www.sunred.nl
HEATER STAND AND LOCATION
The garden table heater is primarily for outdoor use only.
Always ensure that adequate fresh air ventilation is provided.
Always maintain proper clearance to non protected combustible
materials, i.e. top 45 cm and sides 60 cm minimum.
Garden table heater must be fixed on a stable and strong table made of
non-flammable materials such as wood
、
stone
、
glass
、
metal
、
etc.
Height of the table must be 85cm in minimum.
Never operate heater in an explosive atmosphere like in areas where
gasoline or other flammable liquids or vapors are stored.
Distance between gas cylinder and garden table heater must be 1m
in minimum.
GAS REQUIREMENTS
Use propane
,
butane or their mixtures gas only.
The pressure regulator
and
hose
assembly
to be
used must conform to local standard codes.
The installation must conform to local codes, or in the
absence of local codes
,
with
the standard for the
storage and
handling of liquid
petroleum gases.
A dented, rusted
or damaged
tank
may be
hazardous and should
be
check
ed by
your tank
supplier.
Never
use a propane
tank with
a damaged
valv
e connection.
The
tank
must be arranged to
provide
for vapor
withdrawal from the
operating c
ylinder.
Never connect an unregulated
tank to the
heateR
LEAK
AGE
TEST
Gas connections on
the heater
are leak tested at the
factory prior to shipment.
A complete
gas tightness
check
must be
performed at the
installation
site due to possible mishandling in shipment or
excess
ive
pressure being
applied
to the heater.
Make
a soap solution of one part
liquid
detergent
and one
part
water. The soap
solution can
be applied
with
a
spray bottle, brush or rag. Soap
bubbles
will
appear
in
case
of a leak.
The heater must be checked
with a full cylinder.
Make
sure the safety control
valve is
in the OFF position.
Turn the gas supply ON.
In case of a leak, turn off the
gas supply. Tighten any
leaking fittings, then turn the gas supply
on
and re-
check
.
Never leak test
while
smoking.