“Q(P)” Mode
The PF of the inverter output varies in response to the output power of the inverter.
table 8-3 “Q(P)” Mode Parameter Descriptions:
Parameter
Explanation
Default
Range
DE
AU
Q(P) Curve
Select corresponding curve ac-
cording to local regulations
A
A, B, C
*
QP_P1
Output power at P1 on the Q(P)
mode curve (in percentage)
20%
25%
0% ~ 100%
QP_P2
Output power at P2 on the Q(P)
mode curve (in percentage)
50%
20% ~ 100%
QP_P3
Output power at P3 on the Q(P)
mode curve (in percentage)
100%
20% ~ 100%
QP_K1
Power factor at P1 on the Q(P)
mode curve
1
Curve A/C: 0.8 ~
1
Curve B: - 0.6 ~
0.6
QP_K2
Power factor at P2 on the Q(P)
mode curve
1
QP_K3
Power factor at P3 on the Q(P)
mode curve
0.95
0.90
QP_Enter-
Voltage
Voltage percentage for Q(P)
function activation
105%
100% ~ 110%
QP_
ExitVoltage
Voltage percentage for Q(P)
function deactivation
100%
90% ~ 100%
QP_
ExitPower
Power percentage for Q(P) func-
tion deactivation
20%
1% ~ 100%
QP_
EnableMode
Unconditional activation/deacti-
vation of Q(P) function
Yes
Yes / No
* Curve C is reserved and consistent with Curve A currently.
figure 8-4
Q(P) Curve
“Q(U)” Mode
The reactive power output of the inverter will vary in response to the grid voltage.