MAXEON SOLAR TECHNOLOGIES, LTD.
537620 Rev.F
©2022 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this document are subject to change without notice.
5
Maximum Altitude
: AC Modules can be installed in locations with a maximum
of 2000 meter above sea level.
Operating Temperature:
AC Modules must be mounted in environments that
ensure that the modules will operate within the following maximum and
minimum temperatures:
Max. Operating Cell Temp.
+85°C
Max. Operating microinverter Temp.
+ 60°C
Max. AC Module Ambient Temp.
+50°C
Min. AC Module Operating Temp.
−
40°C
Design Strength:
AC Modules are designed to meet a maximum positive (or
upward, e.g. wind) and negative (or downward, e.g. static load) design pressure
when mounted in the mounting configurations specified in Table 1 and 2 for the
details on load ratings and mounting locations. AC Modules have also been
evaluated to IEC 61215 for a positive or negative design load of 3600 Pa with a
1.5 Safety Factor.
When mounting modules in snow-prone or high-wind environments, special care
should be taken to mount the modules in a manner that provides sufficient design
strength while meeting local code requirements.
Important!
The following image and tables show where to mount in module
frame and the allowable load ratings corresponding to the mounting zones
chosen. To use the tables, identify the two mounting zones in which you wish to
mount. You may choose to mount at any location in zones A, B, and C, as long as
the mounting points are symmetric about one axis of the module. Identify the
combination of mounting zones you have chosen in the table and then refer to
the corresponding load rating. Note also that load ratings are different for
modules supported by rails; versus systems that attach modules underneath the
module frame or without rail support.
Table 1. Design Load Ratings (Tested with FOS=1.5 Safety factor)
Mounting
Method
Mounting
Zone
Wind (up and down)/ Snow (down)
(in Pa)
MAX5/MAX6 RES AC
P3 RES AC
Rail
Supported
w/o Rail
Support
*
Rail
Supported
w/o Rail
Support
*
Top
Clamp
BB
2700/
5400
2400/
3600
1600/
3600
1600/
2400
CC
1700/
1600
1600/
1600
1600/
3600
1600/
2400
AA
1600/
2400
1600/
1600
1600/
4000
1300/
1600
AB
1600/
1600
1600/
1600
NA
NA
AC
1600/
2400
1600/
1600
NA
NA
EE
NA
1600/
1600
NA
1000/
1600
Bolt
BB
3600/
6000
3600/
3600
NA NA
CC
2800/
2800
2800/
2400
AA
2000/
3000
2000/
2000
AB
1700/
2800
1600/
1600
AC
2000/
3000
2000/
2000
DD
DO NOT MOUNT
*
Without Rail support means end mounted in long or short side frame.
Fig.1 With Rail Support
For Maxeon 5 and Maxeon 6 RES AC:
For Performance 3 RES AC:
Additional Authorized Operating Environments:
Modules can be mounted in the following aggressive environment according to
the test limits mentioned below:
Salt mist corrosion testing: IEC 61701 Severity 6
Ammonia Corrosion Resistance: IEC 62716 Concentration: 6,667 ppm
Excluded Operating Environments
Certain operating environments are not recommended for SunPower AC
modules, and are excluded from the Maxeon Solar Technologies Limited
Warranty for these modules. Maxeon’s modules should not be mounted a site
where it may be subject to direct contact with salt water, or other aggressive
environment. Maxeon’s modules should not be installed near flammable liquids,
gases, or locations with hazardous materials; or moving vehicles of any type.
Contact Maxeon Solar Technologies if there are any unanswered questions
concerning the operating environment.
5.2 Mounting Configurations
Modules may be mounted at, appropriate orientation to maximize sunlight
exposure.
In order to prevent water from entering the junction box (which could present a
safety hazard), modules should be oriented such that the junction box is in the
uppermost position and should
not
be mounted such that the top surface faces
downward.
In addition, ensure the module orientation also prevents the microinverter from
direct exposure to rain, UV and other harmful weather events (ice/snow).
We also want to remind that the watertightness is not ensured by the modules
but by the mounting system and that drainage should be well designed for AC
modules. Maxeon recommends for a good performance of the system (reduction
of soiling effect/water pooling) a minimum of 5° tilt angle.