Form #43219020 

 

June 09

 

MINIMUM CLEARANCES TO COMBUSTIBLES

 

Mounted Horizontally 

Mounted at 35º Angle 

BELOW BELOW FRONT 

MODEL SIDES 

CEILING 

w/Standard 

Reflector 

w/Reflector 

Extension 

w/Standard 

Reflector 

w/Reflector 

Extension 

w/Standard 

Reflector 

w/Reflector 

Extension 

REAR 

Angle 

Mounting

 

SG3 and SG4 

31”  37”  73” 101” 73” 101” 37”  51”  31” 

(degree)

   

0º min 

35º max 

SG6 and SG8 

49”  49”  99” 138” 99” 138” 49”  69”  37” 

  0º min 

35º max 

SG10 and SG12 

49”  65”  129” 181” 129” 181”  61”  85”  49” 

  0º min 

35º max 

SG13,SG14 and 
SG15 

61”  65”  137” 191” 137” 191”  65”  91”  49” 

10º min 

35º max 

 

NOTE: 

The clearances specified above must be maintained to combustibles and other materials that may be 

damaged by temperatures 90ºF above ambient temperature.  It is the installer’s responsibility to ensure that 
building materials with a low heat tolerance which may degrade at lower temperatures are protected to 
prevent degradation. Clearances to combustibles are posted on the reflector near the control end of the heater. 
 In locations used for storage of combustible materials where they may be stacked below the heater, NFPA 54 
requires that the installer must post signs that will “specify the maximum permissible stacking height to 
maintain the required clearances from the heater to combustibles.”  SunStar recommends posting these signs 
adjacent to the heater thermostat or other suitable location that will provide enhanced visibility. 

 
 

5) 

SG SERIES SPECIFICATIONS 

 

ORIFICE SIZE

7

 

MODEL NO. 

BTU/HR INPUT 

NUMBER 

OF BURNERS 

Natural Gas 

Propane Gas 

SHIPPING WEIGHT 

MINIMUM 

MOUNTING 

HEIGHTS (FEET) 

SG3-N5B   33,000 

3/32” 

n/a 

30 

lbs. 

12 

SG4-N5B   40,000 

#38 

n/a 

30 

lbs. 

12 

SG6-N5B   65,000 

3/32” 

n/a 

35 

lbs. 

13 

SG8-N5B   80,000 

#38 

n/a 

35 

lbs. 

14 

SG10-N5B   100,000 

#41 

n/a 

48 lbs. 

15 

SG12-N5B   120,000 

#38 

n/a 

48 lbs. 

16 

SG14-N5B   140,000 

#41 

n/a 

58 lbs. 

17 

SG15-N5B   155,000 

#38 

n/a 

58 lbs. 

18 

SG3-L5B   32,000 

n/a 

#52 

30 

lbs. 

12 

SG6-L5B   65,000 

n/a 

#52 

35 

lbs. 

13 

SG10-L5B   100,000 

n/a 

#52 

48 

lbs. 

15 

SG13-L5B   140,000 

n/a 

#52 

58 

lbs. 

17 

 
 
 

MODEL SUFFIX 

Gas Type: 

Ignition System: 

GAS-PIPE 

CONNECTION: 

= Natural 

L

 = Propane

 

5

 = Direct Spark  (115 Volt / 0.40 Amp / 60 Hz)

 

 

1/2” NPT (Female)

 

 

7

 One Orifice Per Burner 

 
 
 
 

*MOUNT HEATERS AS HIGH AS POSSIBLE. Minimums are shown as a guideline for human comfort and 
uniform energy distribution for complete building heating applications. Consult your SunStar representative 
for the particulars of your installation requirements. 

 
 

Содержание STARGLO Series

Страница 1: ...or death Read the installation operation and maintenance instructions thoroughly before installing or servicing this equipment In locations used for the storage of combustible materials signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles Signs must either be posted adjacent to the heater thermostats or in t...

Страница 2: ...ls Ontario M3B 2R3 All NFPA codes are available from the National Fire Protection Association Batterymarch Park Quincy Massachusetts 02269 WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance Extinguish any open flame Open windows DO NOT touch any electrical switch DO NOT use any telephone in your building Immediately call your gas supplier from a neighbor s telephone Follow the gas suppl...

Страница 3: ...als having a working load limit of at least 87lbs Supply the owner with a copy of these Installation and Operation Instructions Gravity or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1 000 Btu hr input of installed heaters Never use the heater as a support for a ladder or other access equipment Do not hang anything from the heater Supply all installation materials n...

Страница 4: ...t Hangars ANSI NFPA 88a latest edition Standard for Parking Structures and ANSI NFPA 88b latest edition Standard for Repair Garages with the following clearances a At least 10 feet above the upper surfaces of wings or engine enclosures of the highest aircraft that may be housed in the hangar and at least 8 feet above the floor in shops offices and other sections of hangars communicating with aircr...

Страница 5: ...o do so may result in fire and or explosion property damage serious injury or death When installing the infra red heater system the minimum clearances to combustibles must be maintained These distances are shown in Chart below and on the heater If you are unsure of the potential hazards consult your local fire marshal fire insurance carrier or other qualified authorities on the installation of gas...

Страница 6: ...the installer must post signs that will specify the maximum permissible stacking height to maintain the required clearances from the heater to combustibles SunStar recommends posting these signs adjacent to the heater thermostat or other suitable location that will provide enhanced visibility 5 SG SERIES SPECIFICATIONS ORIFICE SIZE7 MODEL NO BTU HR INPUT NUMBER OF BURNERS Natural Gas Propane Gas S...

Страница 7: ...ry or property damage SUSPENSION HAZARD The heater can be mounted with the reflector horizontal or angled up to 35º from horizontal When the heater is to be angle mounted make sure the gas manifold assembly is on the lower side of the heater Coil chains No 2 or larger or rigid supports may be used to mount the heater which must be suspended from a permanent structure with adequate load capacity Th...

Страница 8: ...nt Trap Drip Leg Manual Gas Shut Off Valve Available as Accessories Alternate Supply Location SIDE VIEW 12 30cm END VIEW Hot Gases Do NOT locate gas line above flue discharge area Hot Gases Do NOT locate gas line above flue discharge area 5 This appliance is equipped with a snap opening combination gas valve The maximum supply pressure to the appliance is 14 W C or 1 2 P S I If the line pressure i...

Страница 9: ...the gas pressure to burner Replace the cover screw 3 Gauges that measure in pounds per square inch are not accurate enough to measure or set the manifold pressure Use a water manometer or a gauge calibrated in inches of water column All measurements MUST BE made when this heater and all other gas burning equipment that is connected to the gas supply system are operating at maximum capacity GAS PRE...

Страница 10: ...Switch All electrical wiring must be located in accordance with the required Clearances to Combustibles below the heater as listed on the nameplate on the heater 5 When connecting the supply circuit to the heater wiring material having a minimum size of 14 AWG and a temperature rating of at least 90 C shall be used TH V1 GND V2 FC FC Line Voltage Thermostat Transformer Red White 24VAC 120 VAC Igni...

Страница 11: ... SG6 0 98 s f SG13 SG14 1 97 s f SG8 0 98 s f SG15 2 30 s f The General Ventilation Rules outlined in ASHRAE GUIDE AND DATA BOOK should be observed when locating vents Exhaust vents must be located at the highest point above and in the vicinity of the heaters and the inlet vents must be located below the level of the heaters Local codes may require that mechanical exhaust systems be interlocked wi...

Страница 12: ...Ignition Gas valve Flame sensing Function ON Function OFF T1 If the flame is not sensed during sequence T2 then the burner will automatically begin re ignition sequence T1 The ignition sequence will be repeated three times with a 15 second inter purge If the flame is not reestablished the heater will go to lockout 14 CLEANING AND ANNUAL MAINTENANCE ELECTRIC SHOCK EXPLOSION HAZARD Disconnect electr...

Страница 13: ...ds below zero the meter leads are reversed Disconnect power and reconnect the meter leads for proper polarity C TROUBLESHOOTING CHART TROUBLE POSSIBLE CAUSE SOLUTIONS Heater is not glowing red The supply gas pressure is too low Improper size of gas piping The orifice is clogged Incorrect orifice size Check the manifold gas pressure and adjust if necessary If you are not sure of the performance use...

Страница 14: ...s the module have a steady red LED Replace ignition module PN 30632030 Check the gas lines are all the shut off s in the on position and have the lines been purged of air Turn on the shut off s and purge the pipework of air Is there 24V at the gas valve Replace gas valve PN s 30333050 NG 30333040 LP Check control wiring and reconnect terminals Does the burner stay lit Check the orifice is it block...

Страница 15: ...G6 SG8 43822020 SG10 SG12 43822030 SG13 SG14 SG15 43822040 17 OPTIONAL PROTECTIVE REVERB SCREEN The optional protective Reverb Screen acts as a safety net in the unlikely event that the ceramic tile assembly is broken by an outside force In addition it increases the overall emissivity of the radiating surface with a blackbody radiation effect It is recommended in high traffic areas as well as wher...

Страница 16: ...o call for heat 3 If ignition fails the unit will spark for approximately 21 seconds go into safety lockout Turn thermostat or power off for 60 seconds to take out of lockout 4 If heater does not light shut off gas completely for 5 minutes before attempting to relight 5 To shut down the heater turn off the gas electrical supply INSTRUCTIONS D ALLUMAGE ET DE FERMETURE 1 mettre la valve a gaz et l i...

Страница 17: ...ED TOANYIMPLIEDWARRANTYOFFITNESSFORAPARTICULARPURPOSEAND ANY IMPLIED WARRANTY OF MERCHANTABILITY FOR ITS PRODUCTS If any provision of this warranty is found to be void unenforceable or unconscionable then the same is hereby severed and the remainder of this warranty is hereby saved and shall remain in force EXCLUSIVE REMEDY The sole and exclusive remedy under this warranty is the replacement of th...

Отзывы: