig Log 4 Middle Twig Log 1 If necessary remove the glass door Pages 63 64 Locate the placement tabs Figure 40 2 Bend up the two log tabs Figure 40 and...

Страница 58: ...3 Place left twig log 2 Bottom View Fits over Tab b Figure 40 Rests against Tab a Figure 40 1 Pin for Log 2 6 Right twig log 3 will straddle the second from the right grate tine and rest on Rear log 1...

Страница 59: ...f necessary remove the glass door Pages 63 64 2 Tear the glowing embers into dime size pieces Place glowing embers as shown in Figure 46 3 Locate and bend up the log placement tabs Figure 47 4 Place t...

Страница 60: ...e 47 Fits over Tab c Figure 47 Fits over Tab d Figure 47 6 Place the Y end of the Right Twig Log 4 on to the grate shown and the other end will lay on to the landing groove Figure 50 on the right side...

Страница 61: ...Pages 63 64 2 Tear the glowing embers into dime size pieces Place glowing embers as shown in Figure 54 3 Locate and bend up the log placement tabs Figure 55 4 Place the Rear Log 1 on to the back left...

Страница 62: ...on to the grate shown and the other end will lay on to the landing groove Figure 58 on the right side of the Rear Log 1 Figure 59 7 Place the Left Twig Log 5 with the pin hole on to the Bottom Left Lo...

Страница 63: ...e installed AVERTISSEMENT Une barri re con ue pour r duire le risque de br lure par le hublot chaude est fournie avec l appareil et doit tre install WARNING Do not operate appliance with the glass fro...

Страница 64: ...lace in order to close If it does remove the door and inspect the door gasket to ensure it is even and not rolled up at the top SEE WARNING IN FIGURE 62 4 Install the barrier 5 Close the control compa...

Страница 65: ...venting system components However more frequent periodic inspections and cleanings should be performed by the homeowner NOTE Prior to the first use of the fireplace and each burn season and periodica...

Страница 66: ...g paint brush Reinstalling the embers and logs Carefully follow the placement instructions Pages 56 62 All logs should fit onto the corresponding pins and or log stoppers This will ensure proper flame...

Страница 67: ...or signs of blockage or obstruction Look for any signs of dislocation of the vent components Appliance Inspection Qualified Service Technician Perform the appropriate appliance inspection procedure de...

Страница 68: ...able speed forced air circulation The FBK 250 offers variable speed control and a heat activated switch perfect for fireplaces controlled thermostatically Touch Up Paint Kits Repair minor scratches an...

Страница 69: ...y indicator Batteries included Wall Control 4 button timer with 30 60 120 OFF minutes Wall surface mounted Connects to wall switch wire Perfect for rental and resort applications Wall Switch Countdown...

Страница 70: ...__________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________...

Страница 71: ...mediately call your service technician or gas supplier LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE If the pilot will not stay lit after several tries turn the gas control knob to OFF and call y...

Страница 72: ...m diatement un technicien qualifi ou le fournisseur de gaz Si la veilleuse ne reste pas allum e apr s plusieurs tentatives r glez la manette d admission du gaz la position OFF et appelez un technicien...

Страница 73: ...y gas control which has been under water Electronic Gas Control Valve SIT Electronic Pilot Assembly 3 Turn off all electric power to the appliance if service is to be performed Note The control may ha...

Страница 74: ...ur peut avoir une batterie de secours installer les batteries au besoin 8 Placez l interrupteur du r cepteur en position REMOTE ou l interrupteur mural en position ON 9 Si applicable Appuyez sur le bo...

Страница 75: ...lighting instructions a Defective pilot generator thermocouple Check pilot flame it must impinge on thermocouple Clean and or adjust pilot for maximum flame impingement on thermocouple Ensure that th...

Страница 76: ...tion F3893 DRT3035DEN C 35 DV Elec NG F3894 DRT3035DEP C 35 DV Elec LP F3891 DRT3035DMN C 35 DV MV NG F3892 DRT3035DMP C 35 DV MV LP F3897 DRT3040DEN C 40 DV Elec NG F3898 DRT3040DEP C 40 DV Elec LP F...

Страница 77: ...nition Board J7906 1 J7906 1 J7906 1 Electronic Power Transformer H8006 1 H8006 1 H8006 1 6 Electronic Battery Holder for backup batteries H8803 1 H8803 1 H8803 1 Electronic Ground Wire H7278 1 H7278...

Страница 78: ...__________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________...

Страница 79: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard...

Страница 80: ...number Date fireplace was Installed Type of gas fireplace uses Dealer name Innovative Hearth Products IHP reserves the right to make changes at any time without notice in design materials specificati...

Отзывы: