20)  REPLACEMENT PARTS GUIDE 

 
 

ITEM# 

PART # 

DESCRIPTION 

 

ITEM# 

PART # 

DESCRIPTION 

30333040  Valve VR8205A-2081 @ 10” W.C. – Propane Gas 

 

17 

43908010  Frame Assembly 

(1 Burner Unit) 

30333050  Valve VR8205A-2123 @ 6” W.C. – Natural Gas 

 

18 

43908020  Frame Assembly 

(2 Burner Unit) 

30279000 Transformer 

AT120B1051 

 

19 

43908030  Frame Assembly 

(3 Burner Unit) 

30632030  Spark Module, Fenwal #35-605950-015 

 

20 

43908040  Frame Assembly 

(4 Burner Unit) 

30295020 Electrode 

PSE-GF9 

 

21 

03548000  Junction Box, 2 

x

 4 

x

 1½  

30314100  Ignition Cable 10” 

 

22 

03606000 Cover 

Plate 

43856029  Burner Assembly Kit (Ignition Unit) 

 

23 

43849000  Ignition Control Bracket 

43856039  Burner Assembly Kit (2

nd

, 3

rd

, and 4

th

 Unit) 

 

24 

43872380  Orifice #38 for SG4, SG8, SG12, SG15 – Natural Gas 

43862010  Manifold for SG3, SG4 

 

25 

43872410  Orifice #41 for SG10, SG14 – Natural Gas 

10 

43862020  Manifold for SG6, SG8 

 

26 

43872980  Orifice 3/32” for SG3, SG6 – Natural Gas 

11 

43862030  Manifold for SG10, SG12 

 

27 

43872520  Orifice #52 for SG3, SG6, SG10, SG13– Propane Gas 

12 

43862040  Manifold for SG13, SG14, SG15 

 

28 

43219020

 

Installation and Operation Manual  

(Not Shown)

 

13 

43847010  Reflector for SG3, SG4 

29 

42052030  Label - Connection Wire Diagram   

14 

43847020  Reflector for SG6, SG8 

30 

42849020  Label – Nameplate 

15 

43847030  Reflector for SG10, SG12 

31 

43247030  Label – Clearances to Combustibles 

16 

43847040  Reflector for SG13, SG14, SG15 

 

32 

42875000  Label – General Warnings 

 

 

 

 
 
 
 
 

 

IMPORTANT: 

 Please order by Part Number, not by Item Number. 
 Refer to complete Model Number when ordering. 
 All replacement parts available when ordering. 

 
 
Screws, nuts and washers are standard hardware 
items and can be purchased at any local hardware 
store. 
 
 
ALL ILLUSTRATIONS ARE INTENDED TO GIVE THE 
GENERAL IMPRESSION OF UNITS ONLY.  WE 
RESERVE THE RIGHT TO ALTER ANY SPECIFICATION 
WITHOUT NOTICE 
 

 

7

8

17, 18, 19, 20

5

6

4

3

21, 22

23

1, 2

13, 14, 15, 16

9, 10, 11, 12

24, 25, 26, 27

TH

V1

GND

V2

FC+

FC-

Thermostat

R

W

24VAC

120
VAC

MV

MV

BL

W

Ignition Module

Fenwal No.

2460D

Chaud

Neutral

Ground

CONNECTION WIRING DIAGRAM

S

chéma de circuit de connexion

TRANSFORMER

120V PRIMARY

24V SECONDARY

If any of the original wire as supplied with the

appliance must be replaced. It must be

replaced with wiring material having a

temperature rating of at least 105oC. (18

AWG. - UL / CSA 600V Type TEW)

When connecting the supply circuit to the

heater, wiring material having a minimum size

of 14 AWG and a temperature rating of at

least 90oC shall be used.

Transformateur

bobine primaire 120ÊV

bobine secondaire 24ÊV

S'il faut remplacer un fil de l'appareil d'origine,

utiliser exclusivement des fils  à température

de service nominale d'au moins 105C (18

AWG. - UL / CSA 600ÊV

Type TEW).

Pour raccorder le circuit d'alimentation au

radiateur, utiliser des fils de calibre 14 AWG

ou plus à température de service nominale

d'au moins 90C.

Neutre

HIGH VOLTAGE CABLE

Haute tension

Terre

GAS VALVE

Robinet à gaz

WIRE LEGEND

ENGLISH

FRANCAIS

W

WHITE

BLANC

R

RED

ROUGE

BL

BLUE

BLEU

G

GREEN

VERT

Bloc d'allumage

FACTORY WIRING

FIELD WIRING

Circuit d'origine

Connexions client

Hot

42052030

Rev. A  3/05

ELECTRODE

GAP 3/16”

Écartement

d'électrode

4,7Êmm

BL

42849000 Rev. H  2/08

LIGHTING & SHUTDOWN INSTRUCTIONS

1. Turn on gas & electrical supply.

2. Set thermostat to call for heat.

3. If ignition fails, the unit will spark for approximately 21 seconds

& go into safety lockout. Turn thermostat (or power) off for 60

seconds to take out of lockout.

4. If heater does not light, shut off gas completely for 5 minutes

before attempting to relight.

5. To shut down the heater, turn off the gas & electrical supply.
INSTRUCTIONS D’ALLUMAGE ET DE FERMETURE
1. mettre la valve a gaz et l’interrupteur a “ON”.

2. Creer une demande de chauffage au thermostat.

3. Si l’allumage ne se fait pas, le controle d’allumage continu de

produire des etincelles sur une periode de 21 sec. et ensuite

tomber en securite. Mettre le thermostat (ou le courant) en

position d’arret (OFF) pour une periode de 60 sec. a fin

d’interrompre le processus de securite.

4. Si l’appareil ne s’allume pas, fermez le gaz completement pour

une period de 5 min. avant d’effectuer une nouvelle tentative

d’allumage.

5. Pour fermer l’appareil, fermez le gaz et le courant electrique.

UNVENTED

RADIATEUR CÉRAMIQUE À INFRAROUGES

HIGH INTENSITY INFRARED RADIANT

CERAMIC HEATER

SANS AÉRATION

ANSI Z83.19b / CSA 2.35b-2007

Gas Fired products Inc. Charlotte, NC

Tel: 1800 438 4936 e-mail [email protected]

Installation in:

1. Aircraft hangers must be in accordance with the

   standard for Aircraft Hangers. ANSI/NFPA 409 (latest edition).

2. Public garages must be in accordance with the standard for

    parking structures, ANSI/NFPA 88a (latest edition), or with the

   standard for repair garages, ANSI/NFPA 88b (latest edition)

Combustible material must be located outside the clearance dimensions listed.

Failure to do so may result in death, serious injury or property damage

43247020 Rev. C  8/05

IMPORTANT!

When angle

mounting,

the control side

must be down.

Gas Valve

CEILING

FRONT

REAR

ANGLE

BELOW

SIDE

Gas Manifold

Assembly

SIDE

CEILING

BELOW

   36” 

50”

30”

(91cm)

(127cm)

(76cm)

   48”

68”

36”

(122cm)

(173cm)

(91cm)

   60”

84”

48”

(145cm)

(213cm) (122cm)

   64”                  90”            48” 

(163cm)

(229cm) (122cm)

             

DK30, DK35,

30”

36” 

72” 

100”

             

DK33, DK40

 

(76cm)

(91cm)

(183cm)

(254cm)

             

DK60, DK70,

48”

48” 

98”

137”

             

DK66, DK80

(122cm) (122cm) (249cm)

(348cm)

             

DK100, DK120

48”

64” 

128”

180”

122cm)

(163cm) (325cm)

(457cm)

             

DK132, DK160,

60”

64”

136”

190”

             

DK140

(145cm) (163cm) (345cm)

(483cm)

SIDES CEILING

w/Standard

Reflector

w/Reflector

Extension

BELOW

MODEL NO.

FRONT

REAR

w/Standard

Reflector

w/Reflector

Extension

ANGLE

MTG.

(degree)

0 min.

35 max.

0 min.

35 max.

0 min.

35 max.

10 min.

35 max.

 WARNING:

 Improper

installation, adjustment,

alteration, service or

maintenance can cause

property damage, injury

or death. Read the

Installation, Operating

and Maintenance

Instruction thoroughly

before servicing this

equipment.

 AVERTISSEMENT:

 Une

installation, un réglage, une

modification, une réparation

ou un entretien incorrect peut

entraîner des dommages

matérials, des blessures ou

la mort. Lisez attentivement

les instructions d’installation,

de fonctionnement et

d’entretien avant de procéder

à l’installation ou à l’entretien

de cet équipment.

 WARNING:

 If not

installed, operated and

maintained in accordance

with the manufacturer’s

instructions, this product

could expose you to

substances in fuel or from

fuel combustion which can

cause death or serious

illness and which are

known to the State of

California to cause cancer,

birth defects or other

reproductive harm.

 WARNING:

 This product

contains a chemical known

to the state of California to

cause cancer.

This heater can be

installed in various

configurations as shown

in the heater layout

section of the instructions

42875000 Rev. E  10/04

29

30

31

32

Содержание STARGLO Series

Страница 1: ...or death Read the installation operation and maintenance instructions thoroughly before installing or servicing this equipment In locations used for the storage of combustible materials signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles Signs must either be posted adjacent to the heater thermostats or in t...

Страница 2: ...ls Ontario M3B 2R3 All NFPA codes are available from the National Fire Protection Association Batterymarch Park Quincy Massachusetts 02269 WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance Extinguish any open flame Open windows DO NOT touch any electrical switch DO NOT use any telephone in your building Immediately call your gas supplier from a neighbor s telephone Follow the gas suppl...

Страница 3: ...als having a working load limit of at least 87lbs Supply the owner with a copy of these Installation and Operation Instructions Gravity or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1 000 Btu hr input of installed heaters Never use the heater as a support for a ladder or other access equipment Do not hang anything from the heater Supply all installation materials n...

Страница 4: ...t Hangars ANSI NFPA 88a latest edition Standard for Parking Structures and ANSI NFPA 88b latest edition Standard for Repair Garages with the following clearances a At least 10 feet above the upper surfaces of wings or engine enclosures of the highest aircraft that may be housed in the hangar and at least 8 feet above the floor in shops offices and other sections of hangars communicating with aircr...

Страница 5: ...o do so may result in fire and or explosion property damage serious injury or death When installing the infra red heater system the minimum clearances to combustibles must be maintained These distances are shown in Chart below and on the heater If you are unsure of the potential hazards consult your local fire marshal fire insurance carrier or other qualified authorities on the installation of gas...

Страница 6: ...the installer must post signs that will specify the maximum permissible stacking height to maintain the required clearances from the heater to combustibles SunStar recommends posting these signs adjacent to the heater thermostat or other suitable location that will provide enhanced visibility 5 SG SERIES SPECIFICATIONS ORIFICE SIZE7 MODEL NO BTU HR INPUT NUMBER OF BURNERS Natural Gas Propane Gas S...

Страница 7: ...ry or property damage SUSPENSION HAZARD The heater can be mounted with the reflector horizontal or angled up to 35º from horizontal When the heater is to be angle mounted make sure the gas manifold assembly is on the lower side of the heater Coil chains No 2 or larger or rigid supports may be used to mount the heater which must be suspended from a permanent structure with adequate load capacity Th...

Страница 8: ...nt Trap Drip Leg Manual Gas Shut Off Valve Available as Accessories Alternate Supply Location SIDE VIEW 12 30cm END VIEW Hot Gases Do NOT locate gas line above flue discharge area Hot Gases Do NOT locate gas line above flue discharge area 5 This appliance is equipped with a snap opening combination gas valve The maximum supply pressure to the appliance is 14 W C or 1 2 P S I If the line pressure i...

Страница 9: ...the gas pressure to burner Replace the cover screw 3 Gauges that measure in pounds per square inch are not accurate enough to measure or set the manifold pressure Use a water manometer or a gauge calibrated in inches of water column All measurements MUST BE made when this heater and all other gas burning equipment that is connected to the gas supply system are operating at maximum capacity GAS PRE...

Страница 10: ...Switch All electrical wiring must be located in accordance with the required Clearances to Combustibles below the heater as listed on the nameplate on the heater 5 When connecting the supply circuit to the heater wiring material having a minimum size of 14 AWG and a temperature rating of at least 90 C shall be used TH V1 GND V2 FC FC Line Voltage Thermostat Transformer Red White 24VAC 120 VAC Igni...

Страница 11: ... SG6 0 98 s f SG13 SG14 1 97 s f SG8 0 98 s f SG15 2 30 s f The General Ventilation Rules outlined in ASHRAE GUIDE AND DATA BOOK should be observed when locating vents Exhaust vents must be located at the highest point above and in the vicinity of the heaters and the inlet vents must be located below the level of the heaters Local codes may require that mechanical exhaust systems be interlocked wi...

Страница 12: ...Ignition Gas valve Flame sensing Function ON Function OFF T1 If the flame is not sensed during sequence T2 then the burner will automatically begin re ignition sequence T1 The ignition sequence will be repeated three times with a 15 second inter purge If the flame is not reestablished the heater will go to lockout 14 CLEANING AND ANNUAL MAINTENANCE ELECTRIC SHOCK EXPLOSION HAZARD Disconnect electr...

Страница 13: ...ds below zero the meter leads are reversed Disconnect power and reconnect the meter leads for proper polarity C TROUBLESHOOTING CHART TROUBLE POSSIBLE CAUSE SOLUTIONS Heater is not glowing red The supply gas pressure is too low Improper size of gas piping The orifice is clogged Incorrect orifice size Check the manifold gas pressure and adjust if necessary If you are not sure of the performance use...

Страница 14: ...s the module have a steady red LED Replace ignition module PN 30632030 Check the gas lines are all the shut off s in the on position and have the lines been purged of air Turn on the shut off s and purge the pipework of air Is there 24V at the gas valve Replace gas valve PN s 30333050 NG 30333040 LP Check control wiring and reconnect terminals Does the burner stay lit Check the orifice is it block...

Страница 15: ...G6 SG8 43822020 SG10 SG12 43822030 SG13 SG14 SG15 43822040 17 OPTIONAL PROTECTIVE REVERB SCREEN The optional protective Reverb Screen acts as a safety net in the unlikely event that the ceramic tile assembly is broken by an outside force In addition it increases the overall emissivity of the radiating surface with a blackbody radiation effect It is recommended in high traffic areas as well as wher...

Страница 16: ...o call for heat 3 If ignition fails the unit will spark for approximately 21 seconds go into safety lockout Turn thermostat or power off for 60 seconds to take out of lockout 4 If heater does not light shut off gas completely for 5 minutes before attempting to relight 5 To shut down the heater turn off the gas electrical supply INSTRUCTIONS D ALLUMAGE ET DE FERMETURE 1 mettre la valve a gaz et l i...

Страница 17: ...ED TOANYIMPLIEDWARRANTYOFFITNESSFORAPARTICULARPURPOSEAND ANY IMPLIED WARRANTY OF MERCHANTABILITY FOR ITS PRODUCTS If any provision of this warranty is found to be void unenforceable or unconscionable then the same is hereby severed and the remainder of this warranty is hereby saved and shall remain in force EXCLUSIVE REMEDY The sole and exclusive remedy under this warranty is the replacement of th...

Отзывы: