SunStar CK18M-4-LP Скачать руководство пользователя страница 3

sunstar corcho T (Convertido)-1 13/3/08 10:27 P gina 3 

Composici n

C

M

Y

CM

MY

CY CMY

K

3

20. The National Fuel Gas Code defines a confined

space as a space whose volume is less than 50
ft

3

 per 1,000 Btu/hr (4.8 m

3

/kw) of the aggregate

input rating of all appliances installed in that
space and an unconfined space as a space
whose volume is not less than 50 ft

3

 per 1,000

Btu/hr (4.8 m

3

/kw) of the aggregate input rating

of all appliances installed in that space.  Rooms
communicating directly with the space in which
the appliances are installed, through openings
not furnished with doors, are considered a part
of the space.

21.

 

WARNING:

  If the area in which the

heater may be operated is smaller than that
defined as an unconfined space,or if the building
is of unusually tight construction, provide
adequate combustion and ventilation air by one
of the methods described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section
5.3 or applicable local codes.

The purpose of this worksheet is to help you determine if you are planning to install this heater in an “unconfined”
or a “confined” space.  An “unconfined” space is one that is large enough to meet all the combustion and
ventilation air requirements of all the fuel burning appliances to be in operation in this space.  No additional
air requirements are needed.  A “confined” space is one that 

is not

 large enough to meet the combustion

and ventilation air requirements for all the fuel burning appliances in that space.  As a result, additional air
is required in this space to meet the appliance needs.  Check with your installer on ways to accomplish this,
or use a smaller Btu/hr input heater.

STEP 1:

Determine the volume of the space in which the heater is to be installed.  Include adjoining
rooms with doorless passageways.  Example: 24' (long) x 16' (wide) x 8' (high) = 3072 ft

3

.

L E N GT H   x   W I DT H   x   H E I G H T   =   _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _   F t

3

STEP 2:

Multiply the volume of the space (calculated in Step 1) by 20 BTU/hr to determine the
maximum BTU/hr that the space can support without additional combustion and ventilation
air provided.

Result from Step 1 ____________________ x 20 BTU/hr = ____________________ BTU/hr

STEP 3:

Add the BTU/hr inputs of all 

fuel burning

 appliances in this space. 

 NOTE:  DO NOT include

Direct-Vent gas appliances because these have sealed combustion systems that draw
combustion air from outdoors.

  Examples of appliances to consider include:  gas ranges,

gas water heaters, gas logs, kerosene heaters, etc.

Proposed Vent-Free Heater

______________________________ BTU/hr

Fuel Burning Appliance #1

______________________________ BTU/hr

Fuel Burning Appliance #2

______________________________ BTU/hr

TOTAL

______________________________ BTU/hr

STEP 4:

Compare the results from Step 2 and Step 3.

If the result from Step 2 is 

greater

 than the result from Step 3, the area where the heater is to be installed

can be classified as an “unconfined space.”  This means that the space is capable of handling the combustion
and ventilation air requirements of the existing fuel burning appliance(s) and the proposed heater.

If the result from Step 2 is 

less

 than the result from Step 3, the area where the heater is to be installed is

classified as a “confined space.”  

This means that either additional combustion and ventilation air must

be provided into this space (use the methods described in the National Fuel Gas Code, ANSI Z223.1-

latest edition) or the size of the proposed heater must be reduced so that the above calculations show

the space to be an  unconfined space.

Содержание CK18M-4-LP

Страница 1: ...alified service person The appliance should be inspected before use and at least annually by a qualified service person More frequent cleaning may be required due to excessive lint from carpeting bedding material etc It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean PN 43126170 INSTALLATION AND OWNER S GUIDE Effective Date June 2006 V...

Страница 2: ...e and other flammable vapors and liquids 11 This appliance may be installed in an aftermarket manufactured mobile home where not prohibited by state or local codes Aftermarket Completion of sale not for purpose of resale from the manufacturer 12 DO NOT use this heater if any part has been under water Immediately call a qualified service person to inspect the room heater and to replace any part of ...

Страница 3: ...ine the volume of the space in which the heater is to be installed Include adjoining rooms with doorless passageways Example 24 long x 16 wide x 8 high 3072 ft3 LE NGTH x WI DTH x H E IG HT ___________________________ Ft3 STEP 2 Multiply the volume of the space calculated in Step 1 by 20 BTU hr to determine the maximum BTU hr that the space can support without additional combustion and ventilation...

Страница 4: ...nside the storage tank or in iron gas pipes The odorant in escaped gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a closed area and the odor intensity could vary at different levels Since it is heavier than air there may be more odor at lower levels Al...

Страница 5: ...eater The heater must be installed no less than 2 above the top surface of carpeting tile or other floor covering When facing the front of the heater the clearance from any combustible materials must be a minimum of 13 from the left 13 from the right 36 from the top and 2 from the bottom and 36 from the front The opening for combustion air located at the bottom of the heater must not be obstructed...

Страница 6: ...the unit See the following instructions in figure 2 2 to place the C angle to the wall stud 1 Select the elbow position as indicated in Figure 2 1 2 Use the template provided to mark out the hole locations 3 Drive two 2 5 16 holes according to the dimensions shown on the upper corner of Figure 2 1 4 Drill another 5 16 hole on the wall stud for the U hook as shown in Figure 2 1 5 Screw in the three...

Страница 7: ...e forced into the pipe and result in clogged gas valves 6 The supply system must include a manual shut off valve a union in the line and a plugged 1 8 NPT tap The tap should be accessible for test gauge connections upstream of the gas supply connection to heater 7 Include a drip leg trap in the supply line The purpose of the drip leg is to prevent moisture and contaminants in the gas supply from e...

Страница 8: ...f your pilot will not stay lit try cleaning it Use a can of compressed air such as is used to clean a computer to blow dust out of the pilot assembly Sometimes just blowing air back through the pilot will get rid of the dirt If that fails to solve the problem remove the wire clip that holds the metal strip onto the pilot assembly Remove the cover and blow any dust out Reassemble and check for prop...

Страница 9: ...ic switch do not use any telephone in your building Immediately call your gas supplier from a neighbor s telephone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand do not try to repair it Call a qualified service person Force...

Страница 10: ...etting OFF OFF P 1 2 3 MODEL TYPES CK18M 4 NG CK18M 4 LP PIEZO IGNITOR PIEZO IGNITOR MODEL TYPES CK 30M 4 NG CK 30M 4 LP BURNER LIGHTING SEQUENCE one radiant Setting 1 O FF P 1 2 3 Setting 2 Three radiant O F F P 1 2 3 one radiant Setting 1 O FF P 1 2 3 one radiant Setting 2 O F F P 1 2 3 Setting 3 O F F P 1 2 3 two radiants Setting 3 Five radiants O F F P 1 2 3 ...

Страница 11: ...ction firmly Replace thermocouple Replace gas valve BURNER DOES NOT LIGHT Pilot stays lit Burner orifice clogged Burner orifices not correct size Extremely low inlet gas pressure Gas valve is defective Clean or replace orifices Replace with correct size Contact gas supplier Replace gas valve IMPROPERBURNERPATTERN Slight smoke or odor during initial operation Residues from manufacturing process or ...

Страница 12: ...sunstar corcho T Convertido 1 13 3 08 10 27 P gina 12 Composici n C M Y CM MY CY CMY K 12 MODELS CK18M 4 LP Propane Gas CK18M 4 NG Natural Gas 1 22 2 3 4 5 6 7 16 15 17 18 21 19 20 14 30 28 29 27 ...

Страница 13: ...r corcho T Convertido 1 13 3 08 10 27 P gina 13 Composici n C M Y CM MY CY CMY K 13 30 21 19 20 18 17 16 15 14 13 11 9 12 10 9 8 7 4 6 2 5 1 27 28 29 CK30M 4 LP Propane Gas CK30M 4 NG Natural Gas 23 24 25 26 ...

Страница 14: ...sunstar corcho T Convertido 1 13 3 08 10 27 P gina 14 Composici n C M Y CM MY CY CMY K 14 MODELS CK18M 4 LP and CK30M 4 LP Propane Gas CK18M 4 NG and CK30M 4 NG Natural Gas 32 33 34 35 36 37 38 39 40 41 ...

Страница 15: ...1 4359101 T Connector CK30M 11 4358559 4358559 Tubing Valve Third Setting 12 4358558 4358558 Tubing valve first setting 13 4358563 4358563 Tubing Third Setting Right 14 4358564 4358564 4358564 4358564 Tubing Regulator to Valve 15 4359601 4358900 4359601 4358900 Valve 16 4358560 4358505 Tubing Valve to ODS 17 4358800 4358800 4358800 4358800 Cotter Clip 18 4360001 4360001 4360001 4360001 Valve Suppo...

Страница 16: ...sunstar corcho T Convertido 1 13 3 08 10 27 P gina 16 Composici n C M Y CM MY CY CMY K 16 PN 43126170 22 130 177 Rev d ...

Отзывы: