Form #43219020 

 

June 09

 

Tighten flexible gas hose and components securely.
Improperly connected gas lines may result in fire,

explosion, poisonous fumes, toxic gases, asphyxiation

or death. Connect gas lines in accordance to national,

state, provincial and local codes.
Failure to do so may result in death, serious injury or

property damage.

FIRE AND EXPLOSION HAZARD

 

 
1.  Connect to the supply tank or manifold in accordance with the latest edition of National Fuel Gas Code (ANSI 

Z223.1), and local building codes.  Authorities having jurisdiction should be consulted before the installation 
is made. 

2.  All gas supply lines must be located in accordance with the required clearances to combustibles below the 

heater as listed on the nameplate of the heater. 

3.  Pipe joint compounds must be resistant to the action of liquefied petroleum gases. 
4.  Where local codes do not prohibit, a CSA or U.L. approved flexible connector (minimum 5/8” I.D.) is 

recommended between the rigid piping and the heater.  A union and an approved shut-off valve should be 
installed before the control valve inlet.  The shut-off valve should be installed within 6 feet of the union. 

 

TYPICAL GAS CONNECTIONS

* Approved

Flexible Connector

*Second Stage Regulator with

Vent Leak Limiter to reduce the

Supply Pressure below 14” W.C.

Gas Pressure

= 2 PSIG

Gas Supply

Piping

Sediment Trap

(Drip Leg)

*Manual Gas

Shut Off Valve

* Available as Accessories

Alternate Supply

Location

SIDE VIEW

12” (30cm)

END VIEW

Hot Gases!!

Do NOT locate gas line above

flue discharge area.

Hot Gases!!

Do NOT locate gas line above

flue discharge area.

 

5.  This appliance is equipped with a snap-opening, combination 

gas valve.  The maximum supply pressure to the appliance is 
14” W.C. or 1/2 P.S.I.  If the line pressure is more than the 
maximum supply pressure, then use a line regulator as 
indicated in the following illustration, or a line regulator 
which corresponds to the supply pressure. 

6.  If a second stage regulator is used and gas seeps through it, 

the redundant combination gas valve is designed to lock out. 
 Pressure build-up in the supply lines prior to the heater must 
be released before proper heater operation. 

7.  After all gas connections have been made, make sure the heater and all gas outlets are turned off before the 

main gas supply is turned on.  Turn the gas pressure on and check for leaks.  To check for leaks, apply a 
soapsuds solution to all connections and joints or check by one of the methods listed in Appendix D of the 
National Fuel Gas Code, ANSI Z223.1-(latest edition). 

 

 

Do not use an open flame of any kind to test for leaks. 

Certified connections are recommended to 
be installed as shown, in one plane, and 
without sharp bends, kinks or twists.  The 
gas take off from the drop line must be 
parallel to the burner gas inlet connection. 
 
If the maximum supply pressure is less 
than ½ psig, a second stage regulator is 
not required. 

Содержание STARGLO Series

Страница 1: ...or death Read the installation operation and maintenance instructions thoroughly before installing or servicing this equipment In locations used for the storage of combustible materials signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles Signs must either be posted adjacent to the heater thermostats or in t...

Страница 2: ...ls Ontario M3B 2R3 All NFPA codes are available from the National Fire Protection Association Batterymarch Park Quincy Massachusetts 02269 WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance Extinguish any open flame Open windows DO NOT touch any electrical switch DO NOT use any telephone in your building Immediately call your gas supplier from a neighbor s telephone Follow the gas suppl...

Страница 3: ...als having a working load limit of at least 87lbs Supply the owner with a copy of these Installation and Operation Instructions Gravity or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1 000 Btu hr input of installed heaters Never use the heater as a support for a ladder or other access equipment Do not hang anything from the heater Supply all installation materials n...

Страница 4: ...t Hangars ANSI NFPA 88a latest edition Standard for Parking Structures and ANSI NFPA 88b latest edition Standard for Repair Garages with the following clearances a At least 10 feet above the upper surfaces of wings or engine enclosures of the highest aircraft that may be housed in the hangar and at least 8 feet above the floor in shops offices and other sections of hangars communicating with aircr...

Страница 5: ...o do so may result in fire and or explosion property damage serious injury or death When installing the infra red heater system the minimum clearances to combustibles must be maintained These distances are shown in Chart below and on the heater If you are unsure of the potential hazards consult your local fire marshal fire insurance carrier or other qualified authorities on the installation of gas...

Страница 6: ...the installer must post signs that will specify the maximum permissible stacking height to maintain the required clearances from the heater to combustibles SunStar recommends posting these signs adjacent to the heater thermostat or other suitable location that will provide enhanced visibility 5 SG SERIES SPECIFICATIONS ORIFICE SIZE7 MODEL NO BTU HR INPUT NUMBER OF BURNERS Natural Gas Propane Gas S...

Страница 7: ...ry or property damage SUSPENSION HAZARD The heater can be mounted with the reflector horizontal or angled up to 35º from horizontal When the heater is to be angle mounted make sure the gas manifold assembly is on the lower side of the heater Coil chains No 2 or larger or rigid supports may be used to mount the heater which must be suspended from a permanent structure with adequate load capacity Th...

Страница 8: ...nt Trap Drip Leg Manual Gas Shut Off Valve Available as Accessories Alternate Supply Location SIDE VIEW 12 30cm END VIEW Hot Gases Do NOT locate gas line above flue discharge area Hot Gases Do NOT locate gas line above flue discharge area 5 This appliance is equipped with a snap opening combination gas valve The maximum supply pressure to the appliance is 14 W C or 1 2 P S I If the line pressure i...

Страница 9: ...the gas pressure to burner Replace the cover screw 3 Gauges that measure in pounds per square inch are not accurate enough to measure or set the manifold pressure Use a water manometer or a gauge calibrated in inches of water column All measurements MUST BE made when this heater and all other gas burning equipment that is connected to the gas supply system are operating at maximum capacity GAS PRE...

Страница 10: ...Switch All electrical wiring must be located in accordance with the required Clearances to Combustibles below the heater as listed on the nameplate on the heater 5 When connecting the supply circuit to the heater wiring material having a minimum size of 14 AWG and a temperature rating of at least 90 C shall be used TH V1 GND V2 FC FC Line Voltage Thermostat Transformer Red White 24VAC 120 VAC Igni...

Страница 11: ... SG6 0 98 s f SG13 SG14 1 97 s f SG8 0 98 s f SG15 2 30 s f The General Ventilation Rules outlined in ASHRAE GUIDE AND DATA BOOK should be observed when locating vents Exhaust vents must be located at the highest point above and in the vicinity of the heaters and the inlet vents must be located below the level of the heaters Local codes may require that mechanical exhaust systems be interlocked wi...

Страница 12: ...Ignition Gas valve Flame sensing Function ON Function OFF T1 If the flame is not sensed during sequence T2 then the burner will automatically begin re ignition sequence T1 The ignition sequence will be repeated three times with a 15 second inter purge If the flame is not reestablished the heater will go to lockout 14 CLEANING AND ANNUAL MAINTENANCE ELECTRIC SHOCK EXPLOSION HAZARD Disconnect electr...

Страница 13: ...ds below zero the meter leads are reversed Disconnect power and reconnect the meter leads for proper polarity C TROUBLESHOOTING CHART TROUBLE POSSIBLE CAUSE SOLUTIONS Heater is not glowing red The supply gas pressure is too low Improper size of gas piping The orifice is clogged Incorrect orifice size Check the manifold gas pressure and adjust if necessary If you are not sure of the performance use...

Страница 14: ...s the module have a steady red LED Replace ignition module PN 30632030 Check the gas lines are all the shut off s in the on position and have the lines been purged of air Turn on the shut off s and purge the pipework of air Is there 24V at the gas valve Replace gas valve PN s 30333050 NG 30333040 LP Check control wiring and reconnect terminals Does the burner stay lit Check the orifice is it block...

Страница 15: ...G6 SG8 43822020 SG10 SG12 43822030 SG13 SG14 SG15 43822040 17 OPTIONAL PROTECTIVE REVERB SCREEN The optional protective Reverb Screen acts as a safety net in the unlikely event that the ceramic tile assembly is broken by an outside force In addition it increases the overall emissivity of the radiating surface with a blackbody radiation effect It is recommended in high traffic areas as well as wher...

Страница 16: ...o call for heat 3 If ignition fails the unit will spark for approximately 21 seconds go into safety lockout Turn thermostat or power off for 60 seconds to take out of lockout 4 If heater does not light shut off gas completely for 5 minutes before attempting to relight 5 To shut down the heater turn off the gas electrical supply INSTRUCTIONS D ALLUMAGE ET DE FERMETURE 1 mettre la valve a gaz et l i...

Страница 17: ...ED TOANYIMPLIEDWARRANTYOFFITNESSFORAPARTICULARPURPOSEAND ANY IMPLIED WARRANTY OF MERCHANTABILITY FOR ITS PRODUCTS If any provision of this warranty is found to be void unenforceable or unconscionable then the same is hereby severed and the remainder of this warranty is hereby saved and shall remain in force EXCLUSIVE REMEDY The sole and exclusive remedy under this warranty is the replacement of th...