4 Installation Guide
User Manual
24
Make sure that the nuts have been screwed into place. If the cable
conductor has not been connected firmly, long-time work may burn the
terminal. Stranded flame-retarded copper wire shall be used, and its size
shall be over the recommended value as described in 8.1.2.
Nuts of water-proof terminals must be screwed correctly and firmly.
Otherwise, water leakage can damage the PVS.
4.3.6 Ground wiring and connections
Ground cables shall be connected correctly and firmly. Otherwise:
The electric shock caused by a malfunction can lead to lethal damage.
The device can be damaged when lightning.
Relevant standards must be observed.
Ground cables must be connected firmly with both device and ground
terminals.
Ground resistance shall be measured after finishing ground connections,
and the measured values should not be over 1Ω.
Step 1
Loosen the union nuts of “
” water-proof terminals.
Step 2
Insert the green-yellow wire from the device outside into the “
”
water-proof terminal, then pull the wire and connect it to the inner terminal.
Enough wire bending space should be ensured.
Step 3
Strip off both protection and insulation layers, with approx. 12mm conductor
length.
Step 4
Loosen the tightening bolt of “
” terminal with the help of a screwdriver.
Step 5
Insert ground cable through the opening and screw the tightening bolts
tightly. Firm the cable onto the cable support bar and enough cable bending
space shall be ensured.
Step 6
Tighten the nuts of water-proof terminal clockwise. Ground wirings have
been finished.
4.3.7 Communication Connections
Refer to the figure below for communication terminals inside the combiner box.